WARNING 1. CAUTION: Review all installation instructions, procedures, cautions and warnings contained within this manual prior to installing and/or servicing this product. As with all releasing device systems, maximum fire protection is provided when installed in accordance with factory specifications and used with optional fuse link systems.
SPECIFICATION Input Power: Voltage Frequency Standby Alarm* Not Supervised 50 Hz 0.3A 0.4A 120VAC 60 Hz 0.3A 0.4A 50 Hz 1.5A 1.8A 24VAC 60 Hz 1.5A 1.8A 24VDC 0.6A 1.2A *Note: Amp value is during alarm condition with 1A load warning connected.
Page 4
IMPORTANT MECHANICAL INSTALLATION PROCEDURE WARNING To reduce the risk of severe injury or death: 1. READ AND FOLLOW ALL INSTALLATION INSTRUCTIONS. 2. Spring tension must be adjusted to allow the fire door to self close during a drop test, alarm activation and/or power failure.
OPERATOR MOUNTING 1. Before the operator is installed, verify that the door is properly operating and balanced. 2. Make sure the mounting plates are correctly positioned for RH or LH mounting. 3. Attach and tighten the mounting hardware to the mounting plate. 4.
Door Sprocket Bracket Door Sprocket Operator Output View "B" Sprocket Correct View "B" View "A" View "A" Drive Sprocket Incorrect * Chain hoist shown. Hand crank similar. ADJUSTING THE DRIVE CHAIN NOTE : Use correct type, size and proper length of roller chain. 1.
Page 8
ADJUSTING OPERATING CHAIN LENGTH (FCA units only) Operating chain is provided in a standard length. Depending on door height, the chain may need to be shortened or lengthened. A DIFFERENT COLOR connecting link can be found in the hand chain. Use this link for breaking the chain to make adjustments to the hand chain length so that the bottom of the hanging chain is 2’...
FIRE ALARM CONNECTION INSTRUCTION For “Indoor Dry” location use only. All wiring must satisfy the most current version of NFPA72 – National Fire Alarm Code and the National Electric Code. 18-gauge wire is recommended. Disconnect power supply before servicing. WARNING 1.
Page 10
TERMINAL CONNECTIONS Disconnect power supply before servicing. WARNING Input power 115VAC*, Not Supervised See Note. 4 Input 24VDC/VAC Alarm Dry Contact (N/C) Alarm door close warning Brake release status Use Power Limited source Not Supervised *Note 1 24VDC, total 1A (Dry contact) only Close button...
Page 11
Connection Chart Terminals Line In Low Voltage Alarm Connection High Voltage 1 & 2 3 & 4 Connection L1 & L2 (24VDC or 24VAC) Type Connect Connect 24VDC or 24VAC Connect FACP* Power Input 115VAC (Voltage supplied by FACP Alarm Dry Contact or an UL listed power supply) Connect Alarm Signal Jump...
Page 12
OPTIONAL FUSIBLE LINK CONFIGURATION/REFERENCE 1. Actual configuration may differ. Must pull cable straight a minimum of 18 inches before changing direction. See door manufacturer recommendations and NFPA 80 for recommended fuselink configurations. 2. To be performed by qualified door system technicians only. Eyebolt Ceiling Thru wall conduit...
All replacement parts must be obtained from the door manufacturer per NFPA 80. Testing of the FCA and FKA are independent of, and shall in no way be interpreted as an alternative method of testing the fire alarm system, and/or any other system component employed on the fire door or counter fire door installation.