General: The AIM-3 is an outboard expansion module for use with the SAFEPATH control panels to expand the number of optional Remote Microphones (RM) from 1 to 3. The module is compatible with all SAFEPATH panels and Remote Microphones. The PCB assembly is mounted in an enclosure.
Operating Temperature 0° to +49° C, 32° to 120.2 ° F Storage Temperature -20° to 70° C, -4° to 158° F Humidity 85±5% @ 30±2° C Non-condensing Installation: AIM-3 Manual P83667 C Rev. C July 2003 Sheet 2 of 12...
Handle the board by its edges, and be careful not to twist or flex it. The AIM-3 is to be installed in a static free area and the user is to properly attach grounded wrist straps before touching any static sensitive areas.
The shield of each cable should be connected only at one end. Each shield of each cable that connects to the AIM-3 is to connect to the grounding points provided near the right edge of the chassis (see Figure 2).
Page 5
CONDUIT KNOCKOUTS 2 PLACES, BOTH ENDS 6.00" MOUNTING HOLES GROUND TERMINALS 11.00" MOUNTING HOLES Figure 2. AIM-3 Mounting NOTE: Drawing is not to scale. AIM-3 Manual P83667 C Rev. C July 2003 Sheet 5 of 12...
Page 6
Wiring Diagram with up to 3 Remote Microphones NOTE: If the AIM-3 is configured for less than 3 Remote Microphones, the +/- RM AUDIO terminals of the unused Remote Microphone port must be terminated with the supplied listed 10K ohm 1/4W resistor.
Page 7
Telephone Input Applications: The AIM-3 can be connected to an unused CO Port, a page port, an analog station port ( with TPI-100 ) or to a zone control (MCZ- 144 ). When it is used for telephone paging, it should only be used for telephone paging only and not for background music. The VOLUME adjust is used to set the telephone page volume.
Page 8
AIM-3 SWITCH CONFIGURATION: ANALOG STATION PORT SWITCH POSITION AUDIO ZONE 1 AUDIO MZEM-3 BOARD ONE WA Y ZONE CENTRAL A MP SEL. 1, SEL. 2 ON AS NEEDED ZONE A RXD/CC SEL. 3 POWER PHONE -24VDC RM/PHONE PHONE RMS-3 OF A IM-3...
Page 9
Operation: The AIM-3 polls the Remote Microphone stations to determine supervision and alarm status. Any trouble condition will light the amber LED. Follow the trouble shooting procedures if the LED is lit. The first Remote Microphone that is selected will have priority over the other two.
Page 10
PHONE SEL3 SEL2 SEL1 AUDIO POWER AUDIO POWER AUDIO POWER AUDIO RXD/CC POWER TB 4 PEAK Figure 8. AIM-3 Board Layout AIM-3 Manual P83667 C Rev. C July 2003 Sheet 10 of 12...
TROUBLESHOOTING: While AIM-3 is connected and powered up, switch SW1 positions SEL. 1, 2, 3 and PHONE to OFF. Switch ON as to be cofigured. Ve rify 1. Check +/- power connection from SAFEPA T H Panel to AIM-3. Power to 2.
(as determined by date code). Correction of defects by repair or replacement shall be at Wheelock's sole discretion and shall constitute fulfillment of all obligations under this warranty. THE FOREGOING LIMITED WARRANTY SHALL IMMEDIATELY TERMINATE IN THE EVENT ANY PART NOT FURNISHED BY WHEELOCK IS INSTALLED IN THE PRODUCT.