Download Print this page

Honeywell ML4125 Product Data page 5

Fast-acting, two-position actuators for heating, ventilation and air-conditioning applications

Advertisement

Installation
CAUTION
Device Malfunction Hazard.
Improper set screw tightening causes device
malfunction.
Tighten set screws with proper torque to prevent
damper shaft slippage.
CAUTION
Actuator Damage Hazard.
Using actuator as shaft bearing causes device
damage.
Use actuator only to supply rotational torque. Avoid
any side loads to actuator output coupling bearings.
To install actuator, proceed as follows:
1. Place actuator over damper shaft; and hold mounting
bracket in place. See Fig. 2.
2. Mark screw holes on damper housing.
3. Remove actuator and mounting bracket.
4. Drill or center-punch holes for mounting screws (or use
no.10 self-tapping sheet metal screws).
5. Turn damper blades to desired normal (closed) position.
6. Place actuator and mounting bracket back into position
and secure bracket to damper box with sheet metal
screws.
7. Tighten set screws securely into damper shaft using
minimum 30 lb-in., maximum 60 lb-in. torque. Use
1/8 in. or 3 mm Allen wrench (see Specifications for
details) to tighten set screws.
Wiring
WARNING
Electrical Power Hazard.
Line voltage can cause death or serious injury
and short equipment circuitry.
Disconnect power supply before installation.
CAUTION
Electrical Shock or Equipment Damage Hazard.
Low voltage can shock individuals or short
equipment circuitry.
Disconnect power supply before installation.
ML4125, ML4135, ML8125, ML8135 FAST-ACTING, TWO-POSITION ACTUATORS
IMPORTANT
See Fig. 4 through 6 for typical wiring diagrams.
L1
L2
M17585
VAC
VAC
BROWN
BLUE
BLACK
WHITE
RED
5
1. All wiring must comply with local electrical codes,
ordinances and regulations.
2. Voltage and frequency of transformer used with
ML8125 or ML8135 must correspond with the
characteristics of power supply and actuator.
3. Use wires rated for at least 75°C (167°F).
( )
R
W
24 VAC
( )
Fig. 4. Typical 24 Vac wiring.
( )
L1
R
W
120
( )
L2
M17589
Fig. 5. Typical 120 Vac wiring.
( )
L1
R
W
230
( )
L2
M17588
Fig. 6. Typical 230 Vac wiring.
Table 4. Color Translations.
G
F
BRAUN
BRUN
BLAU
BLEU
SCHWARZ NOIR
WEISS
BLANC
ROT
ROUGE
RED
BLACK
BLACK
WHITE
BROWN
BLUE
I
E
BRUNO
CAFE
AZZURRO AZUL
NERO
NEGRO
BIANCO
BLANCO
ROSSO
ROJO
63-2567—3