FILTOMAT M104C Installation, Operation And Maintenance Manual

Automatic water filters

Advertisement

FILTOMAT
®
Automatic Water Filters
Installation, Operation and
Maintenance Manual
M100-750 & 1500 Series
Models: M102C, M103C & M104C
Model No:
Serial No.:
Screen Size:
TRIANGLE FILTRATION & IRRIGATION
17 Hinkler Road, Mordialloc, Vic. 3195 .Australia
Ph: 03 9580 2122
Fax: 03 9580 3131
www.trianglefiltration.com.au

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the M104C and is the answer not in the manual?

Questions and answers

Summary of Contents for FILTOMAT M104C

  • Page 1 FILTOMAT ® Automatic Water Filters Installation, Operation and Maintenance Manual M100-750 & 1500 Series Models: M102C, M103C & M104C Model No: Serial No.: Screen Size: TRIANGLE FILTRATION & IRRIGATION 17 Hinkler Road, Mordialloc, Vic. 3195 .Australia Ph: 03 9580 2122 Fax: 03 9580 3131 www.trianglefiltration.com.au...
  • Page 2: Table Of Contents

    Parts drawing #5 - Collector assembly M104C.............17 Control system - Hydraulic ..................18 Screen removal procedure ..................19 Warranty.........................20 Note : Please quote the Filter Model Number, located on the filter housing with your inquiry. FILTOMAT M100-750 Installation & maintenance – 06.2005...
  • Page 3: Introduction

    The FILTOMAT® M100C series filter is a well designed, simple to install and easy-to-operate automatic water filter. The FILTOMAT will work with a range of fine screen mesh sizes from 50 to 800 micron, to suit various applications and is available with 2"& 3" BSP female inlet/outlet ports and 4” flanged.
  • Page 4: Specifications

    Reinforced nylon, brass, stainless steel Control tubing Polyethylene Seals BUNA-N Control Brass, Stainless Steel , PVC, Acetal Filtration screen sizes available Type Moulded screen Flat screen micron 0.13 0.08 0.15 0.13 0.08 0.05 FILTOMAT M100-750 Installation & maintenance – 06.2005...
  • Page 5: Safety Instructions

    Avoid working below lifted equipment. Wear a safety helmet when using lifting equipment. Beware of overhead electrical power lines. DIMENSIONAL INSTALLATION DRAWING NOTE: This is a conceptual installation drawing. (piping /valves etc. are not included.) FILTOMAT M100-750 Installation & maintenance – 06.2005...
  • Page 6: Dimensional Installation Diagram

    (15.7") (29.6") Key: 1. 2" Inlet manifold 2. 2" Inlet butterfly valve 3. 2" Filtomat M102-C filter 4. 2" Outlet butterfly valve 5. 2" Bypass butterfly valve 6. 2" Outlet manifold * Minimum length required for servicing. Filters may be installed either in a vertical or horizontal position to suit your application.
  • Page 7: Operating Principles

    This self-cleaning process takes approximately 10 seconds, depending on the operating pressure. Exhaust valve Drain Rotor chamber Rotor Fine screen Collector pipe Outlet Rinse controller Nozzles Dirt collector Inlet FILTOMAT M100-750 Installation & maintenance – 06.2005...
  • Page 8: Installation

    Install a manual isolating valve before (upstream) the filter if there is any static head on the inlet side. If the inlet operating pressure falls below 250 kPa install a pressure sustaining valve (PSV) after the filter. NOTE: Once pressurized the filter may flush automatically, without prior warning. FILTOMAT M100-750 Installation & maintenance – 06.2005...
  • Page 9: Commissioning

    9. During the self-cleaning cycle, check the pressure at the filter inlet does not drop below 200 kPa, and check the pressure in the rotor chamber. NOTE: The minimum pressure in the rotor chamber should be 150 kPa lower than the inlet pressure. FILTOMAT M100-750 Installation & maintenance – 06.2005...
  • Page 10: Adjusting The Rinse Controller

    (1). This adjusts the rinse controller for a differential pressure of approx. 50 kPa. 5. Observe at least one automatic self-cleaning cycle, if possible, checking the differential set point with the gauge on the 3–way valve. FILTOMAT M100-750 Installation & maintenance – 06.2005...
  • Page 11: Maintenance

    PSV valve is fitted) maintain at least 200 kPa backpressure on the filter while doing this. Once the pipeline has been pressurised open the valve fully. Note: If in doubt, please call us for assistance. FILTOMAT M100-750 Installation & maintenance – 06.2005...
  • Page 12: Parts Schedule

    Nipple 1 1/2” BSP 83-2920-0150-0105 Filter lid assembly 15-1070-0024 Rinse controller 15-1007-0101 12.1 Bolt ¼” 85-4111-04-012 Filter lid 55-1070-0090 3-Way valve 84-31-70-0011 O-Ring 6x3mm 81-41-4100-0603 13.1 Nipple ¼” x 1/8” 83-4324-1012-1925 Plug 1/4" BSP 82-11-0121-0400 FILTOMAT M100-750 Installation & maintenance – 06.2005...
  • Page 13: Parts Drawing #1 - Exploded View M102C & M103C

    PARTS DRAWING #1 – Filter Exploded View M102/3 FILTOMAT M100-750 Installation & maintenance – 06.2005...
  • Page 14: Parts Drawing #2 - Cover Lid Assembly. All Models

    PARTS DRAWING #2 – Cover Lid Assembly M102/3&4 FILTOMAT M100-750 Installation & maintenance – 06.2005...
  • Page 15: Parts Drawing #3 - Collector Assembly M102C & M103C

    PARTS DRAWING #3 - Collector/Rotor Assembly M102/3 FILTOMAT M100-750 Installation & maintenance – 06.2005...
  • Page 16: Parts Drawing #4 - Exploded View M104C

    PARTS DRAWING #4 – Exploded View – M104C FILTOMAT M100-750 Installation & maintenance – 06.2005...
  • Page 17: Parts Drawing #5 - Collector Assembly M104C

    DRAWING #5 – Collector/Turbine Assembly – M104C FILTOMAT M100-750 Installation & maintenance – 06.2005...
  • Page 18: Control System - Hydraulic

    Hydraulic Control System d r a i n 1 = Green 8 mm fittings 7 = Red 6 mm fittings 3 & 5 = Black 6 mm fittings FILTOMAT M100-750 Installation & maintenance – 06.2005...
  • Page 19: Screen Removal Procedure

    FILTOMAT M100-750 Installation & maintenance – 06.2005...
  • Page 20: Warranty

    Faulty replaced parts are to be returned to Triangle Filtration for inspection and assessment, so they in turn can claim warranty replacements from the manufacturer. If you have any questions, contact your local dealer or our service department. FILTOMAT M100-750 Installation & maintenance – 06.2005...

Table of Contents