Download Print this page
Carrier 50FCQ 08 Series Installation Instructions Manual
Carrier 50FCQ 08 Series Installation Instructions Manual

Carrier 50FCQ 08 Series Installation Instructions Manual

Single package rooftop heat pump with puron r-410a refrigerant and ecoblue fan technology
Hide thumbs Also See for 50FCQ 08 Series:

Advertisement

Quick Links

CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1
MODEL NUMBER NOMENCLATURE AND
DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Rated Indoor Airflow . . . . . . . . . . . . . . . . . . . . . . . . . . 2
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Jobsite Survey . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Step 1 — Plan for Unit Location . . . . . . . . . . . . . . . 10
• ROOF MOUNT
Step 2 — Plan for Sequence of Unit Installation . . 10
• CURB-MOUNTED INSTALLATION
• PAD-MOUNTED INSTALLATION
• FRAME-MOUNTED INSTALLATION
Step 3 — Inspect Unit . . . . . . . . . . . . . . . . . . . . . . . . 10
Step 4 — Provide Unit Support . . . . . . . . . . . . . . . . 10
• ROOF CURB MOUNT
• SLAB MOUNT (HORIZONTAL UNITS ONLY)
• ALTERNATE UNIT SUPPORT (IN LIEU OF CURB OR
SLAB MOUNT)
Step 5 — Field Fabricate Ductwork . . . . . . . . . . . . . 12
• FOR UNITS WITH ACCESSORY ELECTRIC HEATERS
Step 6 — Rig and Place Unit . . . . . . . . . . . . . . . . . . 12
• POSITIONING ON CURB
Step 7 — Convert to Horizontal and Connect
Ductwork (when required) . . . . . . . . . . . . . . . . . . 13
Step 8 — Install Outside Air Hood . . . . . . . . . . . . . . 14
• ECONOMIZER HOOD PACKAGE REMOVAL 
(FACTORY OPTION)
• ECONOMIZER HOOD SETUP
Step 9 — Install External Condensate Trap 
and Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Step 10 — Make Electrical Connections . . . . . . . . . 15
• FIELD POWER SUPPLY
• FIELD POWER WIRING CONNECTIONS
• UNITS WITH FACTORY-INSTALLED NON-FUSED
DISCONNECT
• UNITS WITHOUT FACTORY-INSTALLED
NON-FUSED DISCONNECT
• ALL UNITS
• CONVENIENCE OUTLETS
• FACTORY OPTION THRU-BASE CONNECTIONS
• UNITS WITHOUT THRU-BASE CONNECTIONS
• FIELD CONTROL WIRING
• THERMOSTAT
• UNIT WITHOUT THRU-BASE CONNECTION KIT
• HEAT ANTICIPATOR SETTINGS
• COMMERCIAL DEFROST CONTROL
• ELECTRIC HEATERS
• SINGLE POINT BOXES AND SUPPLEMENTARY
FUSES
• SINGLE POINT BOXES WITHOUT FUSES
• LOW-VOLTAGE CONTROL CONNECTIONS
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53500351-01
Installation Instructions
Page
Printed in U.S.A.
Form No. 50FCQ-8-12-02SI Rev. A
WeatherMaker
Single Package Rooftop Heat Pump
with Puron
®
and EcoBlue™ Fan Technology
• CONTROL AND POWER WIRING DIAGRAMS
EconomizerONE (Factory Option) . . . . . . . . . . . . . .31
• ECONOMIZER SETTINGS
• WIRING
• SETUP AND CONFIGURATION
• INSTALLING OPTIONAL HH57LW001 SINGLE 
OUTSIDE AIR ENTHALPY SENSOR
• CHECKOUT
• TROUBLESHOOTING
SystemVu™ Controller (Factory Option) . . . . . . . . .52
Controller Options . . . . . . . . . . . . . . . . . . . . . . . . . . .52
• LOW AMBIENT
Smoke Detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
• COMPLETING RETURN AIR SMOKE SENSOR 
INSTALLATION
• ADDITIONAL APPLICATION DATA
Step 11 — Adjust Factory-Installed Options . . . . . .53
• SMOKE DETECTORS
• ECONOMIZERONE OCCUPANCY SWITCH
Step 12 — Install Accessories . . . . . . . . . . . . . . . . .53
Step 13 — Fan Speed Set Up . . . . . . . . . . . . . . . . . .53
• UNITS WITH ELECTRO-MECHANICAL CONTROLS
• UNITS WITH SYSTEMVU™ CONTROLS
Typical Unit Piping . . . . . . . . . . . . . . . . . . . . . . . . . . .56
Pre-Start and Start-Up . . . . . . . . . . . . . . . . . . . . . . . .59
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . CL-1
SAFETY CONSIDERATIONS
Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components. Only
trained and qualified service personnel should install, repair, or
service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of
cleaning coils and filters and replacing filters. All other operations
should be performed by trained service personnel. When working
on air-conditioning equipment, observe precautions in the
literature, tags and labels attached to the unit, and other safety
precautions that may apply.
Follow all safety codes, including ANSI (American National
Standards Institute) Z223.1. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire
extinguisher available for all brazing operations.
It is important to recognize safety information. This is the safety-
alert symbol
. When you see this symbol on the unit and in
instructions or manuals, be alert to the potential for personal
injury.
Understand the signal words DANGER, WARNING, CAUTION,
and NOTE. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards
which could result in personal injury or death. CAUTION is used
Pg 1
4-24
®
50FCQ*08-12
(R-410A) Refrigerant
Replaces: 50FCQ-8-12-01SI

