Heat Controller RG-51G Service Manual page 16

With r-410a
Table of Contents

Advertisement

RG-51G Service Manual
Water drips from the unit.
Check whether the ambient humidity is too high.
Check whether the indoor outlet airflow foam is too wet, and louver drip.
Check if the indoor airflow foam is too wet and if water is dripping from the louver.
Check whether the unit is correctly installed.
Check whether the air outlet foam install normally.
Check whether the air outlet foam is install normally.
Check whether the foam of evaporator base is damaged.
Check whether the drain passage of evaporator is blocked. Replace if failed.
Fan motor speed will not change
Fan motor speed can't change.
Check whether the selector knob is damaged.
Check whether the selector is damaged.
Check whether the capacitor of fan motor is in the range from 95% to
105% of rated capacity. Replace the capacitor if failed.
Check the resistance of fan motor and replace if failed.
Room Air Conditioner with R-410A
15
Heat Controller, Inc.