SM_AG(GA)_R32_3D INV_EU_NB_2006 XTREME 3D INVERTER SERIES SERVICE MANUAL...
Page 3
Table of Contents §. Safety Precautions Precautions Information servicing(For flammable materials) §. Specifications Model Reference Pipe length and the Drop Height Electrical Wiring Diagrams §. Product Features Display Function Safety Features Basic Features Optional Features §. Maintenance First Time Installation Check Refrigerant Recharge Re-Installation §.
Page 4
Table of Contents §. Troubleshooting Safety Caution General Troubleshooting Complain Record Form Information Inquiry Error Diagnosis and Troubleshooting Without Error Code Quick Maintenance by Error Code Troubleshooting by Error Code Check Procedures Appendix Temperature Sensor Resistance Value Table for T1,T2,T3 and T4 (°C – K) Temperature Sensor Resistance Value Table for TP(for some units) (°C –...
Page 7
1. Precautions CAUTION To prevent personal injury, or property or unit damage, • • While unpacking be careful of sharp edges around adhere to all precautionary measures and instructions the unit as well as the edges of the fins on the con- denser and evaporator.
Page 8
2. Information servicing(For • Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable flammable materials) hazards or ignition risks. • NO SMOKING signs shall be displayed. Checks to the area Ventilated area •...
Page 9
• that capacitors are discharged: this shall be done in shall also take into account the effects of aging or a safe manner to avoid possibility of sparking; continual vibration from sources such as compressors or fans. • that there no live electrical components and wiring are exposed while charging, recovering or purging 2.13 Detection of flammable refrigerants the system;...
Page 10
• The refrigerant charge shall be recovered into the • Before attempting the procedure ensure that: correct recovery cylinders. The system shall be flushed • mechanical handling equipment is available, if with OFN to render the unit safe. This process may required, for handling refrigerant cylinders;...
Page 11
• Empty recovery cylinders are evacuated and, if • The recovered refrigerant shall be returned to the possible, cooled before recovery occurs. refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged. Do not • The recovery equipment shall be in good working mix refrigerants in recovery units and especially not in order with a set of instructions concerning the cylinders.
Page 12
Specifications Contents Model Reference ....................2 Pipe Length and Drop Height ................3 Electrical Wiring Diagrams ..................4...
Page 13
1. Model Reference Refer to the following table to determine the specific indoor and outdoor unit model. Indoor Unit Model Outdoor Unit Model Capacity (Btu/h) Power Supply MSAGBU-09HRFN8-QRD1GW(GA) MOX230-09HFN8-QRD6GW 220-240V~, 50Hz, 1Phase MSAGBU-12HRFN8-QRD1GW(GA) MOX230-12HFN8-QRD6GW Specifications 2 ...
Page 14
2. Pipe Length and Drop Height The length and elevation of connection pipe are shown in the table below. if the pipe length exceeds max pipe length, additional refrigerant should be charged to ensure nominal cooling/heating capacity. Capacity(Btu/h) Standard Length Max Pipe Length Max Elevation Additional Refrigerant...
Page 15
3. Electrical Wiring Diagrams Indoor and outdoor unit wiring diagram Indoor Unit Outdoor Unit IDU Model IDU Wiring Diagram ODU Model ODU Wiring Diagram MSAGBU-09HRFN8-QRD1GW(GA) MOX230-09HFN8-QRD6GW 16022000019533 16022000020169 MSAGBU-12HRFN8-QRD1GW(GA) MOX230-12HFN8-QRD6GW Outdoor unit printed circuit board diagram Outdoor Unit ODU Model...
Page 16
Indoor unit abbreviations Abbreviation Paraphrase Yellow-Green Conductor Positive and Negative Ion Generator Capacitor PLASMA Electronic Dust Collector LIVE NEUTRAL Outdoor unit abbreviations Abbreviation Paraphrase 4-WAY Gas Valve Assembly/4-WAY VALVE AC-FAN Alternating Current FAN DC-FAN Direct Current FAN COMP Compressor L-PRO Low Pressure Switch H-PRO High Pressure Switch...
Page 17
Indoor unit wiring diagram: 16022000020169 OPTIONAL OPTIONAL Applicable to INDOOR WIRING DIAGRAM AC motor only 16022000020169 5(3or2) HEATER SWITCH BOARD CN701 OPTIONAL HA HB E 12V/5V Applicable for MULTI and MONO unit without 1W standby control feature OPTIONAL Applicalbe for MONO unit with OPTIONAL 1W standby control feature To Randomly...
Page 18
Outdoor unit wiring diagram: 16022000019533...
Page 19
Outdoor unit printed circuit board diagram: 17122000044714, 17122000048121...
Page 20
Name Meaning Earth: connect to Ground N_in: connect to N-line (208-230V AC input) CN1A L_in: connect to L-line (208-230V AC input) CN16 S: connect to indoor unit communication HEAT1 CN17 connect to compressor heater, 208-230V AC when is ON 4-WAY CN60 connect to 4 way valve, 208-230V AC when is ON.
1. Display Function Unit display functions fresh defrost run timer Display A Display B Display Function fresh Fresh(available on select units only) defrost Defrost When the unit is on timer When TIMER is on WiFi control (available on select units only) Temperature value Temperature Activation of Timer ON, Fresh, Swing, Turbo, or Silent...
2. Safety Features Compressor three-minute delay at restart Compressor functions are delayed for up to ten seconds upon the fi rst startup of the unit, and are delayed for up to three minutes upon subsequent unit restarts. Automatic shutoff based on discharge temperature If the compressor discharge temperature exceeds a certain level for a period of time, the compressor ceases operation.
3. Basic Functions frequency(FminC). • Compressor runs at FminC more than 10 minutes. Abbreviation • T1 is lower than or equal to (Tsc-CDIFTEMP). Note: CDIFTEMP is EEPROM setting parameter. It is 2°C Unit element abbreviations usually. Abbreviation Element 3) If one of the following conditions is satisfied, not judge protective time.
