6. MAINTENANCE

6.1.
G
R
ENERAL
EMARKS
6.2.
C
LEANING THE
6.3.
C
LEANING THE
IMPORTANT!!
If the boiler is not to be used for a prolonged period, the
condensate trap should be filled before operating the
boiler. A shortage of water in the trap will temporarily
risk flue gasses escaping into the room.
P
E
RIMARY
XCHANGER
C
T
ONDENSATE
RAP
To ensure the validity of the 5 Year Guarantee, the boiler must be
serviced annually by a CORGI registered gas engineer.
MTS (GB) Limited will write to the householder as the boiler
becomes due for it's annual service.
With the letter will also be sent a 'Service Pack', this will include the
annual maintenance checklist to be completed and signed by the
CORGI registered engineer, also included in this pack may be a
component which must be replaced and the old one returned with all
documentation included in the 'Service Pack' to MTS (GB) Ltd.
See Section 10 for annual maintenance requirements.
N
: F
OTE
AILURE TO COMPLY WITH THE ANNUAL SERVICE
REQUIREMENTS WILL RESULT IN THE
.
BECOMING VOID
CLEANING THE EXHAUST SIDE
Access the combustion chamber (see section 7.3). Check that the
exhaust passages are clear; if there are deposits present, wash the
exchanger with compressed air, water or a vinegar-based detergent.
NOTE: it is possible to use a brush in order to mechanically remove
the residues.
Use of detergents:
-
soak the blades well
-
allow the detergent to act for about 20 minutes
-
rinse with a strong jet of water to remove the deposits (the
control panel must be kept closed)
-
make sure that there are no traces of detergents in the
exchanger.
CLEANING THE WATER SIDE
Use detergents that dissolve CaCO3. Leave to act for a short time
and then rinse. Make sure that the detergent does not remain inside
the exchanger.
To clean the condensate trap it is simply necessary to unscrew the
lower part of the condensate trap and clean it. Lastly, fill it with water
and replace the stopper.
6.4.
O
PERATIONAL
After having carried out the maintenance operations, fill the
heating circuit to a pressure of approx. 1.5 bar and release the
air from the system. Also fill the domestic hot water system.
-
Place the boiler in operation;
-
If necessary, release the air again from the heating system.
-
Check the settings and the correct functioning of all the
control, regulation and monitoring parts;
-
Check the seal and the correct functioning of the system for
expelling fumes/drawing of combustion air;
-
Check that the boiler ignites properly and carry out a visual
check on the burner flame;
-
Check the CO
values are correct (see Section 3.6.3)
2
5
YEAR GUARANTEE