This concept allows total electrical heat tracing control configured to the needs of the customer. The TC 816 hardware is based on electronic modules. With this approach the TC 816 can be set up for a huge variety of control tasks required for all electric heat tracing concepts Thermon has to offer.
TC 816 Operation Manual The TC 816 for Process Temperature Maintenance The enclosure of the TC 816 is constructed to be mounted on the back plane of a panel. The enclosure facili- tates 6 slots for electronic modules, each having its particular task.
The advantage is, that off the shelf Solid State relays can be connected to the TC 816 so switching capacity of a TC 816 system is only limited by the panel construction parameters like feeding power, cooling capacity in the panel.
The TCD 01 tracing control display allows the operator to have full control over the heat tracing circuits which are controlled by the connected TC 816 temperature controllers. The TCD 01 is the host on the RS 485 data communication bus. It searches on the communication bus for TC 816 heat tracing temperature controllers which need to have their own unique communication address (to be set by DIP switches on the AF TC4 tracing central processing module).
TCD 01 System Alarm Light Illuminates when the hardware controlled self check detects a program stop in the TCD 01 tracing control display ® THERMON…The Heat Tracing Specialists Page 8 of 42 Operation Manual 0503 E TC 816...
• having setup the hardware wiring of the RS 485 data communication bus • setting the communication address of the connected TC 816 controllers • and applying the 24 Vdc power supply The TCD 01 tracing control display illuminates yellow and looks as below: Figure 4.2...
SELECTION you can select the appropriate parameter to be changed. By pressing the buttons below SETPOINT you can change the values of the parameters. ® THERMON…The Heat Tracing Specialists Page 10 of 42 Operation Manual 0503 E TC 816...
: means no password protection of parameters NOTE: The password must always be set in case a TC 816 configured as Heat Tracing Cable Temperature Limiter is connected to the TCD 01. It ensures that all trips of that safety device can only be acknowl-...
The password value is entered with the ENTER button . If the password is correct the TCD 01 continues to the desired Parameter display or to the General Settings Menu. ® THERMON…The Heat Tracing Specialists Page 12 of 42 Operation Manual 0503 E TC 816...
Data Communication Bus Search After the Start-Up screen is left automatically or the General Settings Menu has been left by pushing the ac- knowledge button, the TCD 01 starts searching the RS 485 communication bus for connected TC 816 heat tracing temperature controllers.
Page 14
TCD 01 with the original circuit numbers. After choosing CONFIRM SKIP the TCD 01 automatically switches to heat tracing circuit display. ® THERMON…The Heat Tracing Specialists Page 14 of 42 Operation Manual 0503 E TC 816...
TCD 01 Tracing Control Display: Heat Tracing Circuit Display for three phase current display By pressing the buttons below CIRCUIT you can scroll through the heat tracing circuits. ® THERMON…The Heat Tracing Specialists Operation Manual 0503 E TC 816 Page 15 of 42...
-line) , using: Zone 17 of TC 816 controller with communication address 1. The TC 816 automatically assigns Zone 17 to Zone 1 of the same controller if at start-up an AF TIC Tracing Input module for load Current is detected.
• the assigned TC 816 communication address • the assigned controller Zone number of the applicable TC 816 controller. With CURRENT LIMITER values and values some analogue inputs are linked together as one circuit,...
RS 485 data communication bus. -OFF- Alarm condition monitoring disabled This situation occurs if the heat tracing circuit is set to manual or OFF (parameter P06) ® THERMON…The Heat Tracing Specialists Page 18 of 42 Operation Manual 0503 E TC 816...
Page 19
RS 485 data communication bus. -OFF- Alarm condition monitoring disabled This situation occurs if the heat tracing circuit is set to manual or OFF (parameter P06) ® THERMON…The Heat Tracing Specialists Operation Manual 0503 E TC 816 Page 19 of 42...
TCD 01 for three phase current display per tracing circuit, with firmware AZ 884, will not sound an audi- ble alarm. Also the applicable hardware alarm contacts of the AF TPA Thermon Power supply module AC trip (see TC 816 Hardware Configuration Guide).
TCD 01 for three phase current display per tracing circuit, with firmware AZ 884, will not sound an audi- ble alarm. Also the hardware high alarm contacts of the AF TPA Thermon Power supply module AC will trip (see TC 816 Hardware Configuration Guide).
Page 22
NOTE: Heat Tracing Cable Temperature Limiter will NOT switch the heat tracing back on unless the trip has been acknowledged the alarm status has disappeared. ® THERMON…The Heat Tracing Specialists Page 22 of 42 Operation Manual 0503 E TC 816...
7. The brackets around the set point will disappear automatically after about half a minute, if no buttons have been pressed. NOTE: Zones are not supervised when their set point is set to 0. ® THERMON…The Heat Tracing Specialists Operation Manual 0503 E TC 816 Page 23 of 42...
7. By pressing the buttons below you can select the appropriate parameter to be changed. Notice the change of parameter description in the top line. ® THERMON…The Heat Tracing Specialists Page 24 of 42 Operation Manual 0503 E TC 816...
