OWN-GEN WaveNet Digital Monitoring System General Installation and User Manual Marine Generators | Marine Diesel Engines | Land-Based Generators...
0.45 kg (1.0 lb) * Use of industry standard CT required. ** The LCD display will exhibit color and response time changes at high and low temperatures respectively but will not be damaged as long as within Operating Temp. OWN-GEN 01/12...
In addition to the monitoring features, the WaveNet controller can be used to provide protective warnings or shutdowns. 1.1 THIS MANUAL This manual is divided into two sections: WaveNet Back View 1. Hardware installation 2. Operation / Confi guration OWN-GEN 01/12...
Page 6
Any damage should be reported to a Northern Lights representative after a thorough inspection has been completed. A shipping label affi xed to the shipping box includes a variety of product and shipping information, such as items and Customer numbers.
4.WaveNet is connected on a NMEA 2000 network. Installation must be made by an NMEA 2000 certifi ed technician. 3.2 WAVENET 12/24VDC SYSTEM OPERATION The WaveNet controller can be placed in either 12V or 24V electrical systems. OWN-GEN 01/12...
24VDC systems. The WaveNet comes preinstalled with the correct relays depending on the product number specifi ed when ordered. Contact Northern Lights if replacement relays are required. Relays for 12 or 24VDC system operation are as follows: • 22-42047 for 12VDC operation •...
Page 9
updated 1-17-12 WaveNet is connected on a NMEA 2000 network. Installation must be made by an NMEA 2000 certifi ed technician. Figure 1 - General WaveNet System Wiring Diagram...
Page 10
Option Coolant Level Switch Input D - BAT Input C - BAT Input B - BAT Input A - BAT Emer. Stop Allows Manual Emergency Stop (Open = Active) Ground Ground Ground Ground 1 Ground input to generate logic high. OWN-GEN 01/12...
Page 11
It is extremely important to connect each phase to the appropriate terminal location. Never misphase inputs. Always match terminal details to the matching terminal location The current transformers (CTs) negative leads must be terminated individually into the WaveNet AC Current connector. DO NOT CONNECT TOGETHER. OWN-GEN 01/12...
“Emergency Stop” when powered. Emergency Stop also forces the controller to the OFF mode. To prevent this ground the emergency stop input (pin 9) to ground (pin 12) on the digital input terminal. See Figure 1 on page 6. OWN-GEN 01/12...
AUTO mode by pressing the Info key, automatic starting will be enabled. If the engine is started, failures will be automatically detected allowing for safe engine operation. While in AUTO mode the controller will display engine temperature, battery voltage and engine hours. OWN-GEN 01/12...
The screen will automatically unlock after 10 minutes. 4.4 WAVENET START / STOP BEHAVIOR There are two ways to start the generator (start conditions): 1. Start key – Located on the WaveNet front panel. 2. Remote WaveNet panel Start key OWN-GEN 01/12...
Each menu has a “Back” selection. To go back to the previous menu scroll up to the Back selection and press the Enter key. When in the basic menu you can go back to the OFF mode by pressing the Stop key. OWN-GEN 01/12...
DC power is supplied to the controller. Two week memory storage is available in a completely charged controller clock. DC power is required to be supplied continually to the WaveNet for approximately 1 hour to allow a complete clock charge. OWN-GEN 01/12...
10-600s. Shorter is ideal to extend the backlighting life. Maintenance Read only. Displays the amount of hours until next service if this feature is enabled. If service is overdue the hours become negative. Not In Auto Disable Beep, Enable Beep OFF Mode Start Disable, Enable OWN-GEN 01/12...
AC current sensing indicating that the generator is not running. This could indicate something is wrong with the WaveNet. (See section 4.11 on page 20.) HIGH BATTERY Failure occurred due to high battery voltage. HIGH ENGINE TEMP Failure occurred due to high engine coolant temperature. OWN-GEN 01/12...
Page 19
These are internal WaveNet failures. Try power cycle int WaveNet. If the failure occurs repeatedly the unit could be defective. UNDER FREQUENCY The generator frequency is too low. UNDER SPEED The engine speed is too low. UNDER VOLTAGE The generator voltage is too low. OWN-GEN 01/12...
A solid yellow illuminated LED represents a High engine Yellow Temp Warning Condition Low Oil A solid red illuminated LED represents a Low Oil Press Solid Red Pressure Failure condition. Solid Yellow A solid yellow illuminated LED represents a Low Oil Yellow Pressure Warning condition. OWN-GEN 01/12...
Also, after the warning is displayed, instructions are displayed showing the user how to silence the warning. When in the AUTO or RUN modes the instructions are to press the Info key and when in the OFF mode press the Stop key. OWN-GEN 01/12...
Check for any overheating due to loose Check for any discoloration, melting or blistering connections. of any wiring or connections Perform regular testing of controller Perform regular testing of the controller to check for proper operation. OWN-GEN 01/12...
The 3 main line positions display the current available on-line genset controllers. Each line displays the on-line Genset Controller’s Name, State and the Status Mark. On the second line of the display, the relevant message of the selected genset controller, like warning, running detail etc., is shown. OWN-GEN 01/12...
The ON-LINE GENSET PARAMETER mode has 3 different pages corresponding to the on-line genset controller, the AUTO, RUN and FAIL states. Start and stop functionality is the same in this mode as the ON-LINE GENSET STATUS mode. Press the Info key to return to the ON-LINE GENSET STATUS mode. OWN-GEN 01/12...
673 AC Wire Harness 22-40575 673 DC Wire Harness 22-40570 WaveNet NMEA Panel Connector 22-40598 (for Remotes, use 22-40597) WaveNet is connected on a NMEA 2000 network. Installation must be made by an NMEA 2000 certifi ed technician. OWN-GEN 01/12...
40A. If installing lower amperage fuse protection be certain that current draw does not exceed the fuse current limit. Table 12 – WaveNet fuse part list. Fuse Description Manufacturer Part No. 40A, 32VDC Auto Fast Action Littlefuse-257040 OWN-GEN 01/12...