Carrier 30RA-900 052 Series Installation & Operation Instructions
Carrier 30RA-900 052 Series Installation & Operation Instructions

Carrier 30RA-900 052 Series Installation & Operation Instructions

Chilled water storage tank accessory

Advertisement

Installation and Operation Instructions
Part No: 30RA-900---050; 30RA-900---051; 30RA-900---052
CONTENTS
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Step 1 - Rig and Place the Tank . . . . . . . . . . . . . . . 1
• RIGGING
• PLACING ACCESSORY TANK
• MOUNTING ACCESSORY TANK
Step 3 - Make Electrical Connections . . . . . . . . . . . 8
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

INTRODUCTION

The chilled water storage tank accessory permits a storage tank to
be mounted under the 30RAP chiller. Chilled water storage is rec-
ommended on some applications to maintain a desired loop vol-
ume, allowing the chiller to achieve the desired performance and
control compressor cycling. See Table 1 for usage.
Located in the control box included with the accessory are fasten-
ers to attach the chiller to the accessory tank. In addition to the
parts supplied with the accessory package, the following material
must be field-supplied:
Water piping between the tank system and the chiller
Tubing insulation (length determined by installation)
Table 1 - Package Usage
ACCESSORY PART NO.
30RA-900---050
30RA-900---051
30RA-900---052

SAFETY CONSIDERATIONS

Installing, starting up, and servicing air-conditioning equipment
can be hazardous due to system pressures, electrical components
and equipment location.
Only trained, qualified installers and service technicians should in-
stall, start up, and service this equipment.
When installing this accessory, observe precautions in the litera-
ture and on any labels attached to the equipment, and all other
safety precautions that may apply.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300276-01
Page
UNIT SIZE 30RAP
010,015
018-030
035-060
Printed in U.S.A.
Form No. 30RAP-21SI
Chilled Water Storage Tank
WARNING
Electrical shock can cause personal injury and death. Shut off
all power to this equipment during installation. There may be
more than one disconnect switch. Tag all disconnect locations
to alert others not to restore power until work is completed.
Follow all safety codes.
Wear safety glasses and work gloves.
Keep quenching cloth and fire extinguisher nearby when
brazing.
Use care in handling, rigging, and setting bulky equip-
ment. Refer to Table 2 for tank weights and Fig. 1 and 2
for rigging and weight information.

INSTALLATION

WARNING
Before beginning installation of this equipment, be sure all
power to the unit is disconnected, and that tags are properly
placed to alert others. Electrical shock can cause personal
injury and death.

Step 1 - Rig and Place the Tank

RIGGING
Use spreader bars to rig the unit at a single point with 4 cables and
hooks. Refer to the rigging label on the accessory for details con-
cerning rigging options, shipping weights, distance between lifting
holes, and center of gravity. See Fig. 1.
If overhead rigging is not possible, the accessory may be lifted
from either end, but care must be taken to align forks to slots pro-
vided in each rail for support. Care must be taken not to hit or
damage insulated tanks with forks.
PLACING ACCESSORY TANK
Determine the location of the accessory and 30RAP unit together.
Ensure that the location supports the filled weight of the tank sys-
tem and the chiller. See Table 2 and Fig. 2-5 for weights and di-
mensions. Since the 30RAP chiller mounts on top of the accesso-
ry, there must be at least 3 ft (0.9 m) for servicing and for unre-
stricted airflow on all non-coil sides of the unit, and a minimum of
3.5 ft (1.1 m) clear air space on coil sides. For multiple units, allow
8 ft (2.5 m) separation between units for airflow and service.
MOUNTING ACCESSORY TANK
When the accessory is in the proper location, the use of mounting
holes in base rails is recommended for securing the accessory to
supporting structure, or for mounting the accessory on vibration
isolators if required. See Fig 3-5. Fasteners for mounting the ac-
cessory are field supplied. Be sure the accessory is level to within
1/8 in. per foot for proper oil return in the 30RAP chiller mounted
on top.
Pg 1
30RAP010-060
Accessory
10-23
Replaces: 30RAP-15SI

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 30RA-900 052 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Carrier 30RA-900 052 Series

  • Page 1: Table Of Contents

    30RAP010-060 Chilled Water Storage Tank Accessory Installation and Operation Instructions Part No: 30RA-900---050; 30RA-900---051; 30RA-900---052 CONTENTS WARNING Page Electrical shock can cause personal injury and death. Shut off INTRODUCTION ......1 all power to this equipment during installation.
  • Page 2: Mounting Unit To Accessory Tank

    MOUNTING UNIT TO ACCESSORY TANK Table 2 — Tank Capacities/Weights The 30RAP chiller mounts on top of the rails of the tank accesso- WEIGHT WEIGHT VOLUME ry. The 30RAP chiller piping connections should be located near (FILLED (UNFILLED) 30RA-900--- the end of the accessory tank that has the piping connections. This Gal.
  • Page 3 Unit Weights Standard Units with Accessory Tank POUNDS KILOGRAMS 30RAP 30RAP Total Total SIZE SIZE Weight Weight 2377 275.2 284.3 262.8 255.8 1078.2 2391 277.4 286.1 263.8 257.1 1084.4 3318 413.6 368.5 343.6 379.3 1505.0 3326 414.5 369.5 344.5 380.2 1508.7 3435 427.0...
  • Page 7: Step 2 - Connect Cooler Fluid And Drain Piping

    Consult local water treatment specialist on characteristics of water Step 2 — Connect Cooler Fluid and Drain Piping and recommended inhibitor. The piping between the chiller and the accessory tank can be done to allow the tank to be on the return side of the chiller (tank piped to chiller inlet) or the supply side of the chiller (tank piped to the Accessory 30RAP...
  • Page 8: Step 3 - Make Electrical Connections

    Water Inlet (Hidden) Water Outlet (Hidden) Tank Inlet/outlet Fig. 8 — Typical Piping Layout — 30RA-900---052 Connect red and brown control wires from conduit to red and Step 3 — Make Electrical Connections brown wires in tank control box using wire nuts supplied in POWER SUPPLY hardware kit.
  • Page 9 Conduit Hole Location Fig. 9 — Conduit Hole Location — 30RAP010-015 Conduit Hole Location Fig. 10 — Conduit Hole Location — 30RAP018-030...
  • Page 10 Conduit Hole Location Fig. 11 — Conduit Hole Location — 30RAP035-060 Power Entry Fig. 12 — Tank Heater Control Box Power Entry...
  • Page 11 POWER *See Table 3. CONTROL BOX 1 - ALL CONTROL BOX 2 - 30RA035, 040, 045, 050, 055 AND 060 ONLY TANK HEATER WIRING CONTROL CONNECT TO THE RED WIRE LABELED TNK-R NEAR LVT T'STAT CONTROL BOX 2 CONTROL BOX 1 TNKR2 30RA-900---052 ONLY LEGEND...
  • Page 12 Fig. 14 — Tank Warning Label Re-Route EXV and Hps Here POWER HARNESS ENTRY EWT,LWT PUMP RGT,CWFS PLUG(S) COMP (A2) SPT,DPT,DDT COMP (A1) H.E. HEATER PUMP(S) HEATER Fig. 15 — Re-Route Hole Location — 30RAP018-030 Re-Route HPS-B Here HPS-B HPS-A FANS HARNESS POWER ENTRY DPT-A...
  • Page 13: Operation

    FB-1 TRAN CCB-2 CCB-1 FB-3 CSB-A1 CSB-A2 DISCONNECT OPTION/TB CWP1 CWP2 C-A1 C-A2 CWP1CWP2 FC1/MM Typical Power BLK and YEL Wiring Path Power Wires Conduit Fig. 17 — Tank Power Connections The tank heaters are wired in the control circuit so that they are op- OPERATION erable as long as the main power to the chiller is ON.
  • Page 14: Appendix A - Pressure Drop Curves

    APPENDIX A — PRESSURE DROP CURVES Storage Tank Pressure Drop Curves 100.0 30RAP035-060 10.0 30RAP010-030 1000 ACCESSORY TANK FLOW RATE (gpm) 100.0 30RAP035-060 10.0 30RAP010-030 10.0 ACCESSORY TANK FLOW RATE (L/s)
  • Page 16 © 2023 Carrier Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Catalog No. 04-53300276-01 Printed in U.S.A. Form No. 30RAP-21SI Pg 16 10-23 Replaces: 30RAP-15SI...

Table of Contents