Mitsubishi Electric Mr.SLIM PUHZ-P100VHA Service Manual
Mitsubishi Electric Mr.SLIM PUHZ-P100VHA Service Manual

Mitsubishi Electric Mr.SLIM PUHZ-P100VHA Service Manual

Split-type, heat pump air conditioners, r410a, outdoor unit

Advertisement

Quick Links

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
SERVICE MANUAL
R410A
Outdoor unit
[model names]
PUHZ-P100VHA
PUHZ-P125VHA
PUHZ-P140VHA
PUHZ-P100VHA.UK
PUHZ-P100VHA
[Service Ref.]
PUHZ-P100VHA.UK
PUHZ-P100VHA
PUHZ-P125VHA.UK
PUHZ-P125VHA
PUHZ-P140VHA.UK
PUHZ-P140VHA
.UK
1
REVISED EDITION-B
Revision:
• PUHZ-P100/125/140VHA
are added in REVISED
EDITION-B.
• Some descriptions have
.UK
been modified.
1
• Please void OC359
REVISED EDITION-A.
.UK
Note:
1
• This manual describes only
service data of the outdoor
units.
• RoHS compliant products
.UK
have <G> mark on the spec
1
name plate.
• For servicing of RoHS com-
pliant products, refer to the
RoHS Parts List.
CONTENTS
1. TECHNICAL CHANGES·································2
2. REFERENCE MANUAL··································2
3. SAFETY PRECAUTION··································3
4. FEATURES ·····················································6
5. SPECIFICATIONS···········································7
6. DATA ·······························································8
7. OUTLINES AND DIMENSIONS ····················11
8. WIRING DIAGRAM ·······································13
9. WIRING SPECIFICATIONS ··························15
10. REFRIGERANT SYSTEM DIAGRAM··············20
11. TROUBLESHOOTING···································22
12. FUNCTION SETTING····································72
13. EASY MAINTENANCE FUNCTION ··············78
15. DISASSEMBLY PROCEDURE ·····················91
16. PARTS LIST ················································101
17. RoHS PARTS LIST ·····································107
December 2006
No.OC359
.UK
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Mr.SLIM PUHZ-P100VHA and is the answer not in the manual?

Questions and answers

Summary of Contents for Mitsubishi Electric Mr.SLIM PUHZ-P100VHA

  • Page 1: Table Of Contents

    SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS December 2006 No.OC359 REVISED EDITION-B SERVICE MANUAL R410A Outdoor unit Revision: [Service Ref.] [model names] • PUHZ-P100/125/140VHA are added in REVISED PUHZ-P100VHA.UK PUHZ-P100VHA EDITION-B. • Some descriptions have PUHZ-P100VHA been modified. • Please void OC359 PUHZ-P125VHA.UK PUHZ-P125VHA REVISED EDITION-A.
  • Page 2: Technical Changes

    TECHNICAL CHANGES PUHZ-P100VHA.UK PUHZ-P100VHA PUHZ-P125VHA.UK PUHZ-P125VHA PUHZ-P140VHA.UK PUHZ-P140VHA 1. NOISE FILTER CIRCUIT BOARD(N.F.) has been changed. 2. ACTIVE FILTER MODULE (ACTM) has been changed. 3.52C Relay (52C) and rush current protect resister (RS) are mounted to the NOISE FILTER CIRCUIT BOARD(N.F.). REFERENCE MANUAL 2-1.
  • Page 3: Safety Precaution

    SAFETY PRECAUTION 3-1. CAUTIONS RELATED TO NEW REFRIGERANT Cautions for units utilizing refrigerant R410A Use new refrigerant pipes. Do not use refrigerant other than R410A. In case of using the existing pipes for R22, be careful with If other refrigerant (R22 etc.) is used, chlorine in refrige- the followings.
  • Page 4 Unit Gravimeter [3] Service tools Use the below service tools as exclusive tools for R410A refrigerant. Specifications Gauge manifold ·Only for R410A ·Use the existing fitting specifications . (UNF1/2) ·Use high-tension side pressure of 5.3MPa·G or over. Charge hose ·Only for R410A ·Use pressure performance of 5.09MPa·G or over.
  • Page 5 (2) Cautions for refrigerant piping work New refrigerant R410A is adopted for replacement inverter series. Although the refrigerant piping work for R410A is same as for R22, exclusive tools are necessary so as not to mix with different kind of refrigerant. Furthermore as the working pressure of R410A is 1.6 time higher than that of R22, their sizes of flared sections and flare nuts are different.
  • Page 6: Features