Advertisement

loading
Need help?

Need help?

Do you have a question about the 50FCQ 08 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Carrier 50FCQ 08 Series

  • Page 1 ® WeatherMaker 50FCQ*08-12 Single Package Rooftop Heat Pump with Puron ® (R-410A) Refrigerant and EcoBlue™ Fan Technology Installation Instructions • CONTROL AND POWER WIRING DIAGRAMS CONTENTS Page EconomizerONE (Factory Option) ....31 •...
  • Page 2 to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight CAUTION suggestions which will result in enhanced installation, reliability, or operation. PERSONAL INJURY HAZARD Failure to follow this caution may result in personal injury. WARNING Sheet metal parts may have sharp edges or burrs.
  • Page 3 Position: 9 10 11 12 13 14 15 16 17 18 Example: Unit/Series/Model Packaging & Seismic Compliance 50FCQ = Packaged Rooftop Heat Pump 0 = Standard Standard Efficiency with 1 = LTL EcoBlue™ Fan Technology Electrical Options A = None Refrig.
  • Page 4 Fig. 2 — 50FCQ 08-09 Unit Dimensional Drawing...
  • Page 5 Fig. 2 — 50FCQ 08-09 Unit Dimensional Drawing (cont)
  • Page 6 Fig. 2 — 50FCQ 08-09 Unit Dimensional Drawing (cont)
  • Page 7 Fig. 3 — 50FCQ 12 Unit Dimensional Drawing...
  • Page 8 Fig. 3 — 50FCQ 12 Unit Dimensional Drawing (cont)
  • Page 9 Fig. 3 — 50FCQ 12 Unit Dimensional Drawing (cont)
  • Page 10 Prepare bottom condensate drain connection to suit planned INSTALLATION condensate line routing (refer to Install External Condensate Jobsite Survey Trap and Line on page 15 for details) Complete the following checks before installation. Rig and place unit Consult local building codes and the NEC (National Electri- Install outdoor air hood cal Code) ANSI/NFPA 70 for special installation requirements.
  • Page 11 ROOFING MATERIAL [115.5] (FIELD SUPPLIED) THIS DOCUMENT AND THE INFORMATION CONTAINED THEREIN IS PROPRIETARY TO CARRIER CORPORATION AND SHALL NOT BE USED OR DISCLOSED TO OTHERS, IN WHOLE OR IN PART, SUPPLY AIR RETURN AIR WITHOUT THE WRITTEN AUTHORIZATION OF CARRIER CORPORATION.
  • Page 12 FOR UNITS WITH ACCESSORY ELECTRIC HEATERS All installations require a minimum clearance to combustible sur- faces of 1 in. (25 mm) from duct for first 12 in. (305 mm) away from unit. Outlet grilles must not lie directly below unit discharge. WARNING PERSONAL INJURY HAZARD Failure to follow this warning could cause personal injury.
  • Page 13 Place all seal strips in place before "B" 36-54 in. placing unit Required Detail "A" on roof curb (914-1371 mm) Spreader Bars Duct End "C" Side "A" See Detail "A" NOTE(S): 1. SPREADER BARS ARE REQUIRED. Top damage will occur if spreader bars are not used. 2.
  • Page 14 discarded. Save the aluminum filter for use in the power exhaust Step 8 — Install Outside Air Hood hood assembly. ECONOMIZER HOOD PACKAGE REMOVAL The indoor coil access panel will be used as the top of the (FACTORY OPTION) hood. Remove the screws along the sides and bottom of the The hood is shipped in knock-down form and must be field indoor coil access panel.
  • Page 15 All units must have an external trap for condensate drainage. In- stall a trap at least 4 in. (102 mm) deep and protect against freeze- up. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1 in. per 10 ft (25 mm in 3 m) of run.
  • Page 16 FIELD POWER WIRING CONNECTIONS Measure from the tip of the shaft to the top surface of the black pointer; the measurement should be 3.75 to 3.88 in. Field power wires are connected to the unit at line-side pressure (95 to 99 mm). lugs on compressor contactor C and indoor fan contactor IFC (see wiring diagram label for control box component arrangement) or Tighten the locking screw to secure the shaft to the NFD.
