Page 2
Start-up of these heat pumps as well as any maintenance operations must only be carried out by the Authorised Technical Assistance Services of DOMUSA TEKNIK. Incorrect installation of these heat pumps could result in damage to people, animals or property, for which the manufacturer accepts no responsibility.
Page 3
REVISIONS Version Description of changes Date First edition 09 June 2023 DUAL CLIMA HT...
..........................84 PERATING MODES 8.2 S ..........................85 TART STOP CYCLE 8.3 D ........................... 85 EFROST FUNCTION 8.3.1 A ......................86 CTIVATION CONDITIONS 8.3.2 D ......................87 EACTIVATION CONDITIONS 8.3.3 A ....................87 DJUSTMENT OF DEFROST SETTINGS DUAL CLIMA HT...
Page 5
HE HEAT PUMP DOES NOT WORK PROPERLY EVEN THOUGH IT DOES NOT GIVE ANY ERROR CODE 12.2 HMI ................157 REMOTE CONTROL DOES NOT SHOW ANY SYMBOL 12.3 P ........................158 ERFORMANCE CURVES 12.4 C ................... 160 HECKING THE QUANTITY OF REFRIGERANT DUAL CLIMA HT...
1 SAFETY WARNINGS 1.1 Warnings about the installation The DUAL CLIMA HT heat pump must be installed by personnel authorised by the Ministry of Industry, in compliance with the applicable laws and regulations. The precautions detailed here cover very important issues. Please be sure to follow them to the letter: The installation and operating instruction book supplied with the heat pump must be kept in •...
1.2 Heat pump refrigerant warnings The Dual Clima HT contains R290 refrigerant gas, which is highly flammable. In normal conditions of use, there is no risk of explosion and the refrigerant is non-toxic. However, in case of leakage, some aspects that could cause damages to third-parties must be taken into account, as the refrigerant could create a flammable atmosphere and give rise to fire or explosion.
1.3 Transport, storage and handling warnings For the correct transport and handling of the unit, carefully follow the following safety warnings: The DUAL CLIMA HT heat pump must be transported, handled and stored in vertical • position. Placing the appliance on its side can cause the oil inside the compressor to spill out, causing premature compressor breakage on start-up.
1.5 Freeze protection warnings The DUAL CLIMA HT is an appliance for installation on the outside of the building and it will consequently be exposed to frost during periods of extremely cold weather. It is therefore of utmost importance that these types of machines are protected against frost. If the water inside the heat pump freezes it can cause the pump to break, stopping its functioning and making costly repairs necessary.
Min. working pressure: (refrigerant circuit) Refrigerant R290 Refrigerant amount 1.05 1.45 1.45 Protection degree IPX4 Working temperature range °C -25/45 (Heating) Working temperature range °C 10/45 (Cooling) Sound pressure level (1m) dB(A) Dimensions: 1115/415/898 1115/415/1320 (Height/Width/Depth) Net weight DUAL CLIMA HT...
3 LIST OF COMPONENTS AND SPARE PARTS 3.1 Dual Clima 6HT Exterior Covers Description REAR DUAL CLIMA HT MANOMETER SIDE DOOR TOP COVER FRONT DOOR LEFT SIDE PANEL TOP FAN GRILLE CENTRAL FAN GRILLE DUAL CLIMA HT...
Page 12
Ventilation circuit Description SEPARATOR EXTERNAL EVAPORATOR (6-9KW) DUAL CLIMA 6-9-12 HT FAN SUPPORT FAN MOTOR FAN BLADES Ø550x124 PCB ELECTRICAL BOX COVER PCB ELECTRICAL BOX IPM ELECTRICAL BOX IPM MODULE SP.KYZ1.5-4.1 2P IPM ELECTRICAL BOX COVER DUAL CLIMA HT...
3.2 Dual Clima 9HT Exterior Covers Description REAR DUAL CLIMA HT MANOMETER SIDE DOOR TOP COVER FRONT DOOR LEFT SIDE PANEL TOP FAN GRILLE CENTRAL FAN GRILLE DUAL CLIMA HT...
Page 17
Ventilation circuit Description SEPARATOR EXTERNAL EVAPORATOR (6-9KW) DUAL CLIMA 6-9-12 HT FAN SUPPORT FAN MOTOR FAN BLADES Ø550x124 PCB ELECTRICAL BOX COVER PCB ELECTRICAL BOX IPM ELECTRICAL BOX IPM MODULE SP.KYZ1.5-4.1 3P IPM ELECTRICAL BOX COVER DUAL CLIMA HT...
