MDE-2530H Pump and Dispenser DIESEL REGULAR UNLEADED PREMIUM REGULAR Installation Manual Please see MDE-2833 for Site Prep Information. ®...
Page 2
Approvals Underwriters Laboratories: Gilbarco pumps and dispensers that bear the U.L. listing mark are listed under the U.L. file number MH1941. National Quality Assurance: Gilbarco is an ISO9001/BS5750 Part 1/EN29001 registered company, certificate number 5119.
Introduction Introduction Purpose Of This manual gives step by step instructions for installing Gilbarco pumps and This Manual dispensers. It does not include site preparation instructions (see MDE-2833 Pump and Dispenser Site Prep). After the installation is complete, a Gilbarco Authorized Service Contractor must commission the unit to activate the warranty.
Products that bear the authorized Listing Mark of U.L. as the manufacturer’s declaration that the product complies with U.L.’s requirements in accordance with the terms of U.L.’s Listing and Follow-Up Service agreement. Page 2 MDE-2530H Gilbarco Pump and Dispenser Installation Manual • 03/95...
Page 5
Class 1 Division 1 within boot area. 48" Pit box. Pit box. 18" Note: The optional field installed canopy (if needed) must be listed for use over hazardous locations. MDE-2530H Gilbarco Pump and Dispenser Installation Manual • 03/95 Page 3...
Page 6
No open No smoking. No power tools. Wear eye flames. protection. Read all related Clean up spills. Turn power off. Collect fuel in manuals. approved containers. Page 4 MDE-2530H Gilbarco Pump and Dispenser Installation Manual • 03/95...
NFPA 30A and NFPA 70. Equipment manufacturer must provide instructions for other equipment, such as submerged turbine pumps (STPs), leak detectors, and underground tanks. Gilbarco does not provide installation instructions for other manufacturer’s equipment. Installation 1. Read all instructions before beginning.
Page 8
Shear Valves (dispensers only) 5. Inspect pump/dispenser cartons and contents for shipping damage. Check tip-and- tell indicator. Gilbarco does not cover shipping damage under its warranty policy. Notify the shipper of any damage. 6. Remove lower panels (doors) of pump/dispenser.
Page 9
• Use nylon slings (safety lift factor of 5) with hoisting brackets to lift unit onto island. The Advantage Series requires three nylon slings and four screw pin shackles. The MPD and Salesmaker series requires two nylon slings and two screw pin shackles.
Page 10
Fire/Explosion could result in severe injury or death. NFPA 30A requires anchoring pumps/dispensers. Install all anchor bolts on the unit for safe operation of shear valves and hose breakaways. Page 8 MDE-2530H Gilbarco Pump and Dispenser Installation Manual • 03/95...
Page 11
Wire all circuits N.E.C. Class 1, except outputs to speaker (intercom) which must be N.E.C. Class 2. Gilbarco two-wire is N.E.C. Class 1 and may share the main power conduit. 2. All field wiring (except speaker) enters the pump/dispenser through the AC Main Junction Box on the “A”...
Page 12
26. Double check all wiring connections for wire nuts, lugs, caps, etc. Replace junction box cover and tighten all bolts. Do not use gaskets on junction box. Do not pinch wires. 27. Replace lower doors and side sheathing. Page 10 MDE-2530H Gilbarco Pump and Dispenser Installation Manual • 03/95...
Page 13
32. Check for correct nozzle cradle/hook type (vapor, non-vapor, etc.). 33. Do not turn on AC power. Applying power now voids warranty. When installation is complete, a Gilbarco Authorized Service Contractor must perform a start-up. MDE-2530H Gilbarco Pump and Dispenser Installation Manual • 03/95...