For AC fan motor units: level per 1 minute. • Hold: Keep the current frequency. • Resume: No limitation for frequency. Heating Mode(Heat Pump Units) 3.4.1 Compressor Control 1) Reach the configured temperature • If the following conditions are satisfied, the compressor ceases operation.
2) Auto fan heating mode: • T3 rises above TCDE1°C. For DC fan motor units: • T3 maintained above TCDE2°C for 80 seconds. • Rise curve • Unit runs for 15 minutes consecutively in defrosting • When T1-Tsc is higher than -1.5°C, fan speed mode.
• setting temperature • Forced defrosting mode: • Press AUTO/COOL button continuously for 5s under forced cooling mode to enter this mode. • Indoor fan will stop, defrosting lamp will light on. • Quit this mode and turn off the unit when: •...
3.14 Silence (Optional) which, the unit exits this mode. • The timer setting is available in this mode. Press “Silence” on the remote control to enable the SILENCE function. While this function is active, the indoor 3.10 Auto-Restart function unit will run at faint breeze(1% fan speed), which reduces noise to the lowest possible level.
3.18 Wireless Control (Optional) • Wireless control allows you to control your air conditioner using your mobile phone and a Wireless connection. • For the USB device access, replacement, maintenance operations must be carried out by professional staff. Product Features ...
Page 30
Maintenance Contents First Time Installation Check .................2 Refrigerant Recharge ....................4 Re-Installation .......................5 Indoor Unit ....................5 Outdoor Unit ....................7...
1. First Time Installation Check Air and moisture trapped in the refrigerant system affects To prevent air and moisture from affecting the air the performance of the air conditioner by: conditioner’s performance, the indoor unit, as well as the pipes between the indoor and outdoor unit, must be be •...
Page 32
Procedure: • If the pressure successfully reaches -0.1 MPa Tighten the flare nuts of the indoor and outdoor (14.5 Psi), fully close the Handle Lo valve, then units, and confirm that both the 2- and 3-way valves cease vacuum pump operations. are closed.
2. Refrigerant Recharge mA A Procedure: Close both 2- and 3-way valves. 3-way valves. Slightly connect the Handle Lo charge hose to the Operate the air conditioner in cooling mode to charge 3-way service port. the system with liquid refrigerant. Connect the charge hose to the valve at the bottom When the electronic scale displays the correct of the cylinder.
3. Re-Installation Indoor Unit Collecting the refrigerant into the outdoor unit Procedure: Confirm that the 2- and 3-way valves are opened. Close the 3-way valve so that the gauge rests between 0.3 MPa (43.5 Psi) and 0.5 MPa (72.5 Psi). Connect the charge hose with the push pin of Handle Lo to the 3-way valve’s gas service port.
Page 35
Air purging with vacuum pump Procedure: • If the pressure successfully reaches -0.1 MPa Tighten the flare nuts of the indoor and outdoor (14.5 Psi), fully close the Handle Lo valve, then units, and confirm that both the 2- and 3-way valves cease vacuum pump operations.
Outdoor Unit Evacuation for the whole system Procedure: Wait for 5 minutes then check whether the gauge Confirm that the 2- and 3-way valves are opened. needle moves after turning off the vacuum pump. If Connect the vacuum pump to the 3-way valve’s the gauge needle moves backward, check whether service port.
Page 37
Refrigerant charging mA A Procedure: Close both 2- and 3-way valves. Fully open the Handle Lo manifold valve, 2- and 3-way valves. Slightly connect the Handle Lo charge hose to the 3-way service port. Operate the air conditioner in cooling mode to charge the system with liquid refrigerant.
Page 38
Indoor Unit Disassembly Contents Dimension ......................2 Indoor Unit Disassembly ..................3 Front Panel ....................3 Electrical parts ....................9 Evaporator ....................11 Fan motor and fan ..................13 Step motor ....................15 Drain Hose ....................16...
2. Indoor Unit Disassembly 2.1 Front Panel Procedure Illustration 1) Hold the front panel by the tabs on Front Panel the both sides and lift it (see CJ_AG_ INV_001). CJ_AG_INV_001 2) Push up the bottom of an air filter (step 1), and then pull it out downwards (step 2) (see CJ_AG_ INV_002).
Page 41
Procedure Illustration 3) Open the horizontal louver and push the hook towards left to open it (see CJ_AG_INV_003). Horizontal Louver Hook CJ_AG_INV_003 4) Bend the horizontal louver lightly by both hands to loosen the hooks, then remove the horizontal louver (see CJ_AG_INV_003).
Page 42
Procedure Illustration 5) Pry the electrical cover by a screw driver, and rotate it towars left, then remove it. (see CJ_AG_INV_005). CJ_AG_INV_005 6) Disconnect the connector for display board. (see CJ_AG_INV_006) . 7) Slid the front panel side to side to release each axis (see CJ_AG_INV_006) CJ_AG_INV_006 Note: This section is for reference only.
Page 43
Procedure Illustration 8) Open the screw cap and then remove the 3 screws (see CJ_AG_INV_008). CJ_AG_INV_007 9) Release the hooks with hands. (see CJ_AG_INV_008) CJ_AG_INV_008 Note: This section is for reference only. Actual unit appearance may vary. Indoor Unit Disassembly 6 ...
Page 44
Procedure Illustration 10) Release the 5 hooks in the back (see CJ_AG_INV_009). CJ_AG_INV_009 11) Pull out the panel frame while pushing the hook through a clearance between the panel frame and the heat exchanger. (see CJ_AG_INV_010) CJ_AG_INV_010 Note: This section is for reference only. Actual unit appearance may vary. ...
Page 45
Procedure Illustration 12) Release the 5 hooks of the vertical blades, then pull the vertical blades rightward and remove it (see CJ_AG_ INV_011). CJ_AG_INV_011 13) Remove 1 screw of the display board. (see CJ_AG_INV_012). 14) Rotate the display board in the direction shown in the right picture.