  • Page 17 wiring connections to the unit power terminal blocks and equip- ment ground. Maximum wire size is no. 2 ga AWG per pole. Provide a ground-fault and short-circuit over-current protection device (fuse or breaker) per NEC Article 440 (or local codes). Refer to unit informative data plate for MOCP (Maximum Over- current Protection) device size.
  • Page 18 GFCI Receptacle Cover — While-In-Use Not Included Weatherproof Gasket Baseplate For GFCI Receptacle Fig. 24 — Weatherproof Cover Installation UNIT CONNECT PRIMARY TRANSFORMER VOLTAGE CONNECTIONS TERMINALS Non-Powered Convenience Outlet L1: RED +YEL H1 + H3 208, 230 This type requires the field installation of a general-purpose L2: BLU + GRA H2 + H4 125-volt 15-A circuit powered from a source elsewhere in the...
  • Page 19 NOTE: Take care not to damage the gasket, as it is reused in the This device can be a thermostat (field-supplied) or a SystemVu™ following step. controller (available as factory-installed option for use on a Carrier Comfort Network ® or as a stand alone control). All field added Place the gasket over the embossed area in the basepan, align- wire must comply with UL and local NEC standards.
  • Page 20 W1 terminal). The accessory thermostats listed on the unit price Raceway pages can provide this signal but they are not configured to en- able this signal as shipped. Install the accessory thermostat according to installation instruc- tions included with the accessory. Locate the thermostat accessory on a solid wall in the conditioned space to sense average temperature in accordance with the ther- mostat installation instructions.
  • Page 21 Fig. 31 — Defrost Control Board Location — 50FCQ 08-09 Electro-Mechanical Units Shown Table 4 — 50FCQ Defrost Board I/O and Jumper Configurations POINT NAME TYPE OF I/O CONNECTION PIN NUMBER UNIT CONNECTION NOTE INPUTS G Fan DI, 24 vac P2-3 CTB-G Y1 Cool 1...
  • Page 22 Reversing Valve Control Defrost The DFB has two outputs for unit reversing valve control. Opera- The defrost control mode is a time/temperature sequence. There tion of the reversing valves is based on internal logic; this applica- are two time components: The continuous run period and the tion does not use an “O”...
  • Page 23 ELECTRIC HEATERS The 50FCQ units may be equipped with field-installed accessory electric heaters. The heaters are modular in design, with heater frames holding open coil resistance wires strung through ceramic insulators, line-break limit switches and a control contactor. Heater modules are installed in the compartment below the indoor (supply) fan outlet.
  • Page 24 SINGLE POINT BOXES WITHOUT FUSES Unit heater applications not requiring supplemental fuses require a special single point box without any fuses. The accessory single point boxes contain a set of power taps and pigtails to complete the wiring between the single point box and the unit’s main control box terminals.
  • Page 25 Fig. 38 — Typical 50FCQ*08-09 Control Wiring Diagram, Electro-Mechanical Controller with POL224, 230, 460, 575-3-60 Unit Shown...
  • Page 26 Fig. 39 — Typical 50FCQ*12 Control Wiring Diagram, Electro-Mechanical Controller with POL224, 230, 460, 575-3-60 Unit Shown...
  • Page 27 Fig. 40 — Typical 50FCQ*08-09 Control Wiring Diagram, SystemVu™ Controller, 230, 460, 575-3-60 Unit Shown...
  • Page 28 Fig. 41 — Typical 50FCQ*12 Control Wiring Diagram, SystemVu™ Controller, 230, 460, 575-3-60 Unit Shown...
  • Page 29 Fig. 42 — Typical 50FCQ*08-09 Power Wiring Diagram, 230, 460-3-60 Unit Shown...