Page 18
PARA 15/7 IPWM1 WILO PUMP TEMPERATURE SENSOR NTC 5K (2m) PCB BUTTERFLY VALVE M-H ½ HH ½ SAFETY VALVE WITHOUT T.M. SEN-HZG1WA FLOW SENSOR TEMPERATURE SENSOR NTC 5K (2m) TERMINAL STRIP DRAIN VALVE ASSEMBLY EXPANSION VESSEL 5 L DUAL CLIMA HT...
Page 19
GMCC 9kW COMPRESSOR TEMPERATURE SENSOR NTC 50K (1.2m) SHF-9 4-WAY VALVE AMBIENT TEMPERATURE SENSOR SUPPORT AMBIENT TEMPERATURE SENSOR NTC 5K (2m) BALANCING TANK 0.5 L WELDABLE GAS FILLER VALVE ELECTRONIC EXPANSION VALVE DFP(Q)1.8C HIGH PRESSURE SENSOR LOW PRESSURE SENSOR DUAL CLIMA HT...
Page 20
INDUCTANCE 9-12 PFC EI86 TERMINAL STRIP BRIDGING STRIP SMALL CABLE DUCT POWER SUPPLY STRIP LARGE CABLE DUCT DUAL CLIMA HT POWER BOARD REMOTE CONTROL 5K ACS RESISTOR 5K PCB RESISTOR CONDENSATION OUTLET 5x20 5A CERAMIC FUSE TEMPERATURE SENSOR NTC 5K (10m)
3.3 Dual Clima 12HT Exterior Covers Description REAR DUAL CLIMA HT MANOMETER SIDE DOOR TOP COVER FRONT DOOR LEFT SIDE PANEL TOP FAN GRILLE CENTRAL FAN GRILLE DUAL CLIMA HT...
Page 22
Ventilation circuit Description SEPARATOR EXTERNAL EVAPORATOR (12KW) DUAL CLIMA 6-9-12 HT FAN SUPPORT FAN MOTOR FAN BLADES Ø550x124 PCB ELECTRICAL BOX COVER PCB ELECTRICAL BOX IPM ELECTRICAL BOX IPM MODULE SP.KYZ1.5-4.1 3P IPM ELECTRICAL BOX COVER DUAL CLIMA HT...
Page 23
PARA 25-130/8-75/IPWM1 WILO PUMP TEMPERATURE SENSOR NTC 5K (2m) PCB BUTTERFLY VALVE M-H ½ HH ½ SAFETY VALVE WITHOUT T.M. SEN-HZG1WA FLOW SENSOR TEMPERATURE SENSOR NTC 5K (2m) TERMINAL STRIP DRAIN VALVE ASSEMBLY EXPANSION VESSEL 5 L DUAL CLIMA HT...
Page 24
12HT COMPRESSOR INSULATING SLEEVE GMCC 12kW COMPRESSOR SUCTION ACCUMULATOR_KFR50WLB-16 ELECTRONIC EXPANSION VALVE DFP(Q)1.8C HIGH PRESSURE SENSOR LOW PRESSURE SENSOR BALANCING TANK 0.5 L WELDABLE GAS FILLER VALVE AMBIENT TEMPERATURE SENSOR NTC 5K (2m) AMBIENT TEMPERATURE SENSOR SUPPORT SHF-9 4-WAY VALVE DUAL CLIMA HT...
Page 25
INDUCTANCE 9-12 PFC EI86 TERMINAL STRIP BRIDGING STRIP SMALL CABLE DUCT POWER SUPPLY STRIP LARGE CABLE DUCT DUAL CLIMA HT POWER BOARD 5K ACS RESISTOR 5K PCB RESISTOR CONDENSATION OUTLET 5x20 5A CERAMIC FUSE TEMPERATURE SENSOR NTC 5K (10m) REMOTE CONTROL...
LOW PRESSURE SENSOR HIGH PRESSURE SENSOR PLATE HEAT EXCHANGER. DISCHARGE TEMPERATURE SENSOR EVAPORATOR TEMPERATURE PROBE EXTERNAL TEMPERATURE PROBE SUCTION TEMPERATURE PROBE RETURN TEMPERATURE PROBE FLOW TEMPERATURE PROBE INTERNAL HEAT EXCHANGER TEMPERATURE PROBE EXPANSION VESSEL FLOW METER CIRCULATING PUMP DUAL CLIMA HT...
