.. CR,o++o ioo l HOTLINE INDIRECT P.O.Box4729 Utica, NY 13504.4729 WATERHEATER www.ecrinternational.com MODELS HL30SK, H L40SK, H LSOSK, HL80SK, H L119SK SET-UP,OPERATING& MAINTENANCE INSTRUCTION MANUAL Twice the recovery of a standard gas-fired water heater .rid four times the recovery of an electric water heater.
Page 2
Indirect Coil Tank Water Heater Instruction Manual WARNING INSTALLER RESPONSIBILITIES Improper installation, adjustment, alteration, Please read all instructions thoroughly before service or maintenance can cause serious installing or placing the heater into service. injury or property damage. Refer to this This unit must be installed...
Page 5
SECTION I: SPECIFICATIONS (cont.) Table 2: Capacity & Performance Capacities Model 85 I 85,000 HL30SK HL40SK 2.30 77,000 HL50SK 2.30 77,000 HL80SK 2.76 I 83,000 183,000 HL119SK 2.76 NOTES: * Based on 77°F rise with 58°F potable water inlet temperature at 8 GPM heat source flow rate. Heat source temperature was 180°R ** Minimum Coil output based on continuous boiler operation over 30 minutes.
SECTION Ih GENERAL INFORMATION LOCATION The indirect coil tank water heater should be located in a central location to the piping system, as close as practical to the boiler and in an area not subject to freezing temperatures. Leave sufficient space for servicing and maintaining...
Page 7
SECTION II: GENERAL INFORMATION (cont.) ANODE RODS The anode rod is used as a sacrificial element within the volume of the storage tank. purpose of the magnesium anode rod is to protect the inside of the tank against corrosion. Anode rods should be inspected twice...
SECTION II1: PRE-INSTALLATION BOILER AND CIRCULATOR SIZING The ratings published in this manual for your Hothine Indirect Coil Tank Water Heater be obtained through proper selection of boiler output circulator capacity. As noted, ratings in Table 2 are based on a 77°F rise with 58°F potable water inlet...
SECTION IV: INSTALLATION WATER CONNECTIONS All piping between the boiler the indirect heater should be new copper with minimum size of 3/4" ID for models HL30SK, HL40SK, and HLSOSK. Use 1" minimum copper for models HL80SK and HL119SK. Elbows should be minimized.
Page 11
SECTION IV: INSTALLATION (cont.) See Figure 8 for piping your HotLine Indirect Coil Tank Water Heater to a low-mass boiler (diagram recommended by boiler manufacturer). NEAT[NG ZONE FROM HEATING ZONE CHECK VALVES ZONE CIRCULATORS VALVES ISOLATION VALVES ISOLATIOI@ ADDITIONAL ADDITIONAL ZONES ZONES iNDiRECT...
Page 12
SECTION IV: INSTALLATION (cont.) ELECTRICAL CONNECTIONS iNDiRECT Figures 9 and 10 are general wiring diagrams. CIRCULATOR For a maintaining temperature boiler, Figure should closely match your system. For cold start AQUASTAT boilers your wiring may resemble Figure 10, but will vary depending on the boiler type L1 HOT @...
SECTION V: MAINTENANCE WATER PIPING On an annual basis, all piping should be checked for leakage at joints, shut-off valves, unions. T&P RELIEF VALVE On an annual basis, the temperature pressure relief valve should be checked for proper operation. First, attach a drain line to the valve to direct...
SECTION VI: TROUBLESHOOTING PROBLEM CAUSE SOLUTION No hot water at faucet Boiler does not Refer to boiler installation instructions operate Check main service switch Check fused disconnect Circulator does not Check power supply operate Replace as necessary Check aquastat setting Turn tank aquastat...
SECTION VIII: WARRANTY LIMITED LIFETIME WARRANTY GENERAL CONDITIONS 7) ECR International fhtt Line is installed outside of the [!nited States ov Canada. Ilot Line Water Ileaters. ECR International. warrants that the 8) ECR International [lot Line is repaired or ahercd without [lot Line tank shall be fi'ee of defects in material and workman-...