York GY9 User's information, maintenance and Service Manual page 7

High efficiency tubular heat exchager series
Hide thumbs Also See for GY9 User's information, maintenance and:
Table of Contents

Advertisement

167808-UUM-A-1205
3 RED FLASHES:
This indicates
the normally
open pressure switch
contact did not close after the inducer was energized.
This could be
caused by a number of problems: faulty inducer, blocked vent pipe, bro-
ken pressure switch hose or faulty pressure switch.
4 RED FLASHES:
This indicates that a primary or auxiliary limit switch
has opened its normally closed contacts. With this fault code the control
will operate the supply air blower and inducer. This condition may be
caused by: dirty filter, improperly
sized duct system, incorrect blower
speed setting, incorrect firing rate or faulty blower motor.
5 RED FLASHES:
This fault is indicated if the normally closed contacts
in the rollout switch opens. The rollout control is manually reset. If it has
opened, check for proper combustion air, proper inducer operation, and
primary heat exchanger failure or burner problem. Be sure to reset the
switch after correcting the failure condition.
6 RED FLASHES:
This indicates that after the unit was operating,
the
pressure switch opened 4 times during the call for heat. If the main
blower is in a "Delay on" mode it will complete
it, and any subsequent
delay off period. The furnace wilI Iock out for one hour and then restart.
7 RED FLASHES:
This fault code indicates that the flame could not be
established.
This no-light condition occurred 3 times (2 retries) during
the call for heat before locking out. Low gas pressure, faulty gas valve,
dirty or faulty flame sensor, faulty hot surface ignitor or burner problem
may cause this.
8 RED FLASHES:
This fault is indicated if the flame is lost 5 times (4
recycles) during the heating cycle. This could be caused by low gas
pressure, dirty or faulty flame sensor or faulty gas valve. The furnace
will Iock out for one hour and then restart.
9 RED FLASHES:
Indicates reversed line voltage polarity or grounding
problem. Both heating and cooling operations
will be affected. Check
polarity at furnace and branch. Check furnace grounding including the
transformer ground. Check that flame probe is not shorted to chassis.
10 RED FLASHES:
Gas flow with no call for heat. Check gas valve and
gas valve wiring.
11 RED FLASHES: This indicates that a primary or auxiliary limit switch
has opened
its normally-closed
contacts and has remained
open for
more than five minutes.
This condition
is usually caused
by a failed
blower motor or blower wheel. Cycle power (24 VAC) to the contro! to
reset the hard lockout condition after correcting the failure condition.
4 AMBER FLASHES:
Y present with no G call. Normally, both Y and G
are energized on a call for cooling. If a Y signal is present with no G sig-
nal, check to see that the wire from the G terminal on the board to the
wall thermostat
has not broken or disconnected.
STEADY ON RED: Control failure. Replace control board.
60-MINUTE
AUTOMATIC
RESET
FROM
LOCKOUT:
This
control
includes a "watchdog" type circuit that will reset from a lockout condition
after 60 minutes.
Operational
faults 6,7,8 will be reset. This provides
protection to an unoccupied
structure
if a temporary
condition
exists
causing a furnace malfunction.
An example would be a low incoming
gas supply pressure preventing unit operation. When the gas pressure
is restored, at some point the "watchdog" would restart the unit and pro-
vide heat for the house.
NOTE: If a flame is detected the control flashes the LED for !/8 of a
second and then enters a flame stabilization
period.
IGNITION CONTROL
(P/N 03!-0!972-000)
Normal flame sense current is approximately
3.7 microamps DC (pa)
Low flame signal warning starts at 1.5 microamps.
Low flame signal control lockout point is
0.9 microamps DC (pa)
DIAGNOSTIC
FAULT
CODE
STORAGE
AND
RETRIEVAL
The control in this furnace is equipped with memory that will store up to
five error codes to allow a service technician
to diagnose
problems
more easily. This memory will be retained even is power to the furnace
is lost. This feature should only be used bv a aualified service tech-
nician.
The control stores up to five separate
error codes.
If more than five
error codes have occurred since the last reset, only the five most recent
wilI be retained. The furnace control board has a button, labeled "LAST
ERROR" that is used to retrieve error codes. This function will only work
if there are no active thermostat signals. So any call for heating, cooling
or continuous fan must be terminated before attempting to retrieve error
codes.
To retrieve the error codes, push the LAST ERROR button. The LED on
the control will then flash the error codes that are in memory, starting
with the most recent. There will be a two-second pause between each
flash code. After the error codes have all been displayed,
the LED wilI
resume
the normal slow green flash after a five second pause. To
repeat the series of error codes, push the button again.
If there are no error codes in memory, the LED will flash two green
flashes. To clear the memory, push the LAST ERROR button and hold it
for more than five seconds. The LED will flash three green flashes when
the memory has been cleared, then will resume the normal slow green
flash after a five-second pause.
(Seconds}
THERMOSTAT
INDUCER
IGNITOR
MAIN
VALVE
HUMIDIFER
ELECTRONIC
AIR
CLEANER
CIRCU
LATIN
G
BLOWER
:_
Thermostat
Ca[[ir_
for
Heat
_
Thermostat
Sat[stied
02
17
I
L ON
OFF:
I
iON
I
OFF
I
OFF
OFF
I
i
I
_EF ........................................................................
gEE......
60, 9o,12o, 18oSEC _gEE
Se[ec_able
Fan
off
Delay
FIGURE 8: Furnace Control Event Schedule
Unitary
Products
Group
7