Lennox Hearth Products Montebello LSM40MN-2 Installation Instructions Manual page 32

Montebello direct vent gas fireplaces
Table of Contents

Advertisement

LENNOX HEARTH PRODUCTS • MONTEBELLO
SIT Millivolt Gas
Valve Shown
Pressure
Regulator
SIT Electronic Gas Valve
LO
HI
Pressure
Regulator
Millivolt & Electronic Gas Valves
Figure 57
Step 6. Refer to Figure 58 and remove the
pilot hood assembly to access the hexed pilot
orifice. Remove and replace the orifice with
the one provided with the kit.
32
DV GAS FIREPLACES
®
SIT Millivolt Pilot Assembly Shown
Remove
These
Components
Millivolt & Electronic Pilot Assemblies
Figure 58
Step 7. (Refer to Figure 56 on Page 31 and
Figure 59)
VERIFY ThE PROPER ORIFICE SIZE
BEFORE INSTALLING IT.
A. Remove the orifice from the manifold and
replace it with the one provided in the kit. See
the following table for orifice sizes for natural
and propane models. Figure 59 illustrates
the orifice. Use pipe joint compound or
Teflon tape on all pipe fittings before install-
ing (ensure propane resistant compounds
are used in propane applications, do not
use pipe joint compounds on flare fittings).
B. Retrieve the burner and slide the venturi tube
over the orifice. Set the burner assembly
into its position and secure it.
C. Reinstall the grate assembly.
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
(LSM40/45MN-2, LSM40/45MP-2, LSM40/45EN-2)
Thermopile
(on millivolt
pilot assem-
blies only)
Pilot
Orifice
SIT Electronic Pilot
Pilot
Orifice
• INSTALLATION INSTRUCTIONS
Burner Orifice Sizes
Elevation 0-4500 feet ( 0-1372 meters)
Model
Nat.Gas
drill size (inches)
drill size (inches)
LSM40-2
.1405" (#28)*
• H2286
LSM45-2
.161" (#20)*
• H2288
* Standard size installed at factory
Table 9
• Part /Cat. Number
Figure 59
Step 8. Reassemble the remaining components
by reversing the procedures outlined in the
preceding steps.
Step 9. Attach the conversion label provided
in the conversion kit to the rating plate on the
appliance.
Step 10. Turn on gas supply and test for gas
leaks.
Step 11. Attach manometer to the manifold
side pressure test fitting and verify manifold
pressure reads 3.5 inches water column (0.87
kPa) for natural gas, and 10.0 inches water
column (2.49 kPa) for propane gas.
ALWAYS TEST PRESSURES WITh ThE VALVE
REGULATOR CONTROL AT ThE hIGhEST
SETTING.
Propane
.086" (#44)*
• H2287
.093" (#42)*
• H4816