Download Print this page

Fogmaker Universal User Manual page 2

Water-mist fire extinguisher for permanent installation.

Advertisement

Fogmaker
Universal
Fogmaker
is a registered trade mark of the fire extinguisher described in this manual. It is designed for
extinction of burning petrol, diesel, oil etc. in engine rooms or other enclosed spaces. The extinguisher
uses a cold water-mist, which reduces the temperature very effectively. At the same time it drives out
the air, so that the oxygen level is reduced. Full effect is obtained when the extinguishant is vaporized.
Fogmaker
Universal consists of the following parts:
General description
Installing the Cylinder
Valve Hose
Release Valve
Manual Activation
Electrical Activation
Pneumatic Activation - Firetrace
Pipes
Couplings
Firetrace Components
Nozzles
Double-assembled Extinguisher
Cover Boxes
Installations in Racing Cars
Functionality Check after Installation
Measures in the Event of Fire
Measures after Fire
Checklist Schedule
Restoring the Function after a Fire
Winter Storage
Technical Data
The pipes are not exposed to pressure until the release valve has been activated.
Fogmaker
Universal, User Manual, Page 2 (20)
User Manual
Section 1.1
Section 1.5
Section 2.2
Section 2.1
Section 3.1
Section 3.2-3.3
Section 3.4
Section 4.1-4.2
Section 4.3-4.3.2
Section 4.5
Section 4.6
Section 5
Section 5
Section 5.3
Section 6
Section 7
Section 8
Section 9
Section 10
Section 11
Section 12
Edition 2002
Fogmaker
Universal
12. Technical Data
Type
Diameter excl. assembly fittings
Maximum measure from wall incl. assembly fittings
Maximum width incl. assembly fittings
Length (height) incl. valve
Hole distance on assembly fittings
We i g h t
Filled cylinder incl. assembly fittings (approx. kg)
Volume, pressure
Volume, extinguishant (approx. litres)
Volume, driving gas (approx. litres)
Load pressure (at +20 o C)
Test pressure, cylinder (bar)
Materials
Cylinder
Assembly fittings
Valve
Anodizing, all aluminium parts, interior & exterior
Discharge time (approx, seconds)
2 nozzles
4 nozzles
6 nozzles
8 nozzles
10 nozzles
12 nozzles
Nozzle flow at 100 bar
Other specifications
Driving gas
Extinguishant
Anti-freeze temperature (standard)
Functionality tests and technical approvals:
Institute
SAQ Kontroll AB
Pressure vessel approval
Swedish National Testing and Research Institute (SP)
Swedish Administration of
Shipping and Navigation Regulations 1996-01-11
International Car Sport Federation (FIA)
Homologation No. Ex.001.97, Techn. List No. 16
Swedish Administration of
Shipping and Navigation
Leisure boats, engine compartment < 5 m
3
Swedish Fire Safety Association (SBF)
Approval of extinguishing capacity in peat loader
Fullscale test (SBF) for homologation with
regard to water quantity.
Approval extinguishing capacity 1.2 litres/m 3
Fogmaker
Universal, User Manual, Page 19 (20)
User Manual
Universal 33
Universal 40
Measures (mm)
Measures (mm)
152
152
165
170
152
390
400
445
w 350, h 280 (M8)
1 1
2 3
3.3
4.0
6 6
8 0
100-105 bar
100-105 bar
144
144
Extruded durable aluminium
Aluminium, stainless stell fastening clamps
Brass, components of stainless steel
Min 20 m
Min 20 m
120
6 0
7 8
4 0
5 2
3 0
3 9
Fogmaker 66
Fogmaker 80
4 8
6 2
4 0
5 2
Approx. 80 litres/hour per nozzle
Nitrogen
Water, antifreeze and film-forming agents
-35
o
C
Standard
Date
AFS 1994:39
97-02-12
(-40/+65
C)
o
Extinguishing test
96-06-18
in 5 m
space
3
Art. 253 Safety Equipment 96-12-02
(Groups N, A, B, ST)
Type approval
97-02-04
RUS 127
98-05-18
SBF 127
01-09-15
SBF 127
01-09-15
Edition 2002