    FEATURES PUHZ-P125VHA.UK PUHZ-P125VHA PUHZ-P140VHA.UK PUHZ-P140VHA PUHZ-P100VHA.UK PUHZ-P100VHA CHARGELESS SYSTEM PRE-CHARGED REFRIGERANT IS SUPPLIED FOR PIPING LENGTH AT SHIPMENT. (Max.30m(PUHZ-P125/P140)) The refrigerant circuit with LEV(Linear Expansion Valve) and Accumulator always control the optimal refrigerant level regardless of the length (30m max. and 5m min.) of piping. The additional refrigerant charging work during installation often causes problems.
  • Page 7: Specifications

    SPECIFICATIONS Service Ref. PUHZ-P100VHA.UK PUHZ-P100VHA Cooling Heating Mode Power supply (phase, cycle, voltage) Single, 50Hz, 230V Running current 12.26 12.62 Max. current External finish Munsell 5Y 7/1 Refrigerant control Linear Expansion Valve Hermetic Compressor TNB220FLDM Model Motor output Starter type Line start Protection devices HP switch...
  • Page 8: Data

    DATA 6-1. REFILLING REFRIGERANT CHARGE (R410A : kg) Piping length (one way) Factory Service Ref. charged PUHZ-P100VHA.UK PUHZ-P100VHA PUHZ-P125VHA.UK PUHZ-P125VHA PUHZ-P140VHA.UK PUHZ-P140VHA Longer pipe than 20 or 30m, additional charge is required. 6-2. COMPRESSOR TECHNICAL DATA (at 20°C) PUHZ-P100VHA.UK PUHZ-P125,140VHA.UK Unit PUHZ-P100VHA PUHZ-P125,140VHA...
  • Page 9 6-3. NOISE CRITERION CURVES PUHZ-P100VHA.UK SPL(dB) MODE LINE MICROPHONE COOLING PUHZ-P100VHA HEATING UNIT 1.5m NC-70 NC-60 GROUND NC-50 NC-40 NC-30 APPROXIMATE THRESHOLD OF HEARING FOR NC-20 CONTINUOUS NOISE 1000 2000 4000 8000 BAND CENTER FREQUENCIES, Hz PUHZ-P125VHA.UK PUHZ-P140VHA.UK SPL(dB) MODE LINE MODE SPL(dB)
  • Page 10: Standard Operation Data

    6-4. STANDARD OPERATION DATA PLA-RP100AA2 PLA-RP125AA2 PLA-RP140AA2 Representative matching Heating Cooling Heating Cooling Cooling Heating Mode 16,000 12,300 9,400 11,200 14,000 13,600 Capacity 4.98 Input 4.09 4.11 5.21 3.12 3.28 Indoor unit PLA-RP100AA2 PLA-RP125AA2 PLA-RP140AA2 1 , 50 1 , 50 1 , 50 Phase , Hz Volts...
  • Page 11: Outlines And Dimensions

    OUTLINES AND DIMENSIONS OUTDOOR UNIT Unit : mm PUHZ-P100VHA.UK PUHZ-P100VHA...
  • Page 12 PUHZ-P125VHA.UK Unit : mm PUHZ-P125VHA PUHZ-P140VHA.UK PUHZ-P140VHA...
  • Page 13: Wiring Diagram

    WIRING DIAGRAM PUHZ-P100VHA PUHZ-P125VHA PUHZ-P140VHA T6.3AL250V CY1, CY2 Capacitor...
  • Page 14 PUHZ-P100VHA .UK PUHZ-P125VHA .UK PUHZ-P140VHA...
  • Page 15: Wiring Specifications

