Lightolier ProSpec Track Lighting Installation Instructions page 3

Recessed feed track and plain track units

Advertisement

Instructions for Recessed ProSpec
DIRECT POWER FEED TO "FEED" TRACK
Use solid 12 ga. copper wire when feeding the track. The feed track accepts
two separate 120 V, 60 Hz branch circuits. Each circuit must not exceed the
20 amp capacity of the track system.
FEED FROM ABOVE TRACK (Fig E):
•Remove Bottom cover and save.
•Remove Knockout in Top Plate.
•Remove Top Plate from Track
•Secure electrical connector (by others;
Plate using the Nut provided. Position connector locking screws such
that the screws will be hidden behind the track width.
•Attach Top Plate to track.
•Pass wires through connector and secure the cable or conduit to the
connector. The track must not support the cable . Use separate support
for securing the cable to the building structure.
•Secure the track to the ceiling ( see mounting on previous page ).
•Form the wires in the Feed track to the connector terminals
(see FIG. F). Cut and strip each wire. Attach wires to the screw
terminals. Wires must be tightly held in the screw terminals. Neutral
wires must be attached to screw terminals marked "NEUT". Ground
wire must be attached to the green ground screw.
•Snap Bottom Cover into the track.
FEEDING ALONG THE TRACK LENGTH (Fig. G)
A floating splice box may be used to feed the "Feed Track" from along the
tracks length. The floating splice box can be mounted anywhere on the track
up to 4' from the end of the track. The wires are passed along the top of the
track and into the feed end of the track. The floating splice box may
only be used when there is accessibility to the splice box after the
installation is complete.
Floating Splice Box (Cat. no. 26660) sold separately. See instructions
supplied with 26660 for complete installation details.
Power Feed to Track
3
/
size recommended) to Top
8
Track
Electrical
Connector
Top Plate
Knock out
Bottom Cover
FIG. E
Circuit 2
Circuit 1
Neutral 2
Neutral 1
Neutral
Terminals
Power
Terminals
FIG. F
Floating Splice Box
Wire Cover
Feed End
FIG. G
INSTRUCTION SHEET NO.
IS:26600
A0397
Page 3 of 4
Feed Track
Use 12 ga. solid copper wire for feed
connections including ground.
.50
Two wires may be
attached to one
Ground Terminal
screw terminal.
Dead End
Feed Track Unit