Combustion Air Supply And Ventilation - American Water Heater Flame Guard Safety System Installation Instructions And User Manual

Gas water heater with the flame guard safety system
Table of Contents

Advertisement

Table 1
Natural Gas Pipe Capacity Table (Cu. Ft./Hr.)
Capacity of gas pipe of different diameters and lengths in cu. ft. per hr. with pressure drop of 0.3 in. and specific gravity
of 0.60 (natural gas).
Nominal Iron Pipe
Size, in.
10
1/2
132
3/4
278
1
520
1-1/4
1050
1-1/2
1600
After the length of pipe has been determined, select the pipe size which will provide the minimum cubic feet per hour
required for the gas input rating of the water heater. By formula:
Cu. Ft. Per Hr. Required=
The gas input of the water heater is marked on the water heater data plate. The heating value of the gas (BTU/FT )
may be determined by consulting the local natural gas utility.
Table 2
LP Gas Capacity Table
Maximum capacity of pipe in thousands of BTU per hour of undiluted liquefied petroleum gases (at 11 inches water
column pressure). Based on a pressure drop of 0.5 inch water column.
Nominal Iron Pipe
Size, in.
10
1/2
275
3/4
576
1
1071
1-1/4
2205
Example: Input BTU requirement of the water heater 100,000 BTUH.
Additional tables are available in the latest edition of the "National Fuel Gas Code", ANSI Z223.1.
Combustion Air Supply and
Ventilation
Carbon Monoxide Warning
Follow all the local and state codes or, in
the absence of local and state codes, the
"National Fuel Gas Code", ANSI Z223.1
(NFPA 54)- latest edition to properly
install vent system.
Failure to do so can result in death,
explosion, or carbon monoxide poisoning.
Important: Air for combustion and ventilation must not
come from a corrosive atmosphere. Any failure due to
corrosive elements in the atmosphere is excluded from
warranty coverage.
The following types of installation (not limited to the
following) will require outdoor air for combustion due to
chemical exposure and may reduce but not eliminate
the presence of corrosive chemicals in the air:
beauty shops
photo processing labs
buildings with indoor pools
20
30
40
50
92
73
63
56
190
152
130
115
350
285
245
215
730
590
500
440
1100
890
760
670
Gas Input of Water Heater (BTU/HR)
Heating Value of Gas (BTU/FT³)
20
30
40
189
152
129
393
315
267
732
590
504
1496
1212
1039
Total pipe length, 80 feet = 3/4" IPS required.
Length of Pipe, Feet
60
70
80
90
50
46
43
40
105
96
90
84
195
180
170
160
400
370
350
320
610
560
530
490
Length of Pipe, Feet
50
60
70
80
114
103
96
89
237
217
196
185
448
409
378
346
913
834
771
724
water heaters installed in laundry, hobby, or
craft rooms
water heaters installed near chemical storage
areas
Combustion air must be free of acid-forming chemicals
such as sulfur, fluorine, and chlorine. These elements
are found in aerosol sprays, detergents, bleaches,
cleaning solvents, air fresheners, paint, and varnish
removers, refrigerants, and many other commercial and
household products. When burned, vapors from these
products form highly corrosive acid compounds. These
products should not be stored or used near the water
heater or air inlet.
Combustion and ventilation air requirements are
determined by the location of the water heater. The
water heater may be located in either an open
(unconfined) area or in a confined area or small
enclosure such as a closet or small room. Confined
spaces are areas with less than 50 cubic feet for each
1,000 BTUH of the total input for all gas-using
appliances.
100
125
150
175
38
34
31
28
79
72
64
59
150
130
120
110
305
275
250
225
460
410
380
350
90
100
125
83
78
69
173
162
146
322
307
275
677
630
567
200
26
55
100
210
320
3
150
63
132
252
511
7