2.2 Electrical parts (Antistatic gloves must be worn.) Note: Remove the front panel (refer to 1. Front panel) before disassembling electrical parts. Procedure Illustration 1) Remove one fixing screw of electrical control box subassembly. (see CJ_AG_ INV_013). (If you want to repair the electrical control box components, perform the first step;If you want to repair the main control board assembly, perform steps 2 to 5 below.)
Page 47
Procedure Illustration 4) Pull out the electrical main board along the direction indicated in right image. (see CJ_AG_INV_015). CJ_AG_INV_015 Fan motor swing motor ION(some models) 5) Disconnect the connectors and remove main control board. (see CJ_AG_ INV_016). CJ_AG_INV_016 Note: This section is for reference only. Actual unit appearance may vary. ...
2.3 Evaporator Note: Remove the front panel and electrical parts (refer to 1. Front panel and 2. Electrical parts) before disassembling evaporator. Procedure Illustration 1) Disassemble the pipe holder located at the rear of the unit (see CJ_AG_INV_017). CJ_AG_INV_017 2) Remove the 1 screws on the evaporator located at the fixed plate (see CJ_AG_ INV_018).
Page 49
Procedure Illustration 3) Remove 1 screw and release the hook on the evaporator (see CJ_AG_INV_019). CJ_AG_INV_019 4) Remote the 2 screws on the evaporator located at the fixed plate (see CJ_AG_ INV_020). CJ_AG_INV_020 5) Pull out the evaporator (see CJ_AG_ INV_021).
2.4 Fan motor and fan Note: Remove the front panel, electrical parts and evaporator (refer to 1. Front panel, 2. Electrical parts, and 3. Evaporator). before disassembling fan motor and fan. Procedure Illustration 1) Remove the two screws and remove the fixing board of the fan motor (see CJ_AG_ INV_022).
Page 51
Procedure Illustration 3) Remove the fixing screw (see CJ_AG_ INV_024). 4) Pull out the fan motor and fan assembly from the side. CJ_AG_INV_024 Fixing Screw Note: This section is for reference only. Actual unit appearance may vary. Indoor Unit Disassembly 14 ...
2.5 Step motor Note: Remove the front panel and electrical parts (refer to 1. Front panel, 2. Electrical parts) before disassembling step motor. Procedure Illustration 1) Remove the two screws, then remove the horizontal swing motor(see CJ_AG_ INV_025). Stepping Motor CJ_AG_INV_025 2) Remove 1 screw, then remove the vertical swing motor (see CJ_AG_INV_026).(for...
2.6 Drain Hose Procedure Illustration 1) Rotate the fixed wire clockwise indicated in right image (see CJ_AG_INV_027). CJ_AG_INV_027 2) Pull up the drain hose to remove it (see CJ_AG_INV_028). CJ_AG_INV_028 Note: This section is for reference only. Actual unit appearance may vary. ...
Page 54
Outdoor Unit Disassembly Contents Outdoor Unit Table ....................2 Dimension ......................3 Outdoor Unit Disassembly ....................21 Panel Plate ....................21 Electrical Parts .....................46 Fan Assembly ....................65 Fan Motor ....................66 Sound blanket .....................67 Four-way valve .....................68 Compressor ....................69...
Page 55
1. Outdoor Unit Disassembly Outdoor Unit Table Outdoor Unit Model Panel Plate PCB Board MOX230-09HFN8-QRD6GW X230 PCB Board 9 MOX230-12HFN8-QRD6GW X230 PCB Board 9 Outdoor Unit Disassembly 2 ...
Page 73
For US models: Outdoor Unit Disassembly 20 ...
Page 74
3. Outdoor Unit Disassembly Panel Plate 1. AA30 / AB30 Procedure Illustration 1) Turn off the air conditioner and the power breaker. Big Handle 2) Remove the screws of the big handle and then remove the big handle (1 screws) (see CJ_AA30_001). CJ_AA30_001 Top Cover 3) Remove the screws of the top cover...
Page 75
Procedure Illustration 4) Remove the screws of the front panel and then remove the front panel (6 screws) (see CJ_AA30_003). Front Panel CJ_AA30_003 5) Remove the screws of water collecting cover (2 screws) (see CJ_AA30_004). Water Collecting Cover CJ_AA30_004 Note: This section is for reference only. Actual unit appearance may vary. ...
Page 76
Procedure Illustration 6) Remove the screws of the rear net and then remove the rear net (2 screws) CJ_AA30_005). (for some (see models) CJ_AA30_005 7) Remove the screws of the right panel and then remove the right panel (6 screws) (see CJ_AA30_006). Right Panel CJ_AA30_006 Note: This section is for reference only.
Page 77
2. BA30 Procedure Illustration 1) Turn off the air conditioner and the Big Handle power breaker. 2) Remove the screws of the big handle and then remove the big handle (1 screws) (see CJ_BA30_001). CJ_BA30_001 Top Cover 3) Remove the screws of the top cover and then remove the top cover (3 screws).
Page 78
Procedure Illustration 4) Remove the screws of the front panel and then remove the front panel (7 screws) (see CJ_BA30_003). Front Panel CJ_BA30_003 5) Remove the screws of water collecting Water Collecting Cover cover (2 screws) (see CJ_BA30_004). CJ_BA30_004 Note: This section is for reference only. Actual unit appearance may vary. ...
Page 79
Procedure Illustration 6) Remove the screws of the rear net and then remove the rear net (2 (for some screws) (see CJ_BA30_005). models) CJ_BA30_005 7) Remove the screws of the right panel and then remove the right panel (6 screws) (see CJ_BA30_006). Right Panel CJ_BA30_006 Note: This section is for reference only.
Page 80
3. B30 Procedure Illustration 1) Turn off the air conditioner and the power breaker. Big Handle 2) Remove the screws of the big handle and then remove the big handle (1 screws) (see CJ_B30_001). CJ_B30_001 Top Cover 3) Remove the screws of the top cover and then remove the top cover (3 screws).
