A.O. Smith GPSX-50L Owner's Manual page 7

Power vented gas models with hot surface ignition & 2"/3"/4" pvc vent capability
Hide thumbs Also See for GPSX-50L:
Table of Contents

Advertisement

WARNING
VENT HOOD(S) MAY BE
EXTREMELY HOT DURING
OPERATION
3. A) MASONRY SIDE WALLS
Chisel an opening approximately one half inch larger than the
marked circle.
B) WOODEN SIDE WALLS
Drill a pilot hole approximately one quarter inch outside of the
marked circle. This pilot hole is used as a starting point for a
saws-all or sabre saw blade. Cut around the marked circle
staying approximately one quarter inch outside of the line. (This
will allow the vent pipe to easily slide through the opening. The
resulting gap will be covered up by the vent terminal cover
plates.) Repeat this step on inside wall if necessary.
This unit can vent through 2, 3 or 4 inch nonmetallic pipe and fittings.
Use the appropriate vent terminal for the size vent pipe being used.
The vent pipe installation can be started from either the blower
discharge or the termination wall. Keep in mind the total vent system
equivalent length (pipe and elbows) when installing the vent system.
(SEE VENT TABLES AND FIGURES ON PAGES 9-10.)
The vent terminal should be kept as close as possible to the outside
wall, but you need to allow at least 1.5 inches of pipe past the wall,
for the wall plate and vent terminal to mount on the pipe.
Before the vent terminal is installed, caulk (not supplied) around the
pipe on the exterior wall and install the wall plate (can be held to the
outside wall by placing some of the caulking on the back of the plate).
FIGURE 4
FIGURE 3
The wall plate is supplied for decorative purposes only and is
not a requirement for the vent termination (if not needed by the
installer).
SEQUENCE OF INSTALLATION
1. The Power Vent Models come with the blower assembly
installed.
2. After the unit is set in place, make sure the blower
assembly is still mounted securely. Also make sure there
is no damage to the blower.
3. Make sure there is no packing material in the discharge of the
blower or the intake of the dilution air restrictor. See Fig. 5.
4. Make sure that the plastic tubing is still attached from the
air pressure switch to the port on the blower housing.
5. Make sure the ON/OFF switch is in the OFF position and
that the outer harness is connected from the blower control
box to the connector on the bottom side of the gas valve.
If the outer harness is not factory installed, make sure the
ON/OFF switch is in the OFF position and then connect
the outer harness from the blower control box to the
connector on the right side of the gas valve.
7
FIGURE 5

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gpsx-50Gpst-75lGpsx series

Table of Contents