    WIRING SPECIFICATIONS 9-1. FIELD ELECTRICAL WIRING (power wiring specifications) Outdoor unit model P100, 125V P140V Outdoor unit power supply ~/N (single), 50 Hz, ~/N (single), 50 Hz, 230 V 230 V Outdoor unit input capacity 32 A 40 A Main switch (Breaker) 2 o Min.
  • Page 16 9-2. SEPARATE INDOOR UNIT/ OUTDOOR UNIT POWER SUPPLIES The following connection patterns are available. The outdoor unit power supply patterns vary on models. 1:1 System A Outdoor unit power supply <For models without heater> B Earth leakage breaker * The optional indoor power supply terminal kit is required. C Wiring circuit breaker or isolating switch D Outdoor unit E Indoor unit/outdoor unit connecting cords...
  • Page 17 9-3. INDOOR – OUTDOOR CONNECTING CABLE The cable shall not be lighter than design 60245 IEC or 60227 IEC. The cable length may vary depending on the condition of installation, humidity or materials, etc. Wire size Cross section Number Polarity L(m) 5 of cable of wires...
  • Page 18 9-4. M-NET WIRING METHOD (Points to notice) (1) Outside the unit, transmission wires should stay away from electric wires in order to prevent electromagnetic noise from making an influence on the signal communication. Place them at intervals of more than 5cm. Do not put them in the same conduit tube.
  • Page 19 M-NET wiring M-NET (1) Use 2-core x 1.25mm shield wire for electric wires. terminal Ground (Excluding the case connecting to system controller.) block wire (2) Connect the wire to the M-NET terminal block.Connect one core of the transmission wire (non-polar) to A terminal and the other to B. Peel the shield wire, twist the shield part to a string and connect it to S terminal.
  • Page 20: Refrigerant System Diagram

    REFRIGERANT SYSTEM DIAGRAM Unit : mm PUHZ-P100VHA.UK PUHZ-P100VHA Service High pressure Bypass valve port protect switch (check) Ball valve Outdoor heat exchanger 4-way valve (#50) Thermistor Refrigerant GAS pipe Strainer (TH6) 15.88A({5/8") Thermistor Service (TH3) port Muffler (check) Thermistor (TH4) Accumulator Distributor Strainer...
  • Page 21 1. Refrigerant collecting (pump down) Perform the following procedures to collect the refrigerant when moving the indoor unit or the outdoor unit. 1Turn on the power supply (circuit breaker). wWhen power is supplied, make sure that “CENTRALLY CONTROLLED” is not displayed on the remote controller. If “CENTRALLY CONTROLLED”...
  • Page 22: Troubleshooting