Page 81
Procedure Illustration 4) Remove the screws of the front panel and then remove the front panel (8 screws) (see CJ_B30_003). Front Panel CJ_B30_003 5) Remove the screws of water collecting cover and then remove the water collecting cover (2 screws) (see CJ_ Water Collecting Cover B30_004).
Page 82
Procedure Illustration 6) Remove the screws of the rear net and then remove the rear net (2 screws) CJ_B30_005). (for some models) (see CJ_B30_005 7) Remove the screws of the right panel and then remove the right panel (5 screws) (see CJ_B30_006). Right Panel CJ_B30_006 Note: This section is for reference only.
Page 83
4. CA30 Procedure Illustration 1) Turn off the air conditioner and the power breaker. 2) Remove the screws of the big handle and then remove the big handle Big Handle (1 screws) (see CJ_CA30_001). CJ_CA30_001 Top Cover 3) Remove the screws of the top cover and then remove the top cover (3 screws).
Page 84
Procedure Illustration 4) Remove the screws of the front panel and then remove the front panel (7 screws) (see CJ_CA30_003). Front Panel CJ_CA30_003 5) Remove the screws of water collecting cover and then remove the water Water Collecting Cover collecting cover (2 screws) (see CJ_ CA30_004).
Page 85
Procedure Illustration 6) Remove the screws of the rear net and then remove the rear net (2 screws) CJ_CA30_005). (for some (see models) CJ_CA30_005 7) Remove the screws of the right panel and then remove the right panel (7 screws) (see CJ_CA30_006). Right Panel CJ_CA30_006 Note: This section is for reference only.
Page 86
5. D30 Procedure Illustration 1) Turn off the air conditioner and the Big Handle power breaker. 2) Remove the screws of the big handle and then remove the big handle (2 screws) (see CJ_D30_001). CJ_D30_001 3) Remove the screws of the top cover and then remove the top cover (4 Top Cover screws).
Page 87
Procedure Illustration 4) Remove the screws of the front right panel and then remove the front right panel (2 screws) (see CJ_D30_003). Front Right Panel CJ_D30_003 5) Remove the screws of the front panel and then remove the front panel (9 screws) (see CJ_D30_004).
Page 88
Procedure Illustration 6) Remove the screws of water collecting cover and then remove the water collecting cover (2 screw) (see CJ_ D30_005). Water Collecting Cover CJ_D30_005 7) Remove the screws of the rear net and then remove the rear net (2 screws) CJ_D30_006).
Page 89
Procedure Illustration 8) Remove the screws of the right panel and then remove the right panel (8 screws) (see CJ_D30_007). Right Panel CJ_D30_007 Note: This section is for reference only. Actual unit appearance may vary. Outdoor Unit Disassembly 36 ...
Page 90
6. X130 Procedure Illustration 1) Turn off the air conditioner and the power breaker. 2) Remove the screw of the big handle and then remove the big handle (1 screw) (see CJ_X130_001). Big Handle CJ_X130_001 Top Cover 3) Remove the screws of the top cover and then remove the top cover (3 screws).
Page 91
Procedure Illustration 4) Remove the screws of water collecting cover and then remove the water collecting cover (2 screws) (see CJ_ X130_003). Water Collecting Cover CJ_X130_003 5) Remove the screws of the front panel and then remove the front panel (6 screws(onoff models) or 8 screws(inverter models) (see CJ_ X130_004).
Page 92
Procedure Illustration 6) Remove the screws of the right panel and then remove the right panel (5 screws) (see CJ_X130_005). Right Panel CJ_X130_005 Note: This section is for reference only. Actual unit appearance may vary. Outdoor Unit Disassembly 39 ...
Page 93
7. X230/X330 Procedure Illustration 1) Turn off the air conditioner and the power breaker. 2) Remove the screw of the big handle and then remove the big handle (1 screws) (see CJ_X230_001). Big Handle CJ_X230_001 Top Cover 3) Remove the screws of the top cover and then remove the top cover (4 screws).
Page 94
Procedure Illustration 4) Remove the screws of water collecting cover and then remove the water collecting cover (2 screws) (see CJ_ X230_003). Water Collecting Cover CJ_X230_003 5) Remove the screws of the front panel and then remove the front panel (7 screws(onoff models) or 9 screws(inverter models) (see CJ_ X230_004).
Page 95
Procedure Illustration 6) Remove the screws of the right panel and then remove the right panel (5 screws) (see CJ_X230_005). Right Panel CJ_X230_005 Note: This section is for reference only. Actual unit appearance may vary. Outdoor Unit Disassembly 42 ...
Page 96
8. X430 Procedure Illustration 1) Turn off the air conditioner and the power breaker. 2) Remove the screw of the big handle and then remove the big handle (1 screw) (see CJ_X430_001). Big Handle CJ_X430_001 Top Cover 3) Remove the screws of the top cover and then remove the top cover (3 screws).
Page 97
Procedure Illustration 4) Remove the screws of water collecting cover and then remove the water collecting cover (2 screws) (see CJ_ X430_003). Water Collecting Cover CJ_X430_003 5) Remove the screws of the front panel and then remove the front panel (7 screws(onoff models) or 9 screws(inverter models) (see CJ_ X430_004).
Page 98
Procedure Illustration 6) Remove the screws of the right panel and then remove the right panel (6 screws) (see CJ_X430_005). Right Panel CJ_X430_005 Note: This section is for reference only. Actual unit appearance may vary. Outdoor Unit Disassembly 45 ...
Page 99
Electrical parts Antistatic gloves must be worn when you disassemble the electronic box. WARNING: Note: Remove the air outlet grille(refer to 3.1 Panel Plate) before disassembling electrical parts. PCB for ON-OFF Models 1. PCB board 1 Procedure Illustration 1) Remove the two screws fixed the electronic control board (see CJ_ ODU_PCB_001).
