Download Print this page

Lightolier LOT Series Specification

5.0-10.0 kva single phase ups

Advertisement

Quick Links

LOT
B
A
D
Electronics
Battery
Cabinet
Cabinet
5.0 kVA
6.0-10.0 kVA
Width (A)
36"
36"
Depth (B)
24"
24"
Height (C)
80"
80"
Width (D)
N/A
29"
5.0-10.0
Overall Characteristics
Features: 87% throughput
efficiency with 85% emergency
efficiency. Operating
temperature range 32ºF
(0ºC) to 104ºF (40ºC). Fault
current rating of 42 kAIC.
Audible noise less than 50 dB
at 3 ft on "A" weighted scale.
Automatic low battery voltage
disconnect. Double conversion
with no interruption. Solid
state pulse width modulated
inverter. Internal, make before
break maintenance by-pass.
Standard UL 924 compliant,
90 minute battery back up.
UL 924 auxiliary equipment
10 and 20 minute back up
available. Microprocessor
control and diagnostic system.
LED array system status panel.
Fault annunciating audible
alarm. Current limiting start
sequence. Optional output
C
circuit breakers (OCB) and
circuit breakers with trip alarm
(OCBA). Optional normally
off load (NOL) energizes only
during power outage, normally
off load with time delay (TDT)
also available. Free standing
NEMA 1 enclosure. Lockable
control access panel. Seismic
anchoring compatible.
LOT Series
VA S
K
INGLE
Application: The solid state
pulse width modulated (PWM)
inverter offers enhanced load
compatibility. It operates
incandescent, magnetic, and
electronic ballast fluorescent,
high power factor compact
fluorescent and high intensity
discharge (HID) luminaries.
Provides conditioned,
uninterruptible power for
other types of critical loads.
Consult factory for non-lighting
load applications.
Input: Input power factor
correcting to 0.99. Frequency
range 60 Hz, ±2.5 Hz. Input
harmonic current distortion
< 5%THD. UL1449, ANSI/IEEE
C62.41 surge suppression.
Job Information
Type:
Job Name:
Cat. No.:
Notes:
P
UPS
HASE
Page 1 of 2
Output: Sine wave output.
Voltage regulation ±2%.
Frequency regulation is
synchronized to utility and free
running 60 Hz, ±0.5%. Output
voltage distortion maximum
3% THD with linear load. Load
power factor capability 0.7 lead
to 0.7 lag. Overload capability
125% for 10 seconds.
Code Compliance
UL 924 and UL 924 auxiliary
equipment listed.
Warranty
Lightolier will provide parts
and on-site labor for the first
12 months following start-
up of the product, and parts
only for an additional 12
months. If factory start-up is
not executed within 120 days
of shipment, Lightolier will
provide a parts warranty for
12 months from the date of
shipment. Consult factory for
extended warranty and service
option.

Advertisement

loading

Summary of Contents for Lightolier LOT Series

  • Page 1 Warranty Input: Input power factor Standard UL 924 compliant, Lightolier will provide parts correcting to 0.99. Frequency 90 minute battery back up. and on-site labor for the first range 60 Hz, ±2.5 Hz. Input UL 924 auxiliary equipment...
  • Page 2 Output Circuit On Bus w/ Optional Breaker Distribution Fuse Battery Pack Philips Lightolier Job Information Type: e: lol.webmaster@philips.com t: (508) 679-8131 w: www.lightolier.com LOT Series - 5.0-10.0 September 12, 2011 Specifications are subject to change without notice. © Koninklijke Philips Electronics N.V., 2011. All rights reserved.