    TROUBLESHOOTING 11-1. TROUBLESHOOTING <Error code display by self-diagnosis and actions to be taken for service (summary)> Present and past error codes are logged and displayed on the wired remote controller and control board of outdoor unit. Actions to be taken for service, which depends on whether or not the inferior phenomenon is reoccurring at service, are sum- marized in the table below.
  • Page 23 Operating procedures While the room temperature display on the remote "TEST RUN" and the currently selected controller is “PLEASE WAIT”, the remote controller is disabled. operation mode are displayed altemately. Wait until “PLEASE WAIT” disappears before using remote controller. 1. Turn on the main power supply. “PLEASE WAIT”...
  • Page 24 Test run [for wireless remote controller] Measure an impedance between the power supply terminal block on the outdoor unit and ground with a 500V Megger and check that it is equal to or greater than 1.0M". TEST RUN 1 Turn on the main power to the unit. TEST RUN 2 Press the button twice continuously.
  • Page 25 11-3. HOW TO PRECEED "SELF-DIAGNOSIS" 11-3-1. When a Problem Occurs During Operation If a problem occurs in the air conditioner, the indoor and outdoor units will stop, and the problem is shown in the remote controller display. [CHECK] and the refrigerant address are displayed on the temperature display, and the error code and unit number are displayed alternately as shown below.
  • Page 26 When the error history is reset, the display will look like the one shown below. Press the button twice within three seconds. The self-diagnosis ON/OFF However, if you fail to reset the error history, the error content will be displayed again. address or refrigerant address will flash.
  • Page 27 11-3-4. Malfunction-diagnosis method by wireless remote controller <In case of trouble during operation> When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform unusual stop. < Malfunction-diagnosis method at maintenance service> [Procedure] 1.
  • Page 28 • Refer to the following tables for details on the check codes. [Output pattern A] Beeper sounds Beep Beep Beep Beep Beep Beep Beep OPERATION · · · Repeated INDICATOR lamp blink pattern Approx. 2.5 sec. 0.5 sec. 0.5 sec. 0.5 sec.
  • Page 29 11-4. SELF-DIAGNOSIS ACTION TABLE (Note 1) Refer to indoor unit section for code P and code E. <Abnormalities detected when the power is put on> Error Code Meaning of error code and detection method Judgment and action Case 1 No voltage is supplied to terminal 1 Check following items.
  • Page 30 Error Code Meaning of error code and detection method Case Judgment and action 1 Contact failure or mis-wiring of 1 Check disconnection or looseness or polarity Indoor/outdoor unit connector indoor/outdoor unit connecting of indoor/outdoor unit connecting wire of mis-wiring, excessive number of units indoor and outdoor units.
  • Page 31 <Abnormalities detected while unit is operating> Error Code Meaning of error code and detection method Judgment and action Case Abnormal high pressure (High-pressure 1 Short cycle of indoor unit 1~6Check indoor unit and repair defectives. 2 Clogged filter of indoor unit switch 63H worked) Abnormal if high-pressure switch 63H 3 Decreased airflow caused by...
  • Page 32 Error Code Meaning of error code and detection method Judgment and action Case Open/short circuit of discharge 1 Disconnection or contact 1 Check connection of connector (TH4) on the temperature thermistor (TH4) failure of connector (TH4) on outdoor controller circuit board. Check breaking of the lead wire for the outdoor controller circuit Abnormal if open (3: or less) or short...
  • Page 33 Error Code Meaning of error code and detection method Judgment and action Case 11 Failure in the operation of 1 Check or replace the DC fan motor. Abnormality in the outdoor fan motor The outdoor fan motor is considered to be the DC fan motor 2 Failure in the outdoor circuit 2 Check the voltage of the outdoor circuit...
  • Page 34 Error Code Meaning of error code and detection method Judgment and action Case 1 Stop valve of outdoor unit is 1 Open stop valve. Compressor overcurrent interruption Abnormal if overcurrent DC bus or com- closed. 2 Decrease of power supply volt- 2 Check facility of power supply.
  • Page 35 Error Code Meaning of error code and detection method Judgment and action Case Remote controller transmission 1 Set a remote controller to main, and the error(E3)/signal receiving error(E5) 1 Two remote controllers are set other to sub. 1 Abnormal if remote controller could not as “main.”...
  • Page 36 Error Code Meaning of error code and detection method Judgment and action Case 1 Slight temperature difference Abnormality of pipe temperature Check pipe <liquid or condenser / <Cooling mode> between indoor room evaporator> temperature with room Detected as abnormal when the pipe tem- temperature and pipe <liquid temperature display on remote perature is not in the cooling range 3 min-...
  • Page 37 Error Code Meaning of error code and detection method Case Judgment and action 1 Data of transmission proces- Communication error with communica- Turn off the power supply of outdoor unit, tion processor sor or unit processor is not indoor unit and FRESH MASTER or LOSS- Defective communication between unit transmitted normally because NAY at the same time for 2 minutes or more,...
  • Page 38 From the previous page. Error Code Meaning of error code and detection method Case Judgment and action 1 During group operation with Same as mentioned in “A7” of the previous 4. If displayed address or attribute is remote controller, indoor unit of multi- refrigerant page system, if indoor unit transmit Indoor unit detects abnormality when...
  • Page 39 Error Code Meaning of error code and detection method Case Judgment and action 1 Transmitting condition repeats 1 Check transmission wave form or noise on M-NET•NO RESPONSE Abnormal if a message was transmitted fault because of noise and the transmission wire. like.
  • Page 40 Phenomena Factor Countermeasure 4. Even controlling by the wireless 1The pair number settings of the wireless remote 1Check the pair number settings. remote controller, no beep is heard controller and indoor controller board are mis- and the unit does not start operat- matched.
  • Page 41 Symptoms: “PLEASE WAIT” is kept being displayed on the remote controller. Inspection method and Diagnosis flow Cause troubleshooting Check the display time of “PLEASE WAIT” after turning on the main power. 6 minutes 2 minutes or more or less How long is “PLEASE WAIT” •...
  • Page 42 LED display of the indoor controller board Symptoms: Nothing is displayed on the remote controller 1 LED1 : LED2 : LED3 : Inspection method and Diagnosis flow Cause troubleshooting Check the voltage between S1 and S2 on the terminal block (TB4) of the indoor unit which is used to connect the indoor unit and the outdoor unit.
  • Page 43 LED display of the indoor controller board Symptoms: Nothing is displayed on the remote controller 2 LED1 : LED2 : LED3 : Inspection method and Diagnosis flow Cause troubleshooting Check the voltage between S1 and S2 on the terminal block (TB4) of the indoor unit which is used to connect the indoor unit and the outdoor unit.
  • Page 44 LED display of the indoor controller board Symptoms: Nothing is displayed on the remote controller 3 LED1 : LED2 : LED3 : — Inspection method and Diagnosis flow Cause troubleshooting Check the voltage of the terminal block (TB6) of the remote controller. DC 10V to DC 16V? •...
  • Page 45 • Before repair Frequent calling from customers Phone Calls From Customers How to Respond Note 1 The operating display of remote 1 Check if power is supplied to air conditioner. Unit does not operate controller does not come on. Nothing appears on the display unless power is at all.
  • Page 46 Phone Calls From Customers How to Respondm Note The room cannot be cooled or heated sufficiently. 1 Check the set temperature of remote controller. The outdoor unit cannot be operated if the set temperature is not appropriate. The outdoor unit operates in the following modes. COOL: When the set temperature is lower than the room temperature.
  • Page 47 Phone Calls From Customers How to Respond Note 3 Air blows out for a while after Something 3 This is not a malfunction. However, this control is also is wrong HEAT operation is stopped. The blower is operating just for cooling down the applied to the models which with the heated-up air conditioner.
  • Page 48 Phone Calls From Customers How to Respond Note A white mist is expelled from the indoor unit. This is not a malfunction. This may occur when the operation gets started in the room of high humidity. Water or moisture is expelled from the outdoor Cooling;...
  • Page 49 11-6. HOW TO CHECK THE PARTS PUHZ-P100VHA.UK PUHZ-P125VHA.UK PUHZ-P140VHA.UK PUHZ-P100VHA .UK PUHZ-P125VHA .UK PUHZ-P140VHA Parts name Check points Thermistor (TH3) Disconnect the connector then measure the resistance with a tester. <Outdoor pipe> (Surrounding temperature 10:~30:) Thermistor (TH4) Normal Abnormal <Discharge> 160k"~410k"...
  • Page 50 Check method of DC fan motor (fan motor / outdoor controller circuit board) Notes · High voltage is applied to the connecter (CNF1, 2) for the fan motor. Give attention to the service. · Do not pull out the connector (CNF1, 2) for the motor with the power supply on. board and fan motor.) (It causes trouble of the outdoor controller circuit Self check...
  • Page 51 11-7. HOW TO CHECK THE COMPONENTS <Thermistor feature chart> Low temperature thermistors • Thermistor <Outdoor pipe> (TH3) • Thermistor <Outdoor 2-phase pipe> (TH6) • Thermistor <Outdoor> (TH7) Thermistor R0 = 15k' ± 3% B constant = 3480 ± 2% =15exp{3480( 273+t – 273 )} 15k' 4.3k' 9.6k'...
  • Page 52 Linear expansion valve (1) Operation summary of the linear expansion valve • Linear expansion valve open/close through stepping motor after receiving the pulse signal from the outdoor controller board. • Valve position can be changed in proportion to the number of pulse signal. <Connection between the indoor controller board and the linear expansion valve>...
  • Page 53 (3) How to attach and detach the coil of linear expansion valve <Composition> Linear expansion valve is separable into the main body and the coil as shown in the diagram below. Main body Stopper Coil Lead wire <How to detach the coil> Hold the lower part of the main body (shown as A) firmly so that the main body does not move and detach the coil by pulling it upward.
  • Page 54: Emergency Operation

    11-8. EMERGENCY OPERATION (1) When the error codes shown below are displayed on outdoor unit or microcomputer for wired remote controller or indoor unit has a failure, but no other problems are found, emergency operation will be available by setting the emergency opera- tion switch (SWE) to ON and short-circuiting the connector (CN31) on outdoor controller board.
  • Page 55 (5) Operation data during emergency operation During emergency operation, no communication is performed with the indoor unit, so the data items needed for operation are set to the following values: Operation mode Operation data Remarks COOL HEAT Intake temperature (TH1) 20.5: Indoor liquid pipe temperature (TH2) Indoor 2-phase pipe temperature (TH5)
  • Page 56 11-9. TEST POINT DIAGRAM <CAUTION> TEST POINT1 is high voltage. Outdoor controller circuit board PUHZ-P100VHA.UK PUHZ-P125VHA.UK PUHZ-P140VHA.UK PUHZ-P100VHA PUHZ-P125VHA PUHZ-P140VHA (TEST POINT 1) (voltage between pins of C5E) (TEST POINT 2) : 280V-380V DC (Indoor/outdoor unit Communication High pressure switch (voltage between pins of C6B): DC 15V connecting wire) power supply...
  • Page 57 Outdoor noise filter circuit board PUHZ-P100VHA.UK PUHZ-P125VHA.UK LO, NO Voltage of 220-240V AC is output PUHZ-P140VHA.UK (Connect to the outdoor power circuit board (TABS, TABT)) CNAC1, CNAC2 220-240V AC (Connect to the outdoor controller circuit board (CNAC)) Primary current (Connect to the outdoor power circuit board (CN5))
  • Page 58 Outdoor noise filter circuit board PUHZ-P100VHA PUHZ-P125VHA PUHZ-P140VHA CN52C 52C driving signal (Connect to the outdoor controller circuit board (CN52C).) LO, NO Voltage of 220-240V AC is output (Connect to the outdoor CNAC1, CNAC2 power circuit board 220-240V AC (TABS, TABT)) (Connect to the outdoor controller circuit board...
  • Page 59 Outdoor power circuit board Brief Check of POWER MODULE W Usually, they are in a state of being short-circuited if they are broken. PUHZ-P100VHA.UK Measure the resistance in the following points (connectors, etc.). PUHZ-P125VHA.UK If they are short-circuited, it means that they are broken. 1.
  • Page 60 11-10. FUNCTION OF SWITCHES, CONNECTORS AND JUMPERS (1) Function of switches Type Action by the switch operation Function Effective timing Switch switch When compressor is working Compulsory defrosting Start Normal in heating operation. w Abnormal history clear Clear Normal off or operating 1 2 3 4 5 6 1 2 3 4 5 6...
  • Page 61 (2) Function of connectors and switches Action by open/ short operation Connector Types Function Effective timing Switch Short Open When power supply ON Connector CN31 Emergency operation Start Normal SW6-1 SW6-2 MODEL SW10 MODEL SW10 SW6-3 100V 125V SW6-4 Model select 1 2 3 4 5 6 1 2 3 4 5 6 SW6-5...
  • Page 62 <Display function of inspection for outdoor unit> The blinking patterns of both LED1(green) and LED2(red) indicate the types of abnormality when it occurs. Types of abnormality can be indicated in details by connecting an optional part ‘A-Control Service Tool (PAC-SK52ST)’ to connector CNM on outdoor controller board.
  • Page 63 Indication Error Outdoor controller board Error Detailed Contents Inspection method reference code LED1 (Green) LED2 (Red) page 1Check if stop valves are open. 3 blinking 1 blinking Abnormality of shell thermostat P.31 2Check if connectors (TH4, LEV-A) on outdoor controller board are not and discharging temperature (TH4) disconnected.