Page 100
Procedure Illustration 8) For models with subzero refrigeration control board, remove 3 screws of it showed in the figure. CJ_ODU_PCB_001-03 9) The subzero refrigeration control board is in the back of the medal sheet. CJ_ODU_PCB_001-04 Note: This section is for reference only. Actual unit appearance may vary. Outdoor Unit Disassembly 47 ...
Page 101
2. PCB board 2 Procedure Illustration Fan Motor 1) Disconnect the wires connected to the compressor. (Red wire connects 4-Way Valve Compressor with PCB board, others connects with terminals) (see CJ_ODU_PCB_002-1) 2) Disconnect the connectors for fan motor. (Blue wire, red wire, brown wire and black wire.
Page 102
3. PCB board 3 Procedure Illustration Earth wire 1) Disconnect the connectors for fan Fan motor motor (see CJ_ODU_PCB_003). 2) Disconnect the wires connected to the compressor (see CJ_ODU_ PCB_003). 3) Disconnect the wires connected to Pipe temperature sensor (see CJ_ ODU_PCB_003).
Page 103
PCB for Inverter Models 4. PCB board 4 Procedure Illustration 1) Remove the screws of the top cover. CJ_ODU_PCB_004- (2 screws) (see 1 ). CJ_ODU_PCB_004-1 2) Unfix the hooks and then open the electronic control box cover (4 hooks) CJ_ODU_PCB_004-2 ). (see 3) Disconnect the connector for fan motor from the electronic control...
Page 104
5. PCB board 5 Procedure Illustration 1) Unfix the hooks and then open the electronic control box cover (4 hooks) CJ_ODU_PCB_005-1 ). (see 4-Way Valve 2) Disconnect the connector for fan CJ_ODU_PCB_005-1 motor from the electronic control CJ_ODU_PCB_005-2 ). board (see 3) Remove the connector for the Reactor CJ_ODU_PCB_005-...
Page 105
5. PCB board 6 Procedure Illustration 1) Remove the screws and unfix the hooks, then open the electronic control box cover (5 screws and 2 CJ_ODU_PCB_006-1 ). hooks )(see CJ_ODU_PCB_006-1 2) Disconnect the connector for fan motor from the electronic control CJ_ODU_PCB_006-2 ).
Page 106
6. PCB board 7 Procedure Illustration 1) Remove the screws of the top cover. (1 screws) (see CJ_ODU_PCB_007- 1 ). CJ_ODU_PCB_007-1 2) Unfix the hooks and then open the electronic control box cover (5 hooks) CJ_ODU_PCB_007-2 ). (see CJ_ODU_PCB_007-2 3) Disconnect the connector for fan motor from the IPM board (see ODU_PCB_007-3 ).
Page 107
Procedure Illustration 5) Pull out the wire connected with the CJ_ODU_PCB_007-4 ). terminal. (see T3/T4 6) Pull out connectors of the condenser coil temp. sensor(T3),outdoor ambient temp. sensor(T4) and discharge temp. CJ_ODU_PCB_007-4 ). sensor(TP) (see 7) Disconnect the electronic expansion CJ_ODU_PCB_007- valve wire (see Fig 4 ).
Page 108
7. PCB board 8 Procedure Illustration 1) Unfix the hooks and then open the electronic control box cover (4 hooks) CJ_ODU_PCB_008-1 ). (see 2) Disconnect the connector for outdoor DC fan from the electronic CJ_ODU_ control board (see PCB_008-2 ). 3) Remove the connector for the CJ_ODU_PCB_008- compressor (see...
Page 109
9. PCB board 9 Procedure Illustration 1) Disconnect the connector for compressor and release the ground CJ_ODU_ wire(1 screw). (see PCB_009-1 ). 2) Pull out the wires from electrical supporting plate and turn over the CJ_ODU_PCB_009-1 electronic control assembly. (see CJ_ODU_PCB_009-2 ).
Page 110
Procedure Illustration 4) Remove the fixing board (2 hooks) CJ_ODU_PCB_009-4 ). (see CJ_ODU_PCB_009-4 5) Disconnect the connectors from the electronic control board (see CJ_ODU_PCB_009-5 ). CJ_ODU_PCB_009-5 6) Then remove the electronic control board (4 hooks).(see CJ_ODU_ PCB_009-6 ). CJ_ODU_PCB_009-6 Note: This section is for reference only. Actual unit appearance may vary. Outdoor Unit Disassembly 57 ...
Page 111
10. PCB board 10 Procedure Illustration 1) Unfix the hooks and then open the electronic control box cover (4 hooks) CJ_ODU_PCB_010-1 ). (see CJ_ODU_PCB_010-1 2) Remove 4 screws on the electronic control board and then turn over the electronic control board (see CJ_ODU_PCB_010-2 ).
Page 112
Procedure Illustration 3) Pull out the connectors (see ODU_PCB_010-3 ). 4) Remove the 9 screws and unfix the 3 hooks and then remove the electronic control board(see ODU_PCB_010-3 ). CJ_ODU_PCB_010-3 5) Remove two screws and then remove the electronic control box subassembly on partition board assembly.
Page 113
Procedure Illustration 6) Remove two screws and two connectors and then remove the CJ_ODU_ inverter control board (see PCB_010-5 ). CJ_ODU_PCB_010-5 Note: This section is for reference only. Actual unit appearance may vary. Outdoor Unit Disassembly 60 ...
Page 114
11. PCB board 11 Procedure Illustration 1) Disconnect the connector for compressor and release the ground CJ_ODU_ wire(1 screw). (see PCB_0011-1 ). 2) Pull out the wires from electrical supporting plate and turn over the CJ_ODU_PCB_011-1 electronic control assembly. (see CJ_ODU_PCB_011-2 ).
Page 115
Procedure Illustration 4) Remove the fixing board (2 hooks) CJ_ODU_PCB_011-4 ). (see CJ_ODU_PCB_011-4 5) Disconnect the connectors from the electronic control board (see CJ_ODU_PCB_011-5 ). CJ_ODU_PCB_011-5 6) Then remove the electronic control board (4 hooks).(see CJ_ODU_ PCB_011-6 ). CJ_ODU_PCB_011-6 Note: This section is for reference only. Actual unit appearance may vary. ...
