Goodman HUM-FP Installation Instructions

High-capacity fan-powered flow-thru humidifier

Advertisement

Quick Links

No. 000-0752-077 • Rev 5/05 HBP
CAUTIONS:
1. Do not install the unit where freezing temperatures could occur, or where temperatures
could exceed 180ºF.
2. Do not install the unit on a furnace jacket.
3. Do not install the unit on a plenum face where the blanked-off ends of the cooling coil
4. Do not set humidity higher than recommended. Condensation damages may result.
IMPORTANT:
Placement
Information
1. Tape the template (this
entire sheet) onto the
warm air furnace plenum,
making sure it is level.
Mount the Model HUM-FP
Fan-Powered Flow-Thru
WARM
AIR PLENUM ONLY.
6. Place the mounting
frame into the plenum
opening so that the frame
hooks over the bottom of
the opening. Screw the
frame to the plenum.
shown in relation to the
AC cooling coils.
Toll-free Contractor Helpline: 888-SKUTTLE (758-8853)
Contractor E-line: techservice@skuttle.com
IO-310
Installation Instructions and Mounting Template for
WARNING:
or void all warranties.
ADDITIONAL WARNINGS:
1. Disconnect electrical power to the furnace before starting installation to avoid serious injury or electrocution.
2. Use care when cutting plenum openings and handling ductwork. Sharp edges may cause serious injury.
3. Do not cut or drill any air conditioning or electrical accessories during installation. Electrocution is possible if you
come in contact with a live electrical wire. Blindnes can occur if refrigerant contacts your eyes.
STEP-BY-STEP INSTALLATION INSTRUCTIONS
2. Trace around the
template. (Cutout size is
13-1/8" wide by 16-1/2"
long.) Remove the template.
Accurately cut the plenum
opening.
7. Stand
the evapo-
rator pad
upright with
the black index mark on
top. Make sure the wick is
seated securely in the drip
tray.
Goodman® is a registered trademark of Goodman Manufacturing Company, L. P.
Amana® is a trademark of Maytag Corporation and is used under license to Goodman Company, L. P.
USE THIS INSTRUCTION
SHEET AS A TEMPLATE.
Width of cutout (13-1/8") is equal to the
width of this sheet.
Length of cutout (16-1/2") is equal to the
length of this sheet.
Model HUM-FP
5. Do not set humidity up to recommended levels if there is condensation on the inside
windows of any living space. Condensaion damage may result.
6. Do not install the unit on any plenum where static pressure exceeds 0.4" W.C.
7. Do not install the unit where water pressure exceeds 125 psi. Leakage may result.
codes, ordinances and regulations.
3.
control wires by grasping
and pulling straight out.
8. Place the drip tray on
top of the pad. Reinstall
the evaporator pad and
drip tray.
See Additional Instructions on Back
All rights reserved.
4. Remove the cover by
5. Pull out the drip tray
turning the thumb screw
and evaporator pad
(circled) counter clockwise
assembly by grasping the
Tilt and lift the cover
top lip and tipping out.
off the frame.
10. Position the humidistat
on either an interior wall of
the home or the return air
plenum of the furnace. In-
stall by following the instruc-
tions in the parts bag.
9. Reattach the cover
assembly by hooking it at
the top of the mounting
frame. Secure the cover
by turning the thumb
screw at the bottom clock-
wise
.
13-1/8
TEMPLATE
.
05/06

Advertisement

loading

Summary of Contents for Goodman HUM-FP

  • Page 1 Placement Information 1. Tape the template (this entire sheet) onto the warm air furnace plenum, making sure it is level. Mount the Model HUM-FP Fan-Powered Flow-Thru WARM AIR PLENUM ONLY. 6. Place the mounting frame into the plenum opening so that the frame hooks over the bottom of the opening.