Each model has its specific compressor for R290 refrigerant gas; each model has the following quantity of refrigerant gas: - Dual Clima 6HT: 1.0 Kg - Dual Clima 9HT: 1.05 Kg - Dual Clima 12HT: 1.2 Kg - Dual Clima 16HT/16HTT: 1.45 Kg DUAL CLIMA HT...
Dual Clima Dual Clima Dual Clima 12HT 16HT 16HTT Model: YCQB05H10 Pressure sensor to manage the regulation of the thermodynamic cycle of the heat pump. It also ensures the safety of the high pressure area of the circuit. DUAL CLIMA HT...
Measures the return temperature of the primary water. 4.15 Flow temperature probe Dual Clima Dual Clima Dual Clima Dual Clima Dual Clima 12HT 16HT 16HTT Model: NTC 5K (2m) Measures the flow temperature of the primary water. DUAL CLIMA HT...
• All neutrals are changed to blue. • The inductance cables are changed to red. • The colours of the compressor wiring are changed (W,V,U). • In three-phase models, phase with red cable to grey cable. DUAL CLIMA HT...
Dual Clima 6HT OFF OFF ON OFF OFF OFF OFF Dual Clima 9HT OFF OFF ON OFF OFF OFF OFF Dual Clima 12HT ON OFF ON OFF OFF OFF Dual Clima 16HT ON OFF ON Dual Clima 16HTT DUAL CLIMA HT...
Main communication port RS485 COMM2 Slave communication port 1 RS485 COMM3 Slave communication port 2 RS485 COMM4 Slave communication port 3 RS485 Heat Thermostat Cold Thermostat Reserved Flusostat (Reserved) Reserved Reserved Reserved CN18 Reserved CN57 Software programming input DUAL CLIMA HT...
When the OUT5 output is activated, the LED will be on. OUT4 LED indicator. LED9 When the OUT4 output is activated, the LED will be on. OUT3 LED indicator. LED10 When the OUT3 output is activated, the LED will be on. DUAL CLIMA HT...
Page 73
Heat pump status indicator. If the pump is stopped or in standby DIS1 If the compressor is running, the compressor frequency will be displayed. If there is an error in the heat pump, the error code will be displayed. DUAL CLIMA HT...
Page 75
Connection Function Characteristics Reserved Reserved Reserved Reserved T1-PH Reserved Reserved Reserved Reserved T2-PL Reserved DC-FAN DC fan connection Communication port. RS485-1 Communication with power board RS485-2 Communication port. Reserved. EXV-1 Reserved EXV-2 Reserved DUAL CLIMA HT...
Page 76
Earth (Not connected) Compressor power supply, W terminal 0~12Vdc 160~180Vdc Compressor power supply, V terminal 0~12Vdc 160~180Vdc Compressor power supply, U terminal 0~12Vdc 160~180Vdc Communication port. RS485-1 Communication with power board DC-FAN1 DC1 Fan connection DC-FAN2 DC2 Fan connection DUAL CLIMA HT...
Page 77
160~180Vdc Compressor power supply, V terminal 0~12Vdc 160~180Vdc Compressor power supply, U terminal 0~12Vdc 160~180Vdc Connection 1 to the inductor 485~593Vdc Connection 2 to the inductor 485~593Vdc Communication port. RS485 Communication with power board and fan board. DUAL CLIMA HT...
Sludge filter: Degasifier: Safety valve downstream from separator: Anti-freeze drain valve kit: If it does not have a drain valve kit: Antifreeze fluid: Level of anti-freeze protection……………………ºC Anti-freeze: Anti-freeze activation temperature (P25): ……………………ºC Anti-freeze interval (P21): ……………………ºC DUAL CLIMA HT...
Page 79
Dual Clima 6HT: 14 l/min Dual Clima 9HT: 20 l/min Dual Clima 12HT: 30 l/min Dual Clima 16HT/16HTT: 38 l/min If these parameters are not met, the installation of a back-up circulation pump (in series) connected to connection C1 is required. DUAL CLIMA HT...
Page 80
Cooling ON recommended setpoint (P204): ……....……ºC DHW ON recommended setpoint (P206): ……....……ºC Heating ON mandatory setpoint (P203): ……....……ºC Cooling ON mandatory setpoint (P205): ……....……ºC DHW ON mandatory setpoint (P207): ……....……ºC Night mode (P17): □ Yes □ No DUAL CLIMA HT...
Page 81
The circuit breaker correlates to the consumption current plus 25%: □ Yes □ No It has a differential switch: □ Yes □ No The differential correlates to the intensity of consumption plus 40%: □ Yes □ No L-N: …….……….…….V N-Earth: ….…..…….V Voltage check: L-Earth: ……..………V DUAL CLIMA HT...
3-way valves are working properly: Degasifier installed in the heat pump flow: Hydraulic system pressure: ………………………….. bar Level of anti-freeze protection ………………………….. ºC , Anti-freeze valve: □ Yes □ No Heat pump flow rate: C10 ………………………….. l/min DUAL CLIMA HT...
Page 83
Power as a function of external temperature: ……………………….. kW (See manual, “ ”) Real power: [(1) – (2)] x (3) x 60 / 860 = ……………………….. kW Perform the measurements with the machine at 100%, ensuring that the compressor is at maximum frequency and in thermal equilibrium. DUAL CLIMA HT...
In this operating mode, the DUAL CLIMA HT heat pump will heat the water in the domestic hot water storage tank to the desired temperature, to provide DHW to the home. To do this, select the desired DHW setpoint temperature.
30 seconds later the 4-way valve will switch to Heat mode. After a further 30 seconds, all defrost function operations will be completed and the heat pump will resume its normal operation. DUAL CLIMA HT...
Evaporator temperature (C00) ≤ P29; (default value: 0 ºC). By reducing the value of P29 • activation of the Defrost Function is delayed. Ambient temperature (C02) ≤ P85, (default value: 8 ºC). By reducing the value of P85 • activation of the Defrost Function is delayed. DUAL CLIMA HT...
E.g: If P27 = 35 and P26 = 2, 70 minutes (35 x 2) must elapse between two defrost cycles before the Defrost Function is reactivated. In dry areas where there is no risk of frost and where the time between defrosting cycles is to be extended, parameter P26 can be used. DUAL CLIMA HT...
Minimum separations for installation of a unit (mm). Minimum separations for installation of multiple units in the same location (mm). DUAL CLIMA HT...
Page 89
Follow the steps shown below: (1) Remove the probe clip from (2) Move the probe to the (3) Wrap the probe in the tube frosted tube aluminium foil self-adhesive tape and secure it. DUAL CLIMA HT...
Furthermore, if the external temperature falls below 0ºC at any time, the water circulation pumps (C1 and C2) will start up within a time interval defined in parameter P21 for one minute. DUAL CLIMA HT...
8.5 Fan The Dual Clima HT heat pump fan, is a modulating fan that adjusts the working speed according to the needs at any given moment. Its functioning is determined by various parameters and modulation logic. When the heat pump is operating in heating mode, during the first 60 seconds after start-up, it will run at maximum speed, according to parameter (P60).
8.6 Compressor Element The Dual Clima HT heat pumps are equipped with a heating element to heat the compressor oil before start-up and when the compressor is cold. The compressor resistor will preheat the compressor oil before the first start-up whenever the external temperature is below 10°C.
Page 93
P51 > C13 > P52: The compressor will maintain the operating frequency. • C13 < P52: The compressor will run normally until the frequency set-point is reached. • C13 > P53: The compressor must stop for safety reasons and will display error E13. • DUAL CLIMA HT...
Page 94
The heat pump will limit the running speed of the compressor for safety reasons if the temperature of the internal heat exchanger is too high in cooling mode. 52ºC ≤ C00 ≤56℃: The compressor maintains its frequency. • 56ºC ≤ C00 ≤60℃: The compressor will reduce the operating frequency. • DUAL CLIMA HT...
Page 95
If during the lubricant return process the compressor cannot reach the frequency defined in parameter P41, the compressor speed will be reduced for safety reasons but the function will remain active until the required cycle is completed. DUAL CLIMA HT...
8.7 Electronic Expansion Valve (EEV) The Electronic Expansion Valve (EEV) of the Dual Clima HT heat pump, is an expansion valve that adjusts its opening to suit the needs at any given time. Its functioning is determined by various parameters and settings logic.
8.8 Auxiliary or backup energy sources (E1 and E2) The Dual Clima HT heat pump is equipped with 2 relay outputs (E1, E2) for connecting auxiliary energy sources, which may be heating elements, a gas boiler, an oil-fired boiler, etc. or any combination of these.
8.10 3-way electronic valve G2 In Cooling Mode, valve G3 is deactivated while in Heating Mode it is activated. 2-wire valve: 3-wire valve: NO: Socket Open in idle mode (motor not energised). NO: Socket Closed in idle mode (motor not energised). DUAL CLIMA HT...
9 SYSTEM PARAMETERS (P) Within the Configuration menu, the electronic control of the DUAL CLIMA HT pump has a sub-menu with the System Parameters, in which it will be possible to view and modify all the technical parameters. To validate access to the System Parameters, enter the password “99”. In the case of needing to modify parameters related to the refrigerant circuit, it will be necessary to enter the password "8563".
Legionella prevention function. Anti-legionella function 0: Auto Mode This parameter can be used to enable the 1: Manual Mode prevention function against the proliferation of the legionella bacteria. The function can 2: Disabled also be activated once manually. DUAL CLIMA HT...
Page 104
Anti-freeze interval Time interval in which the circulation pumps C1 and C2 will be activated whenever the 5 ~ 50 minutes external temperature is below 0 °C. DUAL CLIMA HT...
Page 105
Defrosting operation. 0: Auto Manual defrost activation. Returns to 0 on 1: Manual completion. Defrost activation temperature -8 ~ 5 ºC Evaporator temperature (C00) for starting- up the defrosting process. DUAL CLIMA HT...
Page 106
2~15℃ Modifying this parameter may cause the heat pump to malfunction and/or break. Temperature for fan speed adjustment in cool mode. 3~18℃ Modifying this parameter may cause the heat pump to malfunction and/or break. DUAL CLIMA HT...
Page 107
Maximum compressor frequency 50 ~ 120 Hz Modifying this parameter may cause the heat pump to malfunction and/or break. Maximum compressor frequency 0 ~ 90 Hz Modifying this parameter may cause the heat pump to malfunction and/or break. DUAL CLIMA HT...
Page 108
Modifying this parameter may cause the heat pump to malfunction and/or break. Maximum high pressure High pressure at which the compressor will stop for safety reasons. 20 ~ 45Bar Modifying this parameter may cause the heat pump to malfunction and/or break DUAL CLIMA HT...
Page 109
Below this value, error E15 will be displayed. Heating/cooling mode activation 0: Heating + cooling This parameter can be used to activate and 1: Cooling only deactivate the heating and/or cooling operating modes. 2: Heating only DUAL CLIMA HT...
Page 110
P71=0. For technical service use only. Type of pressure sensor 0: Pressure sensor This parameter is used to set the type of 1: Reserved pressure sensor. P74 Reserved P75 Reserved P76 Reserved P77 Reserved P78 Reserved P79 Reserved DUAL CLIMA HT...
Page 111
P88 Reserved P89 Reserved 0 ~ 2.0 P90 Reserved 0 ~ 20 Temperature difference (ambient- evaporator) for defrost 2 0 ~ 20 ºC Required temperature difference for defrost activation when ambient temperature ≤ - 7ºC. DUAL CLIMA HT...
Page 112
Flow/return temperature difference protection P102 8 ~ 20 ºC Maximum difference between flow and return probes. Above this value, error E22 will be displayed. P103 Initial opening time of expansion valve 0 ~ 300 sec DUAL CLIMA HT...
Page 113
P114 0 ~ 60 % Percentage of drop in compressor frequency after reaching the set-point temperature. Maximum flow temperature P115 70 ~ 90 ºC Modifying this parameter may cause the heat pump to malfunction and/or break. DUAL CLIMA HT...
Page 114
0: Disable; P207 10 ~ 70 ºC DHW set-point for switch-on mode. 0: Heat pump + SG Ready function heating devices E1/E2 P208 1: E1/E2 Selection of active devices in the SG Ready 2: Heat pump function. only DUAL CLIMA HT...
10 PARAMETERS OF THE STATUS MENU (C) On the Settings Menu, the DUAL CLIMA HT heat pump electronic control has an Operating status sub- menu. In this Menu, it is possible to view and check the status of all the control and safety components of the heat pump at all times, as well as the values of some operating parameters.
Page 116
Off: Disabled On: Enabled Indicates whether the anti-legionnaire's disease feature is activated. Overcurrent protection Off: Disabled On: Enabled Indicates whether the overcurrent protection is activated. Defrost Off: Disabled On: Enabled Indicates whether the defrost feature is activated. DUAL CLIMA HT...