  • Page 30 Fig. 43 — Typical 50FCQ*12 Power Wiring Diagram, 230-3-60 Unit Shown...
  • Page 31 the harness are made to the C (24 vac common) and R (24 vac EconomizerONE (Factory Option) power) terminals of the economizer controller. See Fig. 46. ECONOMIZER SETTINGS LED Indication Interface Overview NOTE: If different faulty events occur at the same time, then EconomizerONE sensor/DAC LED lights up following the priority below: Red ...
  • Page 32 Table 6 — LED Indication FREE SENSOR Power STATUS COOLING DAC LED Yellow Yellow Yellow Commissioning mode Blinking Blinking Blinking Power start up Yellow On Yellow On Yellow On Free cooling is running Green On — — Free cooling is available Green —...
  • Page 33 Table 7 — Free Cooling Functions CONTROL MODE SENSORS USED ENABLE FREE COOLING? The outside air dry bulb temperature is compared with the set temperature OA (outside air) temperature sensor Control Mode 1 shutoff setpoint. • Fixed Dry bulb If the outside air dry bulb temperature is below the temperature shutoff MA (Mixed Air) temperature sensor setpoint, then the outside air is used to meet all or part of the cooling demand.
  • Page 34 Table 8 — 1 and 2-Stage Cooling Stage I/O Logic Table 11 — Different Fan Speeds with Different Configured Outputs ECONOMIZER COOLING COOLING CONDITION MET STAGE 1 STAGE 2 FAN TYPE 1-SPEED COOLING 2-STAGE COOLING • Spd H (regardless of •...
  • Page 35 Table 13 — Different Damper Position Settings with Different Configured Outputs (DCV is Enabled) FAN TYPE 1-STAGE COOLING 2-STAGE COOLING • 2VENTMIN H to 2VENTMAX H (regardless of • 2VENTMIN H to 2VENTMAX H (regardless of 1-SPEED FAN cooling demand, OCC=Yes) cooling demand, OCC=Yes) 2VENTMIN L to 2VENTMAXL ...
  • Page 36 Exhaust Fan Operation Users can enable this function only from the Climatix mobile ap- ™ plication if the related function is available in the current mobile Up to two exhaust fans can be connected to the economizer application version. controller. Fault Detection and Diagnostics •...
  • Page 37 WIRING WARNING Failure to follow this caution may result in damage to equipment. Be sure to allow enough time for compressor startup and shutdown between checkout tests so that the compressors do not short-cycle. Mounting Devices Connected to the Economizer Controller Devices like damper actuators, sensors (temperature sensor, humidity sensor, combination temperature and humidity sensor, sensor), thermostats, and exhaust fans can be connected to...
  • Page 38 Table 15 — EconomizerONE Control Wiring Settings LABEL TYPE DESCRIPTION RS485 Modbus A Line A RS485 Modbus B Line B ¬ GND_ISO Earth Ground Type II NTC 10K or 0-10 vdc Mixed or Discharge Air Temperature Sensor Mixed or Discharge Air Temperature Sensor Common Type II NTC 10K or 0-10 vdc Outside Air Temperature Sensor 0-10 vdc or 4-20mA...
  • Page 39 Connecting Peripheral Devices to the Economizer Controller See Fig. 51-55 for wiring details. • Outside Air: Connect to the Mixed or Discharge Air Temperature Sensor OAT and COM terminals of the Outside Air Temperature Sensor device. • Return Air (Differential): Return Air Temperature Sensor Connect to the RAT and S-COM...
  • Page 40 • Outside Combination Temperature/ Humidity: Connect Combo Temperature and Humidity Sensor to the OAT, COM, and OAH terminals of the device. • Combo Temperature and Humidity Sensor Return Combination Temperature/ Humidity: Connect to the RAT, S-COM, and RAH terminals of the device. Fig.
  • Page 41 SETUP AND CONFIGURATION NOTE: Parameters and display menus may display differently/dynamically if different applications are config- ured. See Tables 16-23. IMPORTANT: Before setup and configuration, it is recommend- ed to obtain some location-based values, such as shutoff points, IMPORTANT: Not all operations are available on the local or utilize the location services in the Climatix ™...
  • Page 42 Table 16 — Status Display PARAMETER DESCRIPTION VALUE 1FREECOOL Indicates whether the system can use outdoor air for free cooling. 1ECON ENAB Indicates whether outdoor air is being used for the first stage of cooling. Indicates whether the space is occupied. If users choose ALWAYS for 6OCC when configuring I/Os, then the parameter value is YES;...
  • Page 43 Table 17 — Parameter Settings — Basic PARAMETER DESCRIPTION RANGE DEFAULT Temperature shutoff setpoint can be obtained automatically if a smartphone or tablet with the mobile application installed on it is connected to the 2 TEMP OFF 48...80°F; increment by 1 63°F network provided by a Wi-Fi/WLAN stick plugged into the economizer controller.
  • Page 44 Table 18 — Parameter Settings — Advanced PARAMETER DESCRIPTION VALUE/RANGE DEFAULT 3FREEZE POS Anti-freeze protection damper position (closed or minimum). 3SD ACT POS Damper position during shutdown (open or closed). MAT sensor location: • Choose MAT if the sensor is installed before the DX (Direct Expansion) coil. 3DIF T LOC •...
  • Page 45 Table 19 — Parameter Settings — I/O Configurations (cont) PARAMETER DESCRIPTION VALUE DEFAULT Choose “COOL 2” if Cooling Stage 2 is available (another compressor is COOL 2 6Y2O COOL 2 connected to the Economizer). Otherwise, choose “NONE”. NONE Auxiliary DO-1. Configurable as: NONE •...
  • Page 46 Table 22 — Enter Running State PARAMETER DESCRIPTION 8RUN STATE Change to Running State. Press Enter to confirm the change. 8ENTER RUN? Confirm the change to Running State. Perform factory reset. Press Enter to confirm the reset. (This action resets the controller 8FACTORY DEF password to default: OneBT.) 8DEF CONFIRM?
  • Page 47 Fig. 56 — HH57LW001 Dimensional, Connection and Switching Information Fig. 57 — HH79NZ039 Dry Bulb and Mixed Air Sensor Wiring Actuator Wiring Harness HH79NZ039 Outside Air Temperature Sensor Outside Air Damper Fig. 59 — California Title 24 Zones Fig. 58 — EconomizerONE Component Locations (CRECOMZR108A00 Shown)
  • Page 48 U.S. and Canada I-Codes / ASHRAE Zones Climate Zone 1 Climate Zone 5 and Marine Climate Zone 2 Climate Zone 6 Climate Zone 3 Climate Zone 7 and 8 Climate Zone 4 (Except Marine) Fig. 60 — U.S. and Canada Climate Zones Table 24 —...
  • Page 49 Economizers are shipped standard with an HH79NZ039 outside Table 25 — California Title 24 Regional High Limit air dry bulb sensor (see Fig. 57). System default setting (high temp Dry Bulb Temperature Settings limit) is 63°F (17°C) and has a range of 48°F to 80°F (9°C to REQUIRED HIGH LIMIT 27°C).
  • Page 50 CHECKOUT Status Use the Status menu (refer to Table 16) to check the parameter Inspect all wiring connections at the economizer module’s termi- values for the various devices and sensors configured. nals, and verify compliance with the installation wiring diagrams. For checkout, review the Status of each configured parameter and NOTE: For information about menu navigation and use of the perform the Test Commands tests (refer to Table 21).
  • Page 51 TROUBLESHOOTING For EconomizerONE troubleshooting issues see Table 27. Table 27 — Operating Issues and Concerns SYMPTOM REASON SOLUTION An alarm is displayed on the Sensor, damper, or the whole working Check sensor, damper, or the whole working system following the detailed alarm information. system may not work properly DAC LED is blinking RED Damper slippage...
  • Page 52 Screw the sensor and detector plate into its operating position SystemVu™ Controller (Factory Option) using screws from Step 1. See Fig. 62, Step 3. For details on operating 50FCQ*08-12 units equipped with the factory-installed SystemVu controller option refer to the Connect the flexible tube on the sampling inlet to the sampling FCQ/GCQ Series Single Package Rooftop Units with SystemVu tube on the basepan.
  • Page 53 NOTE: The Fan Speed Set Up labels are located on the High Volt- Step 11 — Adjust Factory-Installed Options age cover in the Control Box. SMOKE DETECTORS Connect a multimeter to the vdc terminals on the UCB. Smoke detector(s) will be connected at the Unit Control Board Set the Range Switch to either A, B, or C per the Switch (UCB), at terminals marked “Smoke Shutdown.”...
  • Page 54 ESP in. wg Factory Setting: Calculator 9.0 V 1500 Field Setting: 1625 Record field setting here 1750 1875 2000 Switch Range: 2125 10.0 2250 4.1 - 7.5 2375 6.9 - 8.7 2500 7.7 - 10.0 Field Accessories: Economizer * Overlap in A, B, C switch range 1 Stage E Heat designed for maximum field adjustment potential.
  • Page 55 UNITS WITH SYSTEMVU™ CONTROLS Use the DOWN arrow key highlight the UNIT CONFIGU- RATIONS menu then press ENTER. On units equipped with the factory-installed SystemVu control- ler the Fan Speed settings are accessed through the SystemVu Highlight UNIT CONFIGURATIONS then press ENTER. interface.
  • Page 56 Typical Unit Piping Table 31 — 50FCQ*12 – Cooling Mode Each heat pump system includes two compressors, a reversing COMPONENT STATUS/POSITION valve, dual-function outdoor and indoor coils, a common liquid Reversing Valve Energized line with bi-flow TXV, and dedicated cooling and heating TXVs. Check Valve A 50FCQ*08 and 09 unit outdoor coils contain a vapor header check valve.
  • Page 57 Filter Drier LPS/LOC Heating TXV Cooling TXV Reversing Valve Outdoor Coil Indoor Coil Fig. 66 — Piping Schematic — 50FCQ*08 Cooling Mode Filter Drier LPS/LOC Heating TXV Cooling TXV Reversing Valve Outdoor Coil Indoor Coil Fig. 67 — Piping Schematic — 50FCQ*08 Heating Mode...
  • Page 58 Filter Drier LPS/LOC Heating TXV Cooling TXV Reversing Valve Outdoor Coil Indoor Coil Fig. 68 — Piping Schematic — 50FCQ*09 Cooling Mode Filter Drier LPS/LOC Heating TXV Cooling TXV Reversing Valve Outdoor Coil Indoor Coil Fig. 69 — Piping Schematic — 50FCQ*09 Heating Mode...
  • Page 59 Filter Drier LPS/LOC Heating TXV Cooling TXV Reversing Valve Outdoor Coil Indoor Coil Fig. 70 — Piping Schematic — 50FCQ*12 Cooling Mode Filter Drier LPS/LOC Heating TXV Cooling TXV Reversing Valve Outdoor Coil Indoor Coil Fig. 71 — Piping Schematic — 50FCQ*12 Heating Mode Pre-Start and Start-Up This completes the mechanical installation of the unit.
  • Page 62 © 2024 Carrier Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53500351-01 Printed in U.S.A. Form No. 50FCQ-8-12-02SI Rev. A Pg 62 4-24 Replaces: 50FCQ-8-12-01SI...
  • Page 63 START-UP CHECKLIST 50FCQ*08-12 Single Package Rooftop Heat Pump Units (Remove and use for job file) NOTE: To avoid injury to personnel and damage to equipment or property when completing the procedures listed in this start-up checklist, use good judgment, follow safe practices, and adhere to the safety considerations/information as outlined in preceding sections of this Installation Instruction document.
  • Page 64 (Y/N) _____ Verify smoke detector unit shutdown by utilizing magnet test (Y/N) _____ © 2024 Carrier Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53500351-01 Printed in U.S.A.

This manual is also suitable for:

50fcq 09 series50fcq 12 series