Vent Pipe System; Draft Hood Installation; Vent Pipe Size - Kenmore 153.332421 Use & Care Manual

40 gallon gas water heater
Table of Contents

Advertisement

CONFINED
SPACE
2000
BTUH
1 SQ.
INCH
PER
2000
BTUH
ALL
AIR
FROM
OUTDOORS
USING
HORIZONTAL
DUCTS
FIGURE 16.
ALTERNATIVE
OPENING
LOCATION
CONFINED
SPACE
1SQ.
INCH
PER3OOOBTUH
ALL AIR FROM OUTDOORS - USING A SINGLE PERMANENT
OPENING
FIGURE 17.
Vent Pipe System
This water heater uses a non-direct,
single-pipe vent system
to remove exhaust gases created by the burning of fossil fuels.
Air for combustion
is taken from the immediate water heater
location or is ducted in from the outside (see "Combustion Air
Supply and Ventilation").
This water heater must be properly vented for the removal of
exhaust gases to the outside atmosphere.
Correct installation
of the vent pipe system is mandatory for the proper and efficient
operation of this water heater and is an important factor in the
life of the unit.
The vent pipe must be installed according to all local and state
codes or, in the absence of local and state codes, the "National
Fuel Gas Code", ANSI Z223.1(NFPA
54)-current edition. The
vent pipe installation must not be obstructed
so as to prevent
the removal of exhaust gases to the outside atmosphere.
IMPORTANT: The use of vent dampers
is not recommended
by the manufacturer
of this water heater. Although some vent
dampers
are certified by CSA International,
this certification
applies to the vent damper device only and does not mean they
are certified for use on this water heater.
U.L. recognized fuel gas and carbon monoxide (CO) detectors
are recommended
in all applications
and should be installed
using the manufacturer's
instructions and local codes, rules, or
regulations.
IMPORTANT:
If you tack the necessary
skills required
to
properly install this venting system, you should not proceed, but
get help from a qualified technician.
Draft Hood Installation
L SCREWS
(FOUR PROVIDED)
_tP'--'DRAFT
HOOD
SLOTJ
_
_JACKETTOP
p" LSLOT
INSTALL
THE DRAFT HOOD WITH
THE FOUR SCREWS
PROVIDED.
FIGURE 18.
Align the legs of the draft hood with the slots provided. Insert
the legs and secure the draft hood to the water heater's top
with the four screws provided as shown in Figure 18. Do not
alter the draft hood in any way. If you are replacing an existing
water heater, be sure to use the draft hood supplied with this
water heater.
Vent Pipe Size
It is important that you follow the guidelines in these instructions
for sizing a vent pipe system. If a transition to a larger vent size
is required, the vent transition connection must be made at the
draft hood outlet.
Vent Connectors
1.
Type B, Double wall, U.L. Listed Vent Pipe.
2.
Single walt Vent Pipe.
Maintain the manufacturer's
specified minimum clearance from
combustible materials when using type B double walt vent pipe.
Vent connectors made of type B, double walt vent pipe material
may pass through walls or partitions constructed of combustible
material if the minimum listed clearance is maintained.
Maintain a six inch minimum
clearance from all combustible
materials when using single walt vent pipe.
IMPORTANT: Single walt vent pipe cannot be used for water
heaters located in attics and may not pass through attic spaces,
crawl spaces or any confined or inaccessible
location. A single
wall metal vent connector
cannot pass through
any interior
walt.
When installing
a vent connector,
please
note the following
(See Figures 19-21):
Install the vent connector
avoiding unnecessary
bends,
which create resistance to the flow of vent gases.
Install without dips or sags with an upward slope of at least
1/4-inch per foot.
Joints must be fastened by sheet metal screws or other
approved
means.
It must
be supported
to maintain
clearances and prevent separation of joints and damage.
The length of the vent connector cannot exceed 75% of the
vertical vent height.
The vent
connector
must be accessible
for cleaning,
19

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents