ACIQ 30-EHPB Installation Manual

Manufactured housing electric furnace

Advertisement

EF**20FD-MH SERIES - MANUFACTURED HOUSING ELECTRIC FURNACE
Certified technicians or those individuals
WARNING
meeting the requirements specified by NATE
may use this information.Property and
product damage or personal injury hazard
may occur without such background.
This appliance is not intended for use by persons (including
children) with reduced physical, sensory, or mental capabilities,
or lack of experience and knowledge, unless they have been given
supervision or instruction concerning use of the appliance by a
person responsible for their safety. Children must be supervised to
ensure that they do not play with the appliance.
Product designed and manufactured to permit installation in
accordance with local and national building codes. It is the
installer's responsibility to ensure that the product is installed in
strict compliance with the aforementioned codes. Manufacturer
assumes no responsibility for damage (personal, product or
property) caused due to installations violating regulations.
Disconnect ALL power before servicing or
WARNING
installing this unit. Multiple power sources
may be present. Failure to do so may cause
property damage, personal injury, or death.
WARNING
Do not bypass safety devices.
Product designed and manufactured to
WARNING
permit installation in accordance with local
and national building codes. It is the
installer's responsibility to ensure that
product is installed in strict compliance with national and local
codes. Manufacturer takes no responsibility for damage (personal,
product or property) caused due to installations violating regu-
lations. In absence of local/state codes, refer to National Electric
Code: NFPA 90A & 90B Uniform Mechanical Code.
WARNING
This unit is NOT approved from outdoor
installations.
When this unit is installed in an enclosed
WARNING
area, such as a garage or utility room with
any Carbon Monoxide producing devices
(i.e. automobile, space heater, water heater
etc.) ensure that the enclosed area is properly ventilated.
Installation Guide
1. Safety Instruction
Potential safety hazards are alerted using the following symbols. The symbol is used in
conjunction with terms that indicate the intensity of the hazard. It is the responsibility of the
owner and the installer to read and comply with the safety information and the instructions
accompanying these symbols.
WARNING
This symbol indicates a potentially hazardous situation, which if not avoided,
could result in serious injury, property damage, product damage or death.
This symbol indicates a potentially hazardous situation, which if not avoided,
CAUTION
may result in moderate injury or property damage.
- 1 -
Only factory authorized kits and accessories
should be used when installing or modifying
CAUTION
this unit unless it is so noted in these
instructions. Some localities may require a
licensed installer/service personnel.
The unit is designed for operation with
WARNING
208/240 V, single phase, 60 Hz power supply.
ACiQ will not be responsible for damages
caused due to modification of the unit to operate with alternative
power sources.
If any hot work is to be conducted on the
WARNING
refrigerating equipment or any associated
parts, appropriate fire extinguishing
equipment shall be available to hand. Have a
dry powder or CO2 fire extinguisher adjacent to the charging area.
2. Introduction
This product is designed and manufactured to comply with
national codes. The product shall be installed in accordance
with national wiring regulations. It is the responsibility of the
installer to follow such codes and / or prevailing local codes /
regulations. The manufacturer assumes no responsibility for
equipment installed in violation of any codes or regulations.
The EF**20FD-MH Series air handlers are versatile Downflow
or Upflow units. These air handlers have the following
standard features:
I. Application Versatility
One unit for all, Downflow (Front Return) or Upflow (Bottom
Return) as shipped (field-convertible for downflow-front & top
return and downflow-top return).
II. Cabinet
Sturdy, galvanized steel cabinet with painted doors. Cabinet
fully insulated with ½" faced insulation and anti-microbial, to
encapsulate glass fibers and to provide excellent R- value.
Stick pins ensure insulation remains in place. Units ship with
disposable filter in filter rails. Max coil assembly height of
27.5".
IO-B300 | Revision B

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 30-EHPB and is the answer not in the manual?

Questions and answers

Summary of Contents for ACIQ 30-EHPB

  • Page 1 208/240 V, single phase, 60 Hz power supply. supervision or instruction concerning use of the appliance by a ACiQ will not be responsible for damages person responsible for their safety. Children must be supervised to caused due to modification of the unit to operate with alternative ensure that they do not play with the appliance.
  • Page 2: Installation Preparation

    III. Heat Kits For closet installation, the return air opening can be on the front door, above the furnace casing on a wall, or on the elec- EF**20FD-MH Series air handler heat kits are factory installed tric door’s louvered door (If applicable.) and available from 10 to 20 kW.
  • Page 3 BOTTOM PANEL (PART:151104) UPFLOW (BOTTOM RETURN) Fig. 4B-2A 4B-3. Filter Care COIL DECK ASM (PART: 141128) The filter should be checked every month. You may replace the filter by simply removing the single door and sliding out the existing one to replace it with a new filter. SOLID SINGLE DOOR (PART: 123202 TOP PANEL...
  • Page 4 4C. Conversion Kits ONE PIECE WRAPPER - CONFIGURATION TABLE BROCK CONFIGURATION RETURN DOOR KIT NEEDED FOR AIR MODEL CONVERTIBLE TO (DEFAULT) (DEFAULT) (DEFAULT) CONVERSION (DEFAULT) DOWNFLOW / FRONT & TOP RETURN – AEXK-01 LOUVER DOOR EF1020FD-MH EF1520FD-MH DOWNFLOW / TOP DOWNFLOW FRONT LOUVERED...
  • Page 5 4D-2. KIT# AEXK-02 (DOWNFLOW/FRONT RETURN to DOWNFLOW/TOP RETURN) KIT#: AEXK-02 KIT#: AEXK-02 DOWNFLOW/FRONT RETURN TO DOWNFLOW/TOP RETURN CONVERSION DOWNFLOW/ FRONT RETURN TO DOWNFLOW/ TOP RETURN CONVERSION TOP SOLID PANEL (PART: 151110) (STEP#2) TOP PANEL (PART: 141125) (STEP#4) BLOCK OFF PLATE SCREWS X14 (PART: 151101) FILTER RAILS (L&R)
  • Page 6: Electrical Installation

    5. Ductwork and Duct Connector All models with 5, 6, 8 or 10kW electric heat are arranged for single circuit connections. Models larger than 10kW are ar- Duct systems should be installed in accordance with stan- ranged for multi- circuit protection. Refer to the top part of wir- dards for air-conditioning systems, National Fire Protection ing diagram at the end of this guide for detailed information.
  • Page 7 5. If outdoor unit instructions and charts are not available, speed where the Y2 wire is connected (Fig 6B-1). use ACIQ’s provided charts. Make certain indoor air temperature is near comfort level setpoint 75F, prior to establishing superheat and subcooling levels.
  • Page 8: Blower Data

    7. Air Volume Adjustment Table BLOWER DATA MOTOR CFM V EXTERNAL STATIC MODEL SPEED TAP AMPS VOLTAGE EF1020FD & EF1520FD 1130 1100 1060 1020 1310 1280 1240 1200 1165 1130 1080 1050 1010 1130 1100 1060 1020 1340 1300 1265 1230 1200 1155...
  • Page 9 12. Wiring Diagram for EF**20FD-MH Model - 9 - IO-B300 | Revision B...
  • Page 10 2331 West State Route 55 Troy, OH 45373 1-877-909-ACiQ Phone: www.aciq.com Revised 09-2024. Subject to change without notice and without incurring obligation. © Copyright 2024 ACIQ. All Rights Reserved. IO-B300 | Revision B - 10 -...