Page 116
12. PCB board 12 Procedure Illustration 1) Unfix the hooks and then open the electronic control box cover (4 hooks) CJ_ODU_PCB_012-1 ). (see CJ_ODU_PCB_012-1 2) Remove 6 screws on the electronic control board and then turn over the electronic control board (see CJ_ODU_PCB_012-2 ).
Page 117
Note: This section is for reference only. Actual unit appearance may vary. Procedure Illustration 3) Pull out the connectors (see ODU_PCB_012-3 ). 4) Remove the 4 screws and then remove the electronic control CJ_ODU_PCB_012-3 ). board(see CJ_ODU_PCB_012-3 Note: This section is for reference only. Actual unit appearance may vary. ...
Page 118
Fan Assembly Note: Remove the panel plate (refer to 3.1 Panel Plate) before disassembling fan. Procedure Illustration 1) Remove the nut securing the fan with a spanner (see CJ_ODU_ FAN_001). 2) Remove the fan. D-cut CJ_ODU_FAN_001 Note: This section is for reference only. Actual unit appearance may vary. Outdoor Unit Disassembly 65 ...
Page 119
Fan Motor Note: Remove the panel plate and the connection of fan motor on PCB (refer to 3.1 Panel Plate and 3.2 Electrical parts) before disassembling fan motor. Procedure Illustration 3) Remove the fixing screws of the fan motor (4 screws) (see CJ_ODU_MOTOR_001). 4) Remove the fan motor.
Page 120
Sound blanket Note: Remove the panel plate (refer to 3.1 Panel plate) before disassembling sound blanket. Procedure Illustration 1) Remove the sound blanket (side and top) (see CJ_ODU_BLANKET_001). Sound Blanket(top) Sound Blanket(side) CJ_ODU_BLANKET_001 Note: This section is for reference only. Actual unit appearance may vary. ...
Page 121
Four-way valve (for heat pump models) WARNING: Evacuate the system and confirm that there is no refrigerant left in the system before removing the four-way valve and the compressor. (For R32 & R290, you should evacuate the system with the vacuum pump; flush the system with nitrogen;...
Page 122
Compressor WARNING: Evacuate the system and confirm that there is no refrigerant left in the system before removing the four-way valve and the compressor. (For R32 & R290, you should evacuate the system with the vacuum pump; flush the system with nitrogen; then repeat the two steps before heating up the brazed parts. The operations above should be implemented by professionals.) Note: Remove the panel plate, connection of compressor on PCB (refer to 3.1 Panel plate and 3.2 Electrical parts) before disassembling sound blanket.
Page 123
Procedure Illustration 3) Remove the hex nuts and washers securing the compressor, located on the bottom plate (see CJ_ODU_COMP_003). CJ_ODU_COMP_003 Suction Pipe 4) Heat up the brazed parts and then remove the the discharge pipe and the suction pipe (see CJ_ODU_COMP_004). Discharge Pipe 5) Lift the compressor from the base pan assembly with pliers.
Page 124
Troubleshooting Contents Safety Caution .......................3 General Troubleshooting ..................4 Complain Record Form ..................6 Information Inquiry ....................8 Error Diagnosis and Troubleshooting Without Error Code .......11 Remote maintenance ...................11 Field maintenance ..................12 Quick Maintenance by Error Code ..............17 Troubleshooting by Error Code ................17 TS01 EEPROM Parameter Error Diagnosis and Solution TS02 Indoor and Outdoor Unit Communication Error Diagnosis and Solution TS03 Zero-crossing Signal Detection Error Diagnosis and Solution...
Page 125
Contents TS09 IPM Malfunction or IGBT Over-strong Current Protection Diagnosis and Solution TS10 Over Voltage or Too Low Voltage Protection Diagnosis and Solution TS11 Top temperature Protection of Compressor or High Temperature Protection of IPM Module or High Pressure Protection Diagnosis and Solution TS12 Inverter Compressor Drive Error Diagnosis and Solution TS13 Low Pressure Protection Diagnosis and Solution TS14 Indoor units mode conflic Diagnosis and Solution...
1. Safety Caution WARNING Be sure to turn off all power supplies or disconnect all wires to avoid electric shock. While checking indoor/outdoor PCB, please equip oneself with antistatic gloves or wrist strap to avoid damage to the board. WARNING Electricity remains in capacitors even when the power supply is off.
Page 127
When the indoor unit encounters a recognized error on different models , 1. the running LED with flash in a corresponding series, the timer LED may turn on or begin flashing; 2. an error code will be displayed; 3. both 1 and 2. These error codes are described in the following tables: Running Timer...
Page 128
Top temperature protection of compressor or High temperature 3 times FLASH TS11-S-INV PC 02 protection of IPM module or High pressure protection 5 times FLASH PC 04 Inverter compressor drive error TS12-S 1 time FLASH Current overload protection TS08-S PC 08 Communication error between outdoor main chip and compressor 6 times FLASH...
3. Complain Record Form Complain Record Form Request No.: Date: Installation Date: Service Date: Customer Information Name Telephone No. Home Address Email Product Information Indoor Unit Model Outdoor Unit Model Serial No. of indoor unit Serial No. of outdoor unit Working Mode □Cooling □Heating...
Page 130
Parameter Checking information by Remote controller Displaying code Displaying code meaning Display value Display value meaning Room temperature Indoor coil temperature Outdoor coil temperature Ambient temperature Discharge temperature Targeted Frequency Actual Frequency Compressor current Outdoor AC voltage Indoor capacity test Reserve Outdoor fan speed EXV opening steps...
4. Information Inquiry • To enter information inquiry status, complete the following procedure within 10 seconds: • Press LED 3 times. • Press SWING 3 times. • Finish 1 and 2 within 10 seconds, you will hear beeps for two seconds, which means the unit goes into parameter checking mode.
