Specification - LG ATNH24GPLED[UT24 NPD] Service Manual

Cassette-type air conditioner
Table of Contents

Advertisement

1. Specification

Indoor
Indoor Unit Type
Model
Decorative Panel Model
Power Supply
Current
Nominal Running Current
Fan
Motor Type
Fan Type
Motor Output(W) x No. of Unit
Air Flow Rate
(H / M / L)
External Static Pressure
Capacitor
Drive
Coil
Row x Column x FPI
Dimensions
Body
(W x H x D)
Decorative Panel
Net Weight
Body
Decorative Panel
Air Filter
Sound Level (H / M / L)
Piping
Liquid
Connections
Gas
Drain(OD/ID)
Dehumidification Rate
Safety Devices
Temperature Sensor
Referigerant
Referigerant Control
Connectable Outdoor Unit
Power and Transmission Interunit Cable
Note:
1. Capacities are based on the following conditions:
Cooling: - Indoor Temperature 27°C(80.6°F) DB/19°C(66.2°F) WB
- Outdoor Temperature 35°C(95°F) DB/24°C(75.2°F) WB
Heating: - Indoor Temperature 20°C(68°F) DB/15°C(59°F) WB
- Outdoor Temperature 7°C(44.6°F) DB/6°C(42.8°F) WB
Piping Length - Interconnecting Piping Length 7.5m
- Level Difference of Zero
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes
ATNH24GPLED
[UT24 NPD]
PT-UMC
Ø / V / Hz
1/220~240/50, 60
A
BLDC
Turbo Fan
60*1
CMM
16.5/14.7/13.0
cfm
582/519/459
mmAq
-
µF / Vac
-
Direct Drive
2R*8C*19FPI
mm(inch)
204 * 840 * 840
mm(inch)
25*950*950
kg (lbs)
21
kg (lbs)
5
Long life filter
dB(A)+3
39/37/34
mm (inch)
9.52(3/8)
mm (inch)
15.88(5/8)
mm
32/25
l/h
2.1
Thermistor
R-410A
EEV(Outdoor Unit)
Single A
No. x mm
2
4*0.75
- 2 -
Cealing Concealed Duct
ATNH30GPLED
[UT30 NPD]
PT-UMC
1/220~240/50, 60
BLDC
Turbo Fan
60*1
19/17.3/14.7
670/610/519
-
-
Direct Drive
2R*8C*19FPI
204 * 840 * 840
25*950*950
21
5
Long life filter
43/40/37
9.52(3/8)
15.88(5/8)
32/25
2.5
Fuse, Thermal protector for fan motor
Thermistor
R-410A
EEV(Outdoor Unit)
Single A
4*0.75
ATNH36GNLED
[UT36 NND]
PT-UMC
1/220~240/50, 60
BLDC
Turbo Fan
124*1
24/21.5/19
847/759/671
-
-
Direct Drive
2R*10C*19FPI
246 * 840 * 840
25*950*950
23.5
5
Long life filter
43/40/37
9.52(3/8)
15.88(5/8)
32/25
2.7
Thermistor
R-410A
EEV(Outdoor Unit)
Single A
4*0.75
Conversion Formula
kW = Btu/h x 0.0002931
cfm = CMM x 35.3
LGE Internal Use Only

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents