Table of Contents 765-2704/200-000 Table of Contents Provisions......................... 4 Intended Use ...................... 4 Typographical Conventions.................. 5 Legal Information .................... 7 Safety .......................... 8 General Safety Rules .................... 8 Electrical Safety....................... 8 Mechanical Safety .................... 8 Indirect Safety ...................... 8 Thermal Safety ...................... 9 Overview ......................... 10 Properties ........................ 11 View........................
Page 3
765-2704/200-000 Table of Contents Process Image – Representation of the Voltage Value on the Output.. 23 5.3.3 Planning .......................... 24 Structure Guidelines.................... 24 Overcurrent Protection ................. 24 6.1.1 EMC Installation ................... 24 6.1.2 Connection Example .................. 25 6.1.3 Behavior in the Event of a Communication Interruption ........ 25 Examples and Aids....................
The terms set forth in the General Business and Contract Conditions for Delivery and Service of WAGO GmbH & Co. KG and the terms for software products and products with integrated software stated in the WAGO Software License Contract – both available at ü www.wago.com...
765-2704/200-000 Provisions Obligations of Installers/Operators The installers and operators bear responsibility for the safety of an installation or a sys- tem assembled with the products. The installer/operator is responsible for proper installa- tion and safety of the system. All laws, standards, guidelines, local regulations and ac- cepted technology standards and practices applicable at the time of installation, and the instructions in the the products’...
Page 6
Provisions 765-2704/200-000 Figures Figures in this documentation are for better understanding and may differ from the actual product design. Notes DANGER Type and source of hazard Possible consequences of hazard that also include death or irreversible injury • Action step to reduce risk WARNING Type and source of hazard Possible consequences of hazard that also include severe injury...
Third-party products are always mentioned without any reference to patent rights. WAGO GmbH & Co. KG, or for third-party prod- ucts, their manufacturer, retain all rights regarding patent, utility model or design registra- tion.
• Only use a dry or cloth or a clothed dampened with water to clean the product. Do not use cleaning agents, e.g., abrasive cleaners, alcohols or acetone. • Only permit skilled personnel approved by WAGO to perform repair work. • Replace any defective or damaged devices.
765-2704/200-000 Safety 2.5 Thermal Safety • Observe permissible temperature range of connecting cables. • The conductor cross-sections must be designed for the maximum load current. Product manual | Version: 1.0.0 2AO FLD IOL CONV 0-10V...
The Analog/IO-Link Converter provides an economical, compact solution for easily incor- porating conventional analog sensors and actuators into an IO-Link-capable system like the WAGO I/O System Field, depending on their type. This allows reliable, cost-effective, interference-immune acquisition and output of analog signals. Digital communication can easily be introduced (retrofitted) when old systems are modernized.
765-2704/200-000 Properties 4.3 Connections Figure 3: Connections Table 3: Legend for Figure “Connections” Custom Name IO-Link side (M12 A plug) 8 IO-Link Side [} 13] Actuator side (M12 A socket) 8 Actuator Side [} 13] 4.3.1 IO-Link Side Table 4: IO-Link Side (M12 A Plug) Connection Signal Description 24 VDC supply Not assigned...
IO-Link specification. This allows read and write access to the ISDU ob- jects. The product is parameterized via an IO-Link tool (e.g., WAGO IO-Link Configurator), The terms “index” and “subindex” used in the following tables refer to Indexed Service Data Units (ISDUs).
Subindex Data Length Factory Value Range Type Setting Manufacturer Manufacturer StringT 19 bytes WAGO GmbH name assigned & Co. KG to a manufac- turer ID 5.2.4 Manufacturer Text Table 13: Variables – Manufacturer Text – General Index Access rights Read-only Product manual | Version: 1.0.0...
Subindex Data Length Factory Value Range Type Setting Manufacturer Additional infor- StringT 11 bytes WAGO IO-Link text mation on the Converter manufacturer 5.2.5 Product Name Table 15: Variables – Product Name – General Index Access rights Read-only Table 16: Variables – Product Name...
Functions 765-2704/200-000 Table 22: Variables – Serial Number Name Description Subindex Data Length Factory Value Range Type Setting Serial number Unique manu- StringT 12 bytes facturer-spe- cific identifier of the individual product 5.2.9 Hardware Version Table 23: Variables – Hardware Version – General Index Access rights Read-only...
765-2704/200-000 Functions Table 28: Variables – Application-Specific Attribute Name Description Subindex Data Length Factory Value Range Type Setting Application- Option for tag- StringT 32 bytes Specific At- ging the prod- tribute uct with user- or application- specific infor- mation 5.2.12 Function Tag Function tag (customer-specific system ID), max.
Functions 765-2704/200-000 5.3 Process Image Figure 6: Input and Output Process Data 5.3.1 Input Process Data Table 33: Input Process Data Byte Data Type Content Value Range Description (Bits) Offset UIntegerT (4) Device status Maintenance required Outside specification Function test Error 5.3.2 Output Process Data Table 34: Output Process Data Byte Data...
765-2704/200-000 Functions 5.3.3 Process Image – Representation of the Voltage Value on the Output Figure 7: Analog Value Representation Product manual | Version: 1.0.0 2AO FLD IOL CONV 0-10V...
Planning 765-2704/200-000 Planning 6.1 Structure Guidelines 6.1.1 Overcurrent Protection Protecting Circuits against Overcurrent Protect the circuits by using a fuse. Table 35: Protecting Circuits against Overcurrent Potential M12 A plug Fuse 1L+ / power supply Pin 1 ≤2 A C/Q IO-Link Pin 4 ≤2 A (if not fused via IO-Link master) Required trip characteristics of the fuses: ≤120 s at max.
6.3.1 Aids The parameters are set with an I/O-Link tool, e.g., WAGO IO-Link Configurator. You can obtain the WAGO IO-Link Configurator software, as well as the associated prod- uct manual with a detailed description of the software, from ü www.wago.com. Product manual | Version: 1.0.0...
Installation and Removal 765-2704/200-000 Installation and Removal 7.1 Mounting 7.1.1 Mounting the Product on a Mounting Clip The product can be secured with a Mounting Clip. Figure 9: Mounting Clip (Secured with an M4 Screw or Cable Tie) Figure 10: Mounting Clip with Product Attached 8 Ac- The Mounting Clip is not included upon delivery.
765-2704/200-000 Connection Connection 8.1 Connecting the Plug The mounting method must not cause mechanical stress on the M12 connection parts. Depending on the conditions of use, it may also be necessary to protect the product against mechanical stresses (shock/vibration) through appropriate mounting. ü...
Commissioning 765-2704/200-000 Commissioning Note Commissioning via parameter channel The product is both commissioned and configured via the parameter channel. You can find the individual parameters and additional information in 8 Parameter De- scription [} 17]. 9.1 Configuration and Parameterization Note The product is in operating mode during parameterization During the parameterization process, the product remains in operating mode.
765-2704/200-000 Transport and Storage Transport and Storage The original packaging offers optimal protection during transport and storage. • Store the product in suitable packaging, preferably the original packaging. • Only transport the product in suitable containers/packaging. • Make sure the product contacts are not contaminated or damaged during packing or unpacking.
Diagnostics 765-2704/200-000 Diagnostics 11.1 Diagnostics via Indicators Table 37: Diagnostics via Indicators LED State Explanation The analog value is in the normal range: 0 ... 100 % (0 ... 10 V) Flashing (2 Hz) The analog value is in the range: 100 ... 110 % (10 ... 11 V) Flashing (5 Hz) There is a short circuit or overload at the output. POWER The supply voltage is OK.
Page 31
765-2704/200-000 Diagnostics Table 41: Variables – Detailed Diagnostics Name Description Subindex Data Length Factory Value Range [h] Type Setting Detailed device List of all cur- ArrayT 24 bytes 00 00 00 status rently pending events of the product 11.2.3 Active Events Table 42: Variables – Active Events – General Index Access rights Read-only...
Diagnostics 765-2704/200-000 Table 45: Variables – Parameter Setting Errors Name Description Subindex Data Length Factory Value Range Type Setting Parameter set- Indicates the ArrayT 10*32 bits 0 0 (OK) ting error parameter that 786432 (device access was set incor- blocks, index 12) rectly at the time of down- load...
Page 33
765-2704/200-000 Diagnostics Code Device status Name Type Description 30480 d 3 (Function Short circuit Error Check installation 0x7710 test) 35856 d 2 (Outside Process value Warning Process value uncertain 0x8C10 specification) outside valid Note: This event is not transferred on the range event channel. It can only be read out via in- dex 37 (detailed diagnostics) or 545 (Bit- Coded_ActiveEvents).
Decommissioning 765-2704/200-000 Decommissioning 12.1 Disposal and Recycling WEEE Mark Electrical and electronic equipment may not be disposed of with household waste. This also applies to products without this mark. Electrical and electronic equipment contain materials and substances that can be harmful to the environment and health.
13.1 Technical Data, Approvals, Guidelines and Standards See also 2 Data_sheet_765-2704/200-000 [} 36] Note Subject to changes! Please also observe the further product documentation! You can generate the current ü www.wago.com datasheet at any time at: /<item number>. Product manual | Version: 1.0.0 2AO FLD IOL CONV 0-10V...
Page 36
Housing material Indicators Analog output: 2 x LED, yellow; Power: 1 x LED, green Length of connection cables 20 m WAGO GmbH & Co. KG Postfach 2880 - D-32385 Minden Phone: +49(0)571/887-0 Email: info@wago.com 10.05.22 Subject to changes Hansastr. 27 - D-32423 Minden Fax: +49(0)571/887-844169 www.wago.com...
765-2704/200-000 Appendix 13.2 Installation Regulations Specified by Approvals For the Scope of cULus: Electricity can only be supplied by via SELV/PELV circuits. Device powered according to “Limited Energy” per UL 61010-1, chapter 9.4. External circuits must be isolated per UL 61010-2-201, figure 102.
Page 38
Appendix 765-2704/200-000 • OPC UA is a registered trademark of the OPC Foundation. ® • PROFIBUS is a registered trademark of the PROFIBUS Nutzerorganisation e.V. (PNO). ® • PROFINET is a registered trademark of the PROFIBUS Nutzerorganisation e.V. (PNO). • QR Code is a registered trademark of DENSO WAVE INCORPORATED. ®...
Page 39
765-2704/200-000 List of Figures List of Figures Figure 1 View ..........................Figure 2 Indicators – LEDs......................Figure 3 Connections ........................Figure 4 Dimensional Drawings ....................Figure 5 Circuit Diagram ......................Figure 6 Input and Output Process Data..................Figure 7 Analog Value Representation ..................Figure 8 Connection Example with IO-Link Master ..............
Page 40
List of Tables 765-2704/200-000 List of Tables Table 1 Legend for Figure “View” ....................Table 2 Legend for Figure “Indicators – LEDs”................Table 3 Legend for Figure “Connections” ..................Table 4 IO-Link Side (M12 A Plug) ....................Table 5 Actuator Side (M12 A Socket).................... Table 6 Technical Data –...
Page 42
WAGO is a registered trademark of WAGO Verwaltungsgesellschaft mbH. Copyright – WAGO GmbH & Co. KG – All rights reserved. The content and structure of the WAGO websites, catalogs, videos and other WAGO media are subject to copyright. Distri- bution or modification of the contents of these pages and videos is prohibited. Furthermore, the content may neither be copied nor made available to third parties for commercial pur-...
Need help?
Do you have a question about the 2AO FLD IOL CONV 0-10V and is the answer not in the manual?
Questions and answers