Air Handling Units Pos: 2 /Layout/Titel_Montage Inbetriebnahme Wartung @ 0\mod_1257953072735_2008.doc @ 2125 @ Installation Commissioning Maintenance Pos: 3 /Layout/Hinweis_Deckblatt @ 0\mod_1257492952667_2008.doc @ 2064 @ Translation of the original instructions Englische Version – English Version Keep for future use === Ende der Liste für Textmarke Inhalt2 ===...
Page 2
This manual accords with current technology at the time of writing. As the printed version is not regularly updated, please obtain the latest version before using it, by downloading from www.robatherm.com or on request from robatherm. The copyright to this work, including all illustrations, is reserved. No use which exceeds the limits of copyright law is allowable without our permission, and such use will be prosecuted.
Contents Introduction General Safety Instructions Emergency Provisions Maintenance and Cleaning Instructions Installation RMC / RZ / RM / RL Delivery Unloading and Transport Assembly and Installation Sealing of the Roof of Weatherproof Units ...
For components which are not described, the individual instructions are to be observed (request if required). robatherm will not be held liable for damage or faults which result from non-observance of these instructions.
Page 6
Pos: 7.11 /Einleitung/Übergabe @ 2\mod_1334559030399_2008.doc @ 22410 @ 4 Handover AHUs with integrated control technology may only be taken into operation after to robatherm’s initial commissioning and after handover and customer’s briefing has been concluded. Pos: 7.12 /Einleitung/Einfrierschutz @ 2\mod_1334559151487_2008.doc @ 22425 @ 4...
The floor loading in the AHU must not exceed 100 kg/m² of floor surface. Basically, the units’ roof is not designed to any additional load. In case of need, please contact robatherm directly. Pos: 10 /Layout/Leerzeile @ 0\mod_1256628654328_0.doc @ 2285 @ Pos: 11 /Layout/Seitenumbruch @ 0\mod_1256628615637_0.doc @ 2284 @...
Page 9
ATEX classification applied (category, atmosphere, temperature classification). It is preferable to use identical original components. If inappropriate changes are made to the unit by third parties, the robatherm declaration of conformity ceases to apply.
If a unit is misused, for example by substituting base of unit for building roof or by allocating static functions to the unit, all warranty obligations on the part of robatherm will lapse. Observe the notes in VDI 3803.
Provide a control linkage so that when a damper closes, the fans affected are switched off immediately. robatherm accepts no liability for damage due to incorrect operation. Provide pressure relief dampers to prevent damage from pressure spikes due to fire dampers in the system.
The current consumption is to be checked at all phases by measuring all phases. For rated data see nameplate. If the rated values are exceeded, the robatherm Technical Service must be informed. Pos: 50.9 /Inbetriebnahme und Wartung/_Wartung @ 0\mod_1257929585257_2008.doc @ 2117 @ 3...
Do not operate LICI-rotors with e.g. supersaturated air or clean wet. The commissioning must be carried out in accordance with the rotor manufacturer’s instructions and the commissioning described by robatherm (see page 42). Pos: 62.6 /Inbetriebnahme und Wartung/Entfeuchtungsrotor/Entfeuchtungsrotor_Rotordrehzahl @ 0\mod_1258443875981_2008.doc @ 2194 @ 44...
Page 58
Put burner into operation. Observe continuous operation of supply and extract fan without any recirculation air. This work is only to be performed by the robatherm customer service unless an alternative agreement has been made. The numbers shown below refer to the figures on page 56: ...