Page 132
Error code Display Error Information EH 00/EH 0A Indoor unit EEPROM parameter error Indoor / outdoor unit communication error EL 01 Zero-crossing signal detection error EH 02 Over low voltage protection of indoor external fan EH 30 Over voltage protection of indoor external fan EH 31 The indoor fan speed is operating outside of the normal range EH 03...
Page 133
PC 06 Compressor discharge temperature protection Outdoor current protection PC 08 Anti-cold air in heating mode PH 09 PFC module malfunction PC 0F Outdoor ambient tempreture too low pc 0l Evaporator coil temperature over high protection PH 90 Evaporator coil temperature over low Protection PH 91 Frequency limit caused by voltage LC 05...
5. Error Diagnosis and Troubleshooting Without Error Code WARNING Be sure to turn off unit before any maintenance to prevent damage or injury. Remote maintenance SUGGESTION: When troubles occur, please check the following points with customers before field maintenance. Problem Solution Unit will not start 13-14...
Field maintenance Problem Solution Unit will not start 15-16 Compressor will not start but fans run 15-16 Compressor and condenser (outdoor) fan will not start 15-16 Evaporator (indoor) fan will not start 15-16 Condenser (Outdoor) fan will not start 15-16 Unit runs, but shortly stops 15-16 Compressor short-cycles due to overload...
Page 136
1.Remote Maintenance Electrical Circuit Refrigerant Circuit Possible causes of trouble Unit will not start ☆ ☆ ☆ ☆ The power switch is on but fans will not start ☆ ☆ ☆ The temperature on the display board cannot be set ☆...
Page 137
1.Remote Maintenance Others Possible causes of trouble Unit will not start The power switch is on but fans will not start ☆ The temperature on the display board cannot be set Unit is on but the wind is not cold(hot) Unit runs, but shortly stops The unit starts up and stops frequently ☆...
Page 138
2.Field Maintenance Refrigerant Circuit Others Possible causes of trouble Unit will not start Compressor will not start but fans run ☆ Compressor and condenser (outdoor) fan will not start Evaporator (indoor) fan will not start Condenser (Outdoor) fan will not start Unit runs, but shortly stops ☆...
Page 139
2.Field Maintenance Electrical Circuit Possible causes of trouble Unit will not start ☆ ☆ ☆ ☆ ☆ ☆ Compressor will not start but fans run ☆ ☆ ☆ ☆ ☆ Compressor and condenser (outdoor) fan will not start ☆ ☆ ☆...
6. Quick Maintenance by Error Code If you do not have the time to test which specific parts are faulty, you can directly change the required parts according the error code. You can find the parts to replace by error code in the following table. Error Code Part requiring EH 00/...
TS01-IDU: Indoor EEPROM parameter error diagnosis and solution Description: Indoor PCB main chip does not receive feedback from EEPROM chip. Recommended parts to prepare: • Indoor PCB Troubleshooting and repair: Shut off the power supply and turn it on 2 minutes later. Is it still displaying The unit is operating normally.
Page 142
TS01-ODU: Outdoor EEPROM parameter error or Compressor driven chip EEPROM parameter error diagnosis and solution Description: Outdoor PCB main chip does not receive feedback from EEPROM chip or compressor driven chip. Recommended parts to prepare: • Outdoor PCB Troubleshooting and repair: Shut off the power supply and turn it on 2 minutes later.
Page 143
TS02-S-INV: Indoor and outdoor unit communication error diagnosis and solution Description: Indoor unit can not communicate with outdoor unit Recommended parts to prepare: • Indoor PCB • Outdoor PCB • Short-circuited component Troubleshooting and repair: Power off, then restart the unit after 2 minutes.
Page 144
Remarks: • Use a multimeter to test the DC voltage between 2 port(or S or L2 port) and 3 port(or N or S port) of outdoor unit. The red pin of multimeter connects with 2 port(or S or L2 port) while the black pin is for 3 port(or N or S port) . •...
Page 145
TS03: Zero crossing detection error diagnosis and solution Description: When PCB does not receive zero crossing signal feedback for 4 minutes or the zero crossing signal time interval is abnormal. Recommended parts to prepare: • Connection wires • Indoor main PCB Troubleshooting and repair: Check the connections and power supply.
Page 146
TS04-S-IDU: The Indoor fan speed is operating outside of normal range diagnosis and solution) Description: When indoor fan speed keeps too low or too high for a certain time, the LED displays the failure code and the AC turns off. Recommended parts to prepare: •...
Page 147
Index: 1. DC Fan Motor(control chip is in fan motor) Power on and when the unit is in standby, measure the voltage of pin1-pin3, pin4-pin3 in fan motor connector. If the value of the voltage is not in the range showing in below table, the PCB must has problems and need to be replaced. •...
Page 149
TS04-ODU: The outdoor fan speed is operating outside of normal range diagnosis and solution) Description: When outdoor fan speed keeps too low or too high for a certain time, the LED displays the failure code and the AC turns off. Recommended parts to prepare: •...
Page 150
Index: 1. Outdoor DC Fan Motor (control chip is in outdoor PCB) Release the UVW connector. Measure the resistance of U-V, U-W, V-W. If the resistance is not equal to each other, the fan motor must has problems and need to be replaced. otherwise the PCB must has problems and need to be replaced. 2.
Page 151
TS05-IDU: Open circuit or short circuit of indoor temperature sensor(T1, T2) diagnosis and solution Description: If the sampling voltage is lower than 0.06V or higher than 4.94V, the LED displays the failure code. Recommended parts to prepare: • Connection wires •...
Page 152
TS05-ODU: Open circuit or short circuit of outdoor temperature sensor(T3, T4, TP, T2B,TH) diagnosis and solution Description: If the sampling voltage is lower than 0.06V or higher than 4.94V, the LED displays the failure code. Recommended parts to prepare: • Connection wires •...