Page 25
Those parameters can only be changed with the Paracon or Visual Fecon software through a PC connected to one of the data communication busses. ® THERMON…The Heat Tracing Specialists Operation Manual 0503 E TC 816 Page 25 of 42...
(heat tracing design) engineer. Changing Parameters P16 through P29 is possible by: 1. Set DIP 2 of 5 pole DIP switch of AF TC1/4/5 to ON-position (see TC 816 Hardware Configuration Guide). 2. Use one of the following tools to alter Parameters P16 through P29: - TCD 01 (single phase current display) with firmware AZ871 rev.2.41 or higher...
Measurement above the value set for parameter P02 triggers the respective zone HI-ALARM , this results • tripping the appropriate Hi-alarm contact on the AF TPA Thermon Power supply module AC • the green Hi-LED on the AF TPA module extinguishes Adjustment thresholds: 0...630...
This function is useful in order to avoid alarm trips in case for instance the equipment, traced with a suitable high temperature heating cable is steamed out. Adjustment thresholds: 0...999 Default value: ® THERMON…The Heat Tracing Specialists Page 28 of 42 Operation Manual 0503 E TC 816...
The right panel door can be addressed immediately by checking the circuit number in the panel drawings. In case the TC 816 controller is not configured for load current monitoring with an AF TIC Tracing Input mod- ule for load Current, the MCB/RCD status monitoring allows you to distinguish between: •...
- Zones 1 through 16 - unit in: not applicable • Valid for Limiter Zones - Zones 1 through 16, possibly of different TC 816 unit on same data communication bus - unit in: not applicable • Valid for Current Zones...
P07 determines the power output in % in case Parameter P06: MODE is set to “1” (manual operation). See chapter 4.2.6. The TC 816 regulates power output by switching ON and OFF (cycling) the supply voltage within a certain cycle time (parameter P25 CYCL TIME...
- unit in: 0,1 x A => value of 10 means 1 A OFFSET Parameter P10 allows field tuning of temperature and current by adjusting the Range: -50...+50 Default value: ® THERMON…The Heat Tracing Specialists Page 32 of 42 Operation Manual 0503 E TC 816...
- unit in: s (seconds) • Not valid for Limiter Zones • Not valid for Current Zones In case the TC 816 is configured for: • Frost Protection with Staged Start-Up control concept (default parameter P12 setting) • Parameter P18 (...
4.2.13 Parameter P13: Spare This Parameter has no function, it is a spare parameter to give the possibility of future functional expansion of the TC 816 heat tracing temperature controller. 4.2.14 Parameter P14: Spare This Parameter has no function, it is a spare parameter to give the possibility of future functional expansion of the TC 816 heat tracing temperature controller.
EN 50 014 standard for electrical equipment in hazardous area the limiter Zone needs to be utilised by a separate electronic controller. Within the TC 816 multi circuit temperature controller concept that can be any other TC 816 controller set up as a heat tracing cable temperature limiter (see chapter 1.1.3).
Not valid for Limiter Zones • Not valid for Current Zones CTR MODE Parameter P18 determines the TC 816 control mode ( ). Possible control modes are: • PID control: The temperature controller Zone controls according to PID (Proportional Integral &...
P HEAT With parameter P19 the proportional band ( ) of the controlled heat tracing circuit is set in % (per- centage). The resulting proportional band derives from the TC 816 globally set maximum temperature value (default 700 °C). P HEAT If, for example, is set to 10 % and the maximum temperature value is 700 °C, the effective pro-...
Default value: 4.3.8 Parameter P23: Spare This Parameter has no function, it is a spare parameter to give the possibility of future functional expansion of the TC 816 heat tracing temperature controller. ® THERMON…The Heat Tracing Specialists Page 38 of 42...
Not valid for Current Zones Control mode set to ON/OFF control, see chapter 4.3.3. HYSTER Parameter P24 determines the hysteresis ( ) of the ON/OFF control actions of the TC 816 heat tracing temperature controller. Adjustment thresholds: 1...30 Default value: 4.3.10 Parameter P25: CYCL TIME...
Adjustment thresholds: 1...16 (only if P28 is set to default) Default value: own Zone number MS MODE Note: This Parameter has no effect if P28 is not in default position. ® THERMON…The Heat Tracing Specialists Page 40 of 42 Operation Manual 0503 E TC 816...
Note: Never adjust this parameter for Zones 1 through 16 other than default (own Zone number) if Parame- SENSOR # ter P26 ( ) is not in default position. ® THERMON…The Heat Tracing Specialists Operation Manual 0503 E TC 816 Page 41 of 42...
In the most extreme case the actual circuit can be controlled by 16 temperature sensors. Parameter P28 determines the TC 816 Multi Sensor mode ( MS MODE ). Possible multi sensor modes are: •...
Need help?
Do you have a question about the TC 816 and is the answer not in the manual?
Questions and answers