To inspect base insulation:
The boiler contains ceramic fiber and fiberglass materials.
Use care when handling these materials. See WARNING
above. Failure to comply could result in severe personal
injury.
Make sure base insulation is secure against base front and back panels. If
base insulation is damaged or displaced, do not operate boiler. Replace
or reposition insulation.
Failure to replace damaged insulation or reposition
insulation can result in a fire hazard, causing severe
personal injury, death or substantial property damage.

To place in operation:

1. Make sure boiler is filled with water.
. Follow lighting/operating instructions on boiler.
PROPANE BOILERS ONLY – Your propane
supplier mixes an odorant with the propane to
make its presence detectable. In some instances, the
odorant can fade, and the gas may no longer have
an odor.
Propane gas can accumulate at floor level. Smell
near the floor for the gas odorant or any unusual
odor. If you suspect a leak, do not attempt to light
the pilot.
Use caution when attempting to light a propane
pilot. This should be done by a qualified service
technician, particularly if pilot outages are
common.
Periodically check the odorant level of your gas.
Inspect boiler and system at least yearly to make
sure all gas piping is leak-tight.
Consult your propane supplier regarding installation
of a gas leak detector. There are some products on
the market intended for this purpose. Your supplier
may be able to suggest an appropriate device.
3. If boiler starts, go to Step 5. If boiler fails to start, go to Step 4.
4. If boiler fails to start, check for following conditions:
a) Loose connection or blown fuse?
b) High limit setting below boiler water temperature?
c) Thermostat setting below room temperature?
d) Gas not turned on at meter?
e) Gas not turned on at boiler?
f) If above fails to eliminate the trouble, refer to Control Supple-
ment.
5. Make sure boiler goes through several normal operating cycles.
6. Turn thermostat or operating control to desired setting.
Part Number 550-110-641/0605
-
W
B
Fired
ater
oiler
— B
M
oiler
anual
Check pilot burner flame:
1. Proper pilot flame
a) Blue flame.
b) Inner cone engulfing pilot flame sensor.
c) Pilot flame sensor glows cherry red.
. Improper pilot flame
a) Overfired - flames large and lifting or blowing past pilot flame
sensor.
b) Underfired - flame small; pilot flame sensor not engulfed by
inner cone.
c) Lack of primary air - flame tip yellow.
d) Pilot flame sensor not heated properly.
Figure 7
Typical pilot burner flame
Check main burner flames:
1. Proper burner flame - Yellow-orange streaks may appear - caused
by dust.
. Improper flame
a) Overfired - Flames large.
b) Underfired - Flames small.
c) Lack of primary air - Yellow tipping on flames; sooting will oc-
cur.
Figure 8
Typical main burner flame
17