Cooper Wheelock BG Manual

Fire alarm call points, hazardous location

Advertisement

Description:

These manual fire alarm call points have been designed for use
in hazardous locations and harsh environmental conditions. The
GRP enclosures are suitable for use offshore or onshore, where
light weight combined with a high level of corrosion resistance is
required.
Architects and Engineers Specifications
Fire alarm call points and push buttons for hazardous locations and harsh environments shall be UL Listed for Class
I, Division2, Groups A,B,C&D, and Class I, Zone 1&2 applications. They shall be constructed of lightweight, UV stable
glass reinforced polyester, shall be corrosion resistant, and shall meet NEMA 4x, NEMA 6, IP 66 & IP 67 environmental
requirements over a temperature range of -13°F to +131°F (-25°C to +55°C).
Actuation of the call point or push button shall require the opening of a flap and depression of an actuator. An actuated
unit shall remain latched until reset. A reset operation shall only take place through the use of a key.
ATEX
GOST
Fire Alarm Call Points, Hazardous Location

Features:

ATEX approved
UL Listed for USA and Canada
– Hazardous locations:
Class I, Div 2, Groups A-D
Class II, Div 2, Groups F & G
Class I, Zones 1 & 2, AExd IIC T4
– Ordinary locations: Audible-Signal Device
CSA Certified
NEMA 4x &6, IP66 and IP67
Certified temperature –13°F to +131°F (–25°C to +55°C)
Corrosion resistant GRP
Plastic break glass element available
Retained stainless steel cover screws
Optional lift flap
Key operated test facility on BG
BG and PB

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the BG and is the answer not in the manual?

Questions and answers

Summary of Contents for Cooper Wheelock BG

  • Page 1 Retained stainless steel cover screws ★ Optional lift flap ★ Key operated test facility on BG ★ Architects and Engineers Specifications Fire alarm call points and push buttons for hazardous locations and harsh environments shall be UL Listed for Class I, Division2, Groups A,B,C&D, and Class I, Zone 1&2 applications.
  • Page 2 Certified temp: BGUL: –13°F to +131°F (–25°C to + 55°C); PBUL: –13°F PB & BG Duty label – worded to Client’s requirements. Riveted on. t+131°F (–25°C to +55°C). PB (CSA): -58°F to +104°F (- PB & BG Tag label – worded to Client’s requirements. Screwed on.

This manual is also suitable for:

PbBg seriesPb seriesPbul4c6c4dsn7r

Table of Contents