  • Page 64 <Outdoor unit operation monitor function> [When option part ‘A-Control Service Tool(PAC-SK52ST)’ is connected to outdoor controller board(CNM)] Digital indicator LED1 displays 2 digit number or code to inform operation condition and the meaning of error code by controlling DIP SW2 on ‘A-Control Service Tool’. Operation indicator SW2 : Indicator change of self diagnosis SW2 setting...
  • Page 65 SW2 setting Display detail Explanation for display Unit Pipe temperature / Liquid(TH3) – 40~90 – 40~90 (When the coil thermistor detects 0: or below, “–” and temperature are displayed by turns.) (Example) When -10:; 2 3 4 5 6 0.5 secs. 0.5secs.
  • Page 66 SW2 setting Display detail Explanation for display Unit Pipe temperature / Liquid(TH3) on error – 40~90 occurring (When the coil thermistor detects 0: or below, “–” – 40~90 and temperature are displayed by turns.) (Example) When –15:; 0.5 secs. 0.5secs. 2 secs.
  • Page 67 SW2 setting Display detail Explanation for display Unit The number of connected indoor units (The number of connected indoor units are dis- played.) Unit 2 3 4 5 6 Capacity setting display Displayed as an outdoor capacity code. Capacity Code Code P100V display...
  • Page 68 SW2 setting Display detail Explanation for display Unit Indoor setting temperature 17~30 17~30 2 3 4 5 6 Outdoor pipe temperature / Cond./ -39~88 Eva. (TH6) (When the temperature is 0: or less, “–” and -39~88 temperature are displayed by turns.) 2 3 4 5 6 Outdoor outside temperature (TH7) -39~88...
  • Page 69 SW2 setting Display detail Explanation for display Unit 0~100 Capacity save (When the capacity is 100% hundreds digit, tens digit 0~100 and ones digit are displayed by turns.) When air conditioner is connected to (Example) When 100%; M-NET and capacity save mode is 0.5 secs.
  • Page 70 SW2 setting Display detail Explanation for display Unit 0~480 LEV-A opening pulse on error occurring (When it is 100 pulse or more, hundreds digit, tens 0~480 digit and ones digit are displayed by turns.) (Example) When 130 pulse; Pulse 0.5 secs. 0.5secs.
  • Page 71 SW2 setting Display detail Explanation for display Unit Discharge super heat on error occurring 0~255 (When the temperature is 100°C or more, hundreds digit, tens digit and ones digit are displayed by 0~255 turns.) Cooling = TH4-TH6 (Example) When 150°C; 0.5 secs.
  • Page 72: Function Setting

    FUNCTION SETTING 12-1. UNIT FUNCTION SETTING BY THE REMOTE CONTROLLER Each function can be set according to necessity using the remote controller. The setting of function for each unit can only be done by the remote controller. Select function available from the table 1. (1) Functions available when setting the unit number to 00 (Select 00 referring to 4 setting the indoor unit number.) W1 The functions below are available only when the wired remote controller is used.The functions are not available for floor standing models.
  • Page 73 12-1-1. Selecting functions using the wired remote controller First, try to familiarize yourself with the flow of the function selection procedure. In this section, an example of setting the room temperature detection position is given. For actual operations, refer to steps 1 to 0 . Setting number Refrigerant address Unit number...
  • Page 74 [Operating Procedure] 1 Check the setting items provided by function selection. If settings for a mode are changed by function selection, the functions of that mode will be changed accordingly. Check all the current settings according to steps 2 to 7 , fill in the "Check" column in Table 1, and then change them as necessary. For factory settings, refer to the indoor unit's installation manual. 2 Switch off the remote controller.
  • Page 75 12-1-2. Selecting functions using the wireless remote controller (Type C) