7.2.2.2 Fill and Stop Mode

The following program outputs a sample of the panel temperature to the card
once a second. The first parameter of the CardOut() instruction is 1, which
sets the table on the card to fill and stop mode. The second parameter (1000) is
the number of records which will be written before the table is full and data
storage stops. Once 1000 records have been stored, data storage will stop.
PROGRAM
'CR1000
Public temp
DataTable (Table1,1,1000)
CardOut (1,1000)
Sample(1,temp,IEEE4)
EndTable
BeginProg
Scan(1,SEC,3,0)
PanelTemp(temp,250)
CallTable Table1
NextScan
EndProg
To reset a table after a fill and stop table has been filled and stopped, either use
the reset button in LoggerNet (LN Connect | Datalogger | View Station Status |
Table Fill Times, Reset Tables button) or use the CRBasic ResetTable
instruction.
®