T-Link Compatibility Chart - DSC Network Alarm Communicator Installation Manual

Table of Contents

Advertisement

T-Link Compatibility Chart

Compatible DSC Control Panels
Maxsys PC4020
Power864 PC5020
TCP/IP Communicator
T-Link
TCP/IP Communication Routing / Receiver
Reporter IP V2.0
DRL-IP V1.0 *
Downloading Software
DLS-3 V1.3
Maxsys PC4020 V3.3
(with TCP/IP support)
Driver Pack
Power864 PC5020 V3.2
DLS-3 Driver
DLS-3 V1.3 service pack
System Administration Software
DLS-3 SA V1.3
DLS-3 SA V1.3 Service Pack 1
for Maxsys V3.31 support
DLS-3 SA V1.3 Service Pack 2
for Power864 v3.2 support
*NOTE:
The DLS software could be used with UL Listed installations only when a service per-
sonnel is on the site.
• Software V3.31 or higher
• Hardware Rev 04B
• Software V3.2 or higher
• Hardware Rev 03
• 10baseT TCP/IP communication module
• Static IP required per module
• Required for T-Link communications and DLS
• Supports 255 T-Link accounts, one DLS-3 and
one DLS-3SA at the same time.
• Not for UL Listed installations
• Static IP required for computer
• Required for T-Link communications and DLS
• Supports 255 supervised T-Link accounts, one
DLS-3 and one DLS-3SA at the same time.
• Static IP required per DRL-IP
• Required
• CD from distributor or free download from
dsc.com with a valid password
• Required
• Free download from dsc.com with a valid
password
• Required
• Free download from dsc.com with a valid
password
• Free download from dsc.com with a valid
password
• Required
• Kit with modem or PC4401 from distributor
• Required
• Included in the kit or free download from
dscsec.com/dls3drivers.htm
• Required
• Included in the kit or free download from
dscsec.com/dls3drivers.htm
5.2
Standard Connection with PC4020(CF)/PC5020(CF)
WARNING!
All circuits are supervised and power limited. Refer to Battery Lead and AC
Power Lead Routing for UL Listed Commercial Fire Systems diagram for wire
routing. Do not route any wiring over the circuit boards. Maintain at least 1"
(25.4mm) separation between circuit board and wiring.
A minimum of 1/4" (7mm) separation must be maintained at all points
between non power limited wiring and power limited wiring.
Refer to your control panel Installation Manual for any additional information.
Wiring T-Link to a DSC Compatible Control Panel
• Mount the T-Link using bracket or on the side of the cabinet.
• Secure the T-Link module to the cabinet using the supplied standoffs.
• With both AC and battery disconnected removed from the DSC control panel,
wire the T-Link to the panel using 4 wires from the PC-Link of the panel to the
"PANEL" connector on the T-Link.
• Wire the panel's AUX + and - to 12V and GND terminals of T-Link.
• Apply AC and DC to the main control panel. Both the T-Link and the panel
should power up.
• Do the necessary programming that is required.
NOTES: If a Bell/Siren is not going to be used, wire the Bell/Siren terminals
on the panel with a 1000 ohm resistor.
For Commercial Fire installation, when a bell/siren is used in the applica-
tion, it should be connected to the DSC module PC4702BP.
Please refer to the PC4020 Installation Manual. The keypad or any other
accessory connected to the Combus shall be connected within 3 feet / 0.9 m
and in conduit.
13