Hitachi RAK-25PXA Installation Manual page 2

Split-unit indoor unit/outdoor unit
Hide thumbs Also See for RAK-25PXA:

Advertisement

THIS APPLIANCE MUST BE
WARNING
EARTHED.
Procedures of Wiring
When power supplies to Outdoor Unit
Indoor Unit
Outdoor Unit
ø1.6 or
(A) (B)
L N C D
ø2.0
Connecting Cord
AC 220-230V
1ø 50Hz
Detail of cutting the connecting cord
Indoor Unit
30mm
Green + Yellow
10mm
70mm
10mm
Outdoor Unit
50mm
50mm
10mm
10mm
Green + Yellow
Green + Yellow
Strip wires
WARNING
The naked part of the wire core should be 10mm fix it to
the terminal tightly. Then try to pull the individual wire to
check if the contact is tight. Improper insertion may burn
the terminal.
Be sure to use only wire specified for the use of air-
conditioner.
Please refer to the manual for wire connection and the
wiring technique should meet the standard of the electrical
installation.
There is an AC voltage drop between the LN terminal if the
power is on. Therefore, be sure to remove the plug from its
socket.
WARNING
Leave some space in the connecting
cord for maintenance purpose and be
sure to secure it with the cord band.
Secure the connecting cord along the
coated part of the wire using the cord
band. Do not exert pressure on the wire
as this may cause overheating or fire.
<1458L :
>
Wiring of The Indoor Unit
For wire connection of the Indoor unit, you need to remove the
front cover, the low cover under the body of the unit and
terminal cover.
Remove the cover from the terminal base and screw the cable.
Securely screw in the power cord
and connecting cord so that it will
D
Connecting
C
not get loose or disconnect.
Tightening torque reference value:
1.2 to 1.6 N m (12 to 16 kgf cm)
Excessive tightening may damage
the interior of the cord requiring
earth
teminal
replacement.
cover
screw
Method to remove the low cover
Pull at the
1
and
2
in the directions as shown by
arrows to remove the cover.
Wiring of the Outdoor Unit
Please remove the side cover for wire connection.
WARNING
If you cannot attach the side plate due to the connection
cord, please press the connecting cord in the direction to
the front panel to fix it.
Be sure that the hooks of the side cover fixed in certainly.
Otherwise water leakage may occur and this causes short
circuit or faults.
The connecting cord should not touch to service valve
and pipes. (it becomes high temperature in heating
operation.)
The remote controller
Remote
must be slide in
Controller
the remote controller
holder, in the direction
as shown in the figure,
Remote
until it hooks at the
Controller
lower end of the remote
Holder
controller holder.
Screw (2 pieces)
Checking for the electric source and the voltage range
Before installation, the power source must be checked and
necessary wiring work must be completed. To make the wiring
capacity proper, use the wire gauge list below for the wiring
from house distribution fuse box to the outdoor unit in consider-
ation of the blocked rotor current.
IMPORTANT
cover
Wire length Wire gauge
up to 6m
1.6mm
2
Earth terminal
2
up to 15m
2.5mm
2
up to 20m
4.0mm
Investigate the power supply capacity
IMPORTANT
and
other electrical conditions at the
installing location.
Fuse Capacity
Depending on the model of room air condi-
16A time
tioner to be installed, request the customer
to make arrangements for the necessary
delay fuse
electrical work etc.
The electrical work includes the wiring
work up the outdoor unit. In localities
where electrical conditions are poor, use of
a voltage regulation is recommended.
Install outdoor for the room air conditioner
within the reaching range of the line cord.
RAC Adapter
Wired remote controller
Fix the
wired remote
controller
RAC Adapter
cord and
cord
RAC adapter
cord by band.
Wired remote
controller cord
H-LINK
[For all optional part, please refer catalog for part number]
As for connecting to H-Link, a separately purchased RAC
Adapter is required.
To install the wiring the electrical box cover must be
opened.
Connect the connector of RAC adapter to CN7.
Assemble back the cover of electrical box.
Please refer to the respective user manual of RAC
Adapter for further details.
Please be careful not to damage lead wires by edge of
plate when connecting the optional parts.
WIRED REMOTE CONTROLLER
[For all optional part, please refer catalog for part number]
Connection to the electrical box:
Remove the cover of electrical box.
Connect the connector of Weekly Timer/wired remote
controller to CN9.
Assemble back the cover of electrical box.
Please refer to the respective user manual of Weekly
Timer/wired remote controller for further details.
Please be careful not to damage lead wires by edge of
plate when connecting the optional parts.

Advertisement

loading

This manual is also suitable for:

Rak-35pxaRac-35wxaRac-25wxa