Page 117
°C Temperature setpoint of the anti-legionella prevention function, set on the control panel Lubricant status Off: Disabled On: Enabled Indicates whether or not the lubricant return function is activated. Compressor run time Hours Accumulated compressor run time. DUAL CLIMA HT...
Page 118
Indicates the selected operating mode of the heat pump. 4: Cooling 5: DHW + Cooling. PCB software version Indicates the software version of the heat pump power card Software display version Indicates the software version of the heat pump display DUAL CLIMA HT...
• Reconnect the probe. Return temperature Open circuit or short-circuit • Measure the resistance of the probe at sensor failure. of T11 probe. different temperatures; if it gives an error, replace the probe. DUAL CLIMA HT...
If the error persists, replace the power PCB. • Reconnect the sensor. Open circuit or short circuit in • Replace the sensor. Low pressure sensor failure. the LS pressure sensor. • If the error persists, replace the power PCB. Solution DUAL CLIMA HT...
Check operating flow rate and if it is not within the recommended limits, install a back-up • pump for heating/cooling and/or DHW (C2 and/or C3). Check the connection and operation of the 3-way valve (G1), ensuring that it switches correctly from heating/cooling to DHW. DUAL CLIMA HT...
Page 126
There must be no obstacles preventing air circulation through the evaporator and at the fan outlet It must be ensured that the minimum required installation dimensions are complied with. • 5. Check that the fan is working properly. See section “Fan”. DUAL CLIMA HT...
• Clean the water filter, check whether the water pump has sufficient capacity. • Insufficient water flow. Insufficient water • Include back-up pumps for flow • Flow meter failure. heating/cooling (C2) or for DHW (C3). • Check and reconnect the flow meter. Solution DUAL CLIMA HT...
Communication error • Communication cable fault. connectors and/or along the entire communication cable. • Interference in the communication cable. • Check whether there are large devices or strong magnetic fields around the unit. Solution: DUAL CLIMA HT...
The refrigerant gas contained in the heat pump is highly flammable and can cause damage to persons or property. Read all warnings carefully before handling any component, especially if there is any suspected gas leakage. 4. Check the correct operation of the electronic expansion valve. DUAL CLIMA HT...
SW3 and SW4 on the PCB. (P87). • Incorrect configuration of • Check the software version (C55 and system parameters. C56) of the heat pump and ensure that it corresponds to that required. If necessary, reconfigure the heat pump. Solution DUAL CLIMA HT...
11.9 E21: Voltage error Error Possible reason for the Error meaning Error solution code error Switch the heat pump off and on. If the error persists: Voltage error. Voltage error in the heat pump. • Change SW4-3 to OFF. DUAL CLIMA HT...
• Check and clean the water filter. • Dirty or clogged water • Check whether the water pump has filter. sufficient capacity. Include back-up • Insufficient flow rate. pumps for heating/cooling (C2) or for DHW (C3). Solution DUAL CLIMA HT...
60 minutes. freeze function the DHW tank. The water temperature in the • If there is no DHW function in the • DHW tank is below 5ºC. installation, disable this function by adjusting parameter P63. Solution DUAL CLIMA HT...
Heating/Cooling mode anti- anti-freeze function has been faulty. freeze function triggered twice in the last 90 • Check that the probes are properly minutes. insulated. • Check that the flow rate of the heat pump is correct. Solution DUAL CLIMA HT...
45°C or whether there could be a The room temperature has measurement error in the ambient Room temperature exceeds exceeded the upper limit probe. limit. permitted (45ºC). • Wait until the ambient temperature is within the working range of the heat pump. Solution DUAL CLIMA HT...
• Check operation of the G1 diverter minutes. High return temperature valve. (cooling mode) • Error in diverter valve • Check the reading of the flow and return probes. Temperature probe error. • • Check the installation. Incorrect installation • Solution DUAL CLIMA HT...
• Error in diverter valve G1. (Heating and DHW mode) of the DHW probe. • Temperature probe error. • Check the reading, position and • Incorrect installation insulation of the flow probe. • Check the pump • Check the installation. Solution DUAL CLIMA HT...
Fan communication failure. • Communication cable (Three-phase) with fan motor module. • Replace fan motor module. • Problems in the fan • Replace PCB. motor module. Solution DUAL CLIMA HT...
• Dirty or clogged water • Check and clean the water filter. filter. • Insufficient flow rate. • Ensure that the water circuit is • Air in the water circuit. correctly drained. Solution DUAL CLIMA HT...
• Check that the fan cable is not loose • Loose fan motor cable. or damaged. Fan motor fault. • Problems in the fan • Replace fan motor. motor. • Replace IPM card. • Problems in the power board. Solution DUAL CLIMA HT...
• Temperature probe error. heat pump. Ensure that the • Fan error. recommended minimum distances are maintained. • Incorrect installation. • Check the flow rate of the heat pump and ensure that it meets the requirements for each model. Solution DUAL CLIMA HT...
• Check water flow rate and verify that it is within recommended • Card or wiring error. values. • Incorrect reading of probes. • Check that there are no signs of rust or corrosion on the boards or cables. Solution DUAL CLIMA HT...
The room temperature has measurement error in the ambient Room temperature below fallen below the lower limit probe. limit. permitted (-25ºC). • Wait until the ambient temperature is within the working range of the heat pump. Solution DUAL CLIMA HT...
• Check that the probes are properly reversed or 4-way valve C07>2ºC. insulated. failure. • Flow and return probes • Reconnect 4-way valve, ensure reversed. correct wiring. • Failure in the 4-way • Check the correct functioning of the valve. 4-way valve. Solution DUAL CLIMA HT...
Communication failure with • Communication cable connectors and/or along the entire IPM module. fault. communication cable. • Interference in the • Check whether there are large communication cable. devices or strong magnetic fields around the unit. Solution: DUAL CLIMA HT...
1Ω in the compressor. • Fan problems. • Remove the three wires and measure whether the resistance between the two phases is balanced and around 1Ω in the IPM. • Replace IPM module. Solution: DUAL CLIMA HT...
1Ω in the compressor. • Compressor error. • Remove the three wires and measure whether the resistance • IPM module fault. between the two phases is balanced and around 1Ω in the IPM. • Replace IPM module. Solution: DUAL CLIMA HT...
• Inverted U, V, W cables. and around 1Ω in the compressor. • Remove the three wires and measure whether the resistance between the two phases is balanced and around 1Ω in the IPM. • Replace IPM module. Solution: DUAL CLIMA HT...
• Compressor current is too • Check whether the wiring of the IPM high. module is loose or damaged. • Check that the IPM module is not burnt out. • Replace the IPM module. Solution: DUAL CLIMA HT...
• Error in the power and that the power cable is not supply. loose. E20- PFC module failure in IPM. • Problems in the IPM • Check IPM wiring and inductance. Module. • Replace IPM or inductance. Solution DUAL CLIMA HT...
E20- Low voltage in (C24) is too low or unstable, the heat loose. pump will restart automatically when the • Check IPM wiring and inductance. voltage is within the admissible range. • Replace IPM or inductance. Solution DUAL CLIMA HT...
• Dual Clima 16HT; C35>21A. • Check water flow rate and verify • Dual Clima 16HTT; C19>21A. that it is within recommended values. • Check that there are no signs of rust or corrosion on the boards or cables. Solution DUAL CLIMA HT...
• Check the rest of the IPM and communication IPM module and the power board is inductive wiring. failure. disconnected. • Replace IPM. • Problems in the IPM Module. • Replace the PCB board. • PCB problems Solution DUAL CLIMA HT...
• Check that the power supply is OK and that the power cable is not loose. • Error in the power supply. E20- Phase loss • Check IPM wiring and inductance. • Problems in the IPM Module. • Replace IPM or inductance. Solution DUAL CLIMA HT...
• Check that the power supply is OK and Current that the power cable is not loose. • Error in the power supply. E20- sensor • Check IPM wiring and inductance. • Problems in the IPM Module. failure. • Replace IPM or inductance. Solution DUAL CLIMA HT...
OK. Also, check the cable for signs of damage. If everything is correct, first replace the HMI remote control and the communication cable. If this does not solve the problem, replace the power board. DUAL CLIMA HT...
12.3 Performance curves The following graphs describe the power of each Dual Clima HT model, depending on the external temperature. Dual Clima 6HT Dual Clima 9HT DUAL CLIMA HT...
15~20 minutes of compressor operation. In these cases ice will concentrate on the evaporator inlet tubes even at an external temperature of 14 °C. If ice appears when the air temperature >10°C, there may have been a leak. DUAL CLIMA HT...