Fuel Consumption; Fuel Pipe Sizing - Rheem GEN12S Installation And Start-Up Manual

12000 / 15000 watt residential generator system
Hide thumbs Also See for GEN12S:
Table of Contents

Advertisement

Fuel Consumption

See Figure 7 for estimated fuel supply requirements at half
and full load for both natural gas and LP vapor.
Natural Gas*
1/2 Load
Full Load
12kW
102
15kW
140
* = Natural Gas is in cubic feet per hour
** = LP Vapor is in cubic feet per hour
Figure 7 — Fuel Supply Requirements
NPT
10ft
15ft
3/4"
346
293
1"
653
549
Natural Gas (sg=0.65)
Figure 8 — NATURAL GAS (NG) Pipe Size - Gas Flow Chart, in cubic feet per hour
NPT
10ft
15ft
3/4"
277
192
1"
428
360
Liquid Propane (LP) (sg=1.50)
Figure 9 — LIQUID PROPANE (LP) GAS Pipe Size - Gas Flow Chart, in cubic feet per hour
10
LP Vapor**
1/2 Load
Full Load
195
41
79
218
66
96
20ft
30ft
40ft
240
192
163
446
360
307
20ft
30ft
40ft
158
126
107
293
236
202

Fuel Pipe Sizing

Figures 8 and 9 provide the maximum capacity of pipe in
cubic feet of gas per hour for gas pressures of 0.5 psi or
less and a pressure drop of 0.3 in. water column. Specific
gravity of gas is shown.
Listed values compensate for a nominal amount of
restriction from bends, fittings, etc. If an unusual number of
fittings, bends, or other restrictions are used, please refer to
federal and local codes.
50ft
60ft
70ft
145
132
120
274
250
230
50ft
60ft
70ft
95
87
79
180
164
151
80ft
90ft
100ft
113
106
99
211
197
187
80ft
90ft
100ft
74
69
65
139
129
123