1.4 Specifications
S20LP system specifications
Transmission cable
Cable connection
(cable side connector)
Transmission distance
Topology
Number of stations
Transmission speed
Transmission code
Modulation method
Communication service
S20LP-station specifications
Station type
Max. number on
T2N/T3H
Scan
transmission
capacity
Message transmission
support
RAS information
Consumed current
(internal 5Vdc)
(Note 1) A T3H which has two S20LP-stations can work as a bridge station for two S20LP
layers.
Silica glass SI 200/230 m
H-PCF (Hard-Plastic Clad Fiber)
F07 connector
(JIS C5976)
Max. 1 km (between stations)
Max. 4 km (between stations ; connecting SBR22)
Max. 30 km (system total)
Loop
Max. 64 stations
2 Mbps
Differential Manchester
Baseband
(1) Scan transmission (cyclic broadcast)
(2) Message transmission (on request)
S20LP port for T2N
PU245N...Optical fiber
1 station
(Include of S20LP port)
4096 words
(Link register W (2048 words) in T2N/T3H is assigned)
S-LS (primary / secondary)
T-PDS (primary / secondary)
T-series Computer Link Protocol (secondaty)
Station status, Online / Standby map (S20LP port / SN325)
S20LP port ... 1.5 [A] or less
11
6 F 3 B 0 3 5 6
S20LP-station for T3H
SN325...Optical fiber
2 stations (Note 1)
SN325 ... 800 [mA] or less