Page 153
TS06-INV: Refrigerant Leakage Detection diagnosis and solution Description: Define the evaporator coil temperature T2 of the compressor just starts running as Tcool. In the beginning 5 minutes after the compressor starts up, if T2 < Tcool-1°C(1.8°F) does not keep continuous 4 seconds and compressor running frequency higher than 50Hz does not keep for 3 minutes, and this situation happens 3 times, the LED displays the failure code and the AC turns off.
Page 154
TS07: Indoor PCB / Display board communication error diagnosis and solution Description: Indoor PCB does not receive feedback from the display board. Recommended parts to prepare: • Communication wire • Indoor PCB • Display board Troubleshooting and repair: Power off, then restart the unit 2 minutes later Is it still displaying the error code? The unit functions normally...
Page 155
TS08-S: Current overload protection diagnosis and solution Description: An abnormal current rise is detected by checking the specified current detection circuit. Recommended parts to prepare: • Connection wires • Reactor • Outdoor fan • Outdoor PCB Troubleshooting and repair: Was the protection activated Was the protection activated in standby? in standby?
Page 156
TS09-S: IPM malfunction or IGBT over-strong current protection diagnosis and solution Description: When the voltage signal the IPM sends to the compressor drive chip is abnormal, the LED displays the failure code and the AC turns off. Recommended parts to prepare: •...
Page 157
Index: 1. IPM Continuity Check WARNING Electricity remains in capacitors even when the power supply is off. Ensure the capacitors are fully discharged before troubleshooting. 1. Turn off outdoor unit and disconnect power supply. 2. Discharge electrolytic capacitors and ensure all energy-storage unit has been discharged. 3.
Page 158
4. Compressor check Disconnect the compressor and check the resistance between U-V, V-W and U-W, and all 3 values should be equal. If not, the compressor is faulty and should be replaced. Note: The picture and the value are only for reference, actual condition and specific value may vary. ...
Page 159
TS10-S: Over voltage or too low voltage protection diagnosis and solution Description: Abnormal increases or decreases in voltage are detected by checking the specified voltage detection circuit. Recommended parts to prepare: • Power supply wires • IPM module board • PCB •...
Page 160
TS11-S-INV: Top temperature protection of compressor or High temperature protection of IPM module or High pressure protection diagnosis and solution Description: For some models with overload protection, If the sampling voltage is not 5V, the LED will display the failure. If the temperature of IPM module is higher than a certain value, the LED displays the failure code.
Page 161
Check the fastening screws on the PCB and IPM radiator. Replace the outdoor Are they fixed tightly? control PCB. Tighten the screws and apply silicon grease. Note: For certain models, outdoor PCB could not be removed separately. In this case, the outdoor electric control box should be replaced as a whole.
Page 162
High pressure protection High pressure protection Are the high pressure switch Are the high pressure switch Connect high pressure switch and Connect high pressure switch and and main control boar wired and main control boar wired mian control board mian control board correctly? correctly? Is the high pressure...
Page 163
TS12-S: Inverter compressor drive error diagnosis and solution Description: An abnormal inverter compressor drive is detected by a special detection circuit, including communication signal detection, voltage detection, compressor rotation speed signal detection and so on. Recommended parts to prepare: • Connection wires •...
Page 164
TS13-INV: Low pressure protection diagnosis and solution Description: Outdoor pressure switch cut off the system because low pressure is lower than 0.13 MPa, the LED displays the failure code. Recommended parts to prepare: • Connection wires • Outdoor PCB • Low pressure protector •...
Page 165
Low pressure protection Low pressure protection Are the low pressure protector Are the low pressure protector and main control board wired and main control board wired Reconnect the low pressure protector and main Reconnect the low pressure protector and main properly? properly? control board...
Page 166
TS14: Indoor units mode conflict (match with multi outdoor unit) Description: The indoor units cannot work cooling mode and heating at same time. Heating mode has a priority. • Suppose Indoor unit A working in cooling mode or fan mode, and indoor unit B is set to heating mode, then A will change to off and B will work in heating mode.
Page 167
TS33: Communication error between outdoor main chip and compressor driven chip diagnosis and solution Description: The main chip cannot detect the compressor driven chip Recommended parts to prepare: • Outdoor main PCB • Electric control box Troubleshooting and repair: Shut off the power supply and Shut off the power supply and turn it on 2 minutes later.
Page 168
8. Check Procedures 8.1 Temperature Sensor Check WARNING Be sure to turn off all power supplies or disconnect all wires to avoid electric shock. Operate after compressor and coil have returned to normal temperature in case of injury. 1. Disconnect the temperature sensor from PCB (Refer to Chapter 5&6. Indoor&Outdoor Unit Disassembly). 2.
Page 170
8.3 IPM Continuity Check WARNING Electricity remains in capacitors even when the power supply is off. Ensure the capacitors are fully discharged before troubleshooting. 1. Turn off outdoor unit and disconnect power supply. 2. Discharge electrolytic capacitors and ensure all energy-storage unit has been discharged. 3.
Page 171
Fan Motor Check 1. Turn off outdoor unit and disconnect power supply 2. Disconnect outdoor fan motor power cord from outdoor PCB 3. Measure the resistance value between each windings. The normal value of different motor show as follows: YKFG-13-4-38L Model YKFG-15-4-28-1 YKFG-20-4-10L...
Page 172
Appendix Contents Temperature Sensor Resistance Value Table for T1, T2, T3, and T4 (°C – K) ..2 Temperature Sensor Resistance Value Table for TP (for some units)(°C --K) ..3 iii) Pressure On Service Port ..................4...
Page 173
i) Temperature Sensor Resistance Value Table for T1,T2,T3 and T4 (°C – K) °C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm 115.266 12.6431 2.35774 0.62973 108.146 12.0561 2.27249 0.61148 101.517 11.5 2.19073 0.59386 96.3423 10.9731...
Page 174
ii) Temperature Sensor Resistance Value Table for TP(for some units) (°C --K) °C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm...