Description:
These manual fire alarm call points have been designed for use
in hazardous locations and harsh environmental conditions. The
GRP enclosures are suitable for use offshore or onshore, where
light weight combined with a high level of corrosion resistance is
required.
Architects and Engineers Specifications
Fire alarm call points and push buttons for hazardous locations and harsh environments shall be UL Listed for Class
I, Division2, Groups A,B,C&D, and Class I, Zone 1&2 applications. They shall be constructed of lightweight, UV stable
glass reinforced polyester, shall be corrosion resistant, and shall meet NEMA 4x, NEMA 6, IP 66 & IP 67 environmental
requirements over a temperature range of -13°F to +131°F (-25°C to +55°C).
Actuation of the call point or push button shall require the opening of a flap and depression of an actuator. An actuated
unit shall remain latched until reset. A reset operation shall only take place through the use of a key.
ATEX
GOST
Fire Alarm Call Points, Hazardous Location
Features:
ATEX approved
★
UL Listed for USA and Canada
★
– Hazardous locations:
Class I, Div 2, Groups A-D
Class II, Div 2, Groups F & G
Class I, Zones 1 & 2, AExd IIC T4
– Ordinary locations: Audible-Signal Device
CSA Certified
★
NEMA 4x &6, IP66 and IP67
★
Certified temperature –13°F to +131°F (–25°C to +55°C)
★
Corrosion resistant GRP
★
Plastic break glass element available
★
Retained stainless steel cover screws
★
Optional lift flap
★
Key operated test facility on BG
★
BG and PB