Application Data - Dodge SP600 Series Datasheet

Ac drives from 0.5 to 200 horsepower

Advertisement

• Ramp Control
- 2 accel/decel rates
- Frequency avoidance bands (3)
to lock out mechanical resonance
points.
- "S" curve acceleration and
deceleration for smooth speed
transitions
• Time Stamped Fault Log
- User Interlock Open
- High DC Bus Voltage
- Low DC Bus Voltage
- Over-Current
- Over-Frequency
- Over-Temperature
- Electronic Motor Overload
- Ground Fault
- Others
• Option Kits
- Braking resistors
- Remote NEMA 4 operator
interface
- PC based V*S Utilities
- EMC line filters
- Network communications modules
- ControlNet
- DeviceNet
- Profibus
- Others
• Stopping Modes
- DB Braking
- Ramp Stop
- Coast Stop
- DC Injection Braking
• Operator Interface Modules
- Multi-line, 6-language graphical
LCD OIM for local or remote
operation. Allows drive control,
configuration, monitoring and
diagnostics. Function keys are
configurable for desired functions.
• Drive Protection
- Line-to-line and line-toground and
output short circuit protection.
Instruction Manuals
• D2-3485
(6SP Series - Frames A, B, C, D)
• D2-3501
(6SB Series - Frames 2, 3, 4, 5, 6)
Service Conditions
• Elevation to 3300 ft.
(1000 meters); Derate 3% for every
1000 ft. above 3300 ft.
• Operating temperature ranges:
- NEMA enclosures:
- 0°C to 40°C (external ambient)
- IP20 enclosures:
- 0°C to 50°C
(50 HP - 45°C; 200 HP - 40°C)
(panel ambient)
• Atmosphere non-condensing relative
humidity: 5% to 95%
• AC line voltage variation: rated input
voltage ±10%
• AC line frequency variation (50/60
Hz): 48 - 62 Hz
• Storage temperature:
- - 40°C to 65°C
(-40°F to 149°F)

Application Data

• Pulse width modulation (PWM)
sensorless vector control
• Maximum load:
- 110% continuous for one minute
(Normal Duty Rating)
- 150% continous for one minute
(Heavy Duty Rating)
• Frequency stability long term: 0.01%
of base speed with digital keypad
0.5% of base speed with analog
speed reference.
• Linearity (speed reference to output
frequency): ± 1.0%
Quiet Motor Operation Up
to 200 Feet
• The SP600 controller uses IGBT
transistors switched at frequencies up
to 10kHz to reduce PWM induced
motor audible noise.
• Unique transistor control circuits also
allow drive to motor distances of
up to 300 feet when applied with
Reliance motors before output filtering
considerations must be applied.
• Tested to ensure that the waveform at
the motor conduit box will not exceed
the limits specified in NEMA MG1
31.40.4.2. at lead lengths of 200 ft.

Advertisement