Data creazione documento: 04.06.2019- PG The professional instrument for Set of probes for all the detection and localization purposes to use with of gas leaks for CH4 e C3H8 HUBERG instruments: with Bluetooth and GPS. carpet probe, sucker There is also a version with an probe, flexible probe, Ethane sensor.
Document creation date: 03.10.2019- RC GENERAL DESCRIPTION RIVELGAS plus / EX-PEX plus / Rivelgas Combi are a new family of portable devices for localization of gas leak and for personal safety. Depending on the device model, they are used either to check pipes, gas leak detection or for personal safety.
Form creation date: 01.04.2008 - SpKa Document creation date: 03.10.2019- RC Keyboard and display layout Fig. 2 The device has a keyboard with three keys in order to enter the menu. KEY “OK/START” is used to: 1. turn on/off the device 2.
“EXPL”, used for personal safety 100%, diffusion mode “1” and “VOL” symbol, for Rivelgas Plus 1% with pump “100” and “VOL” symbol, for Rivelgas Plus 100% with pump ...
Form creation date: 01.04.2008 - SpKa Document creation date: 03.10.2019- RC o In case the instrument notices sensor malfunctioning, the word “S Er” appears on screen, and buzzer beeps for 5 seconds, before the instrument switches off. Device is ready to use and measure is shown. WARNING: in order to have a correct calibration of the device, it has to be turn on in a place with no gas.
Form creation date: 01.04.2008 - SpKa Document creation date: 03.10.2019- RC (system alarm cannot be turned off). Led alarm will flash independently. When system alarm is reached, buzzer will sound and it cannot be turned off. Led alarm will flash. For Ex-Pex 09 model: once measurement exceeds system threshold (generally 2,2%VOL), the display will show a blinking value of 2,2% (indicating that true measurement may fall above that value), and buzzer will sound with higher frequency.
Form creation date: 01.04.2008 - SpKa Document creation date: 03.10.2019- RC 3.10 PoFF In the instruments with pump if there is an occlusion of the tube the instrument block the pump in order to protect the instrument. In order to start the pump again you must click on “Down” key. 11/21...
Form creation date: 01.04.2008 - SpKa Document creation date: 03.10.2019- RC BATTERY CHARGE To charge batteries, switch off the instrument and insert it in the charger support (see fig. 3). A LED will indicate battery charge state. Led flashes once per second: it means that it is charging batteries in fast-charge mode. Led flashes twice per second: it means that it is charging in maintaining/trickle charge mode.
Form creation date: 01.04.2008 - SpKa Document creation date: 03.10.2019- RC MAINTENANCE AND PERIODICAL CALIBRATION For a proper operation and good reliability of the device, QED Environmental Systems Limited suggests to control and calibrate the instrument periodically, and at least, once a year. It is reminded that QED Environmental Systems Limited releases a calibration certificate (ISO 9001) after each instrument calibration.
Form creation date: 01.04.2008 - SpKa Document creation date: 03.10.2019- RC 7 APPENDIX A – SAFE USE OF THE INSTRUMENT INTRODUCTION This safety instruction is for installing, working and for the maintains of the gas leak detector instrument RIVELGAS/EXPEX type and for use it in areas with potentially explosive atmospheres. The equipment covered by these instructions is characterized by the following marking: II 2G Ex ib d IIC T4 Gb The information contained in these safety instructions must be followed in addition to the warnings...
Page 18
Form creation date: 01.04.2008 - SpKa Document creation date: 03.10.2019- RC Security Summary Instrument for detecting the presence of gases or vapors of category 2 suitable II 2 G for zone 1 with redundancy for zone 2 Instrument with intrinsically safe circuits and chamber of analysis for Gas with Ex ia d explosion-proof enclosure Equipment for gasses of group IIB and IIA...
Form creation date: 01.04.2008 - SpKa Document creation date: 03.10.2019- RC APPENDIX B - INFORMATION ON DISPOSAL FOR USERS OF WASTE ELECTRICAL & ELECTRONIC EQUIPMENT (PRIVATE HOUSEHOLDS) This symbol on the product(s) and / or accompanying documents means that used electrical and electronic products should not be mixed with general household waste.
Need help?
Do you have a question about the RIVELGAS COMBI and is the answer not in the manual?
Questions and answers