Indoor Unit
Power Supply
Cooling Capacity
Heating Capacity
Current
Nominal Running Current
Fan
Motor Type
Fan Type
Motor Output(W) x No. of Unit
Air Flow Rate
(H / M / L)
External Static Pressure
Capacitor
Drive
Coil
Row x Column x FPI
Dimensions (W x H x D) Body
Decorative Panel
Net Weight
Body
Decorative Panel
Air Filter
Sound Level (H / M / L)
Piping Connections
Liquid
Gas
Drain(OD/ID)
Dehumidification Rate
Safety Devices
Temperature Sensor
Referigerant
Referigerant Control
Connectable Outdoor Unit
Power and Transmission Interunit Cable
Note:
1. Capacities are based on the following conditions:
Cooling:
- Indoor Temperature 26.7˚C(80˚F) DB/19.4˚C(67˚F) WB
- Outdoor Temperature 35˚C(95˚F) DB/23.9˚C(75˚F) WB
Heating:
- Indoor Temperature 21.1˚C(70˚F) DB/15.6˚C(60˚F) WB
- Outdoor Temperature 8.3˚C(47˚F) DB/6.1˚C(43˚F) WB
Piping Length - Interconnecting Piping Length 7.5m
- Level Difference of Zero
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.
Ø / V / Hz
kW
Btu/h
kW
Btu/h
A
CMM
cfm
mmAq
µF / Vac
mm(inch)
mm(inch)
kg (lbs)
kg (lbs)
dB(A)+3
mm (inch)
mm (inch)
mm
l/h
No. x mm
2
Product Specifications

B-DMH18DB-1

1/208~230/60
2.63
9000
2.63
9000
0.5
BLDC
Cross Flow fan
15*1
7
247.1
-
-
Direct drive
2*15*20
870*270*153(34.2*10.6*6)
-
7(15.4)
-
Long life filter
31/27/21
6.35(1/4)
9.52(3/8)
20/13
1.2
Fuse
Thermistor
R-410A
EEV(Outdoor Unit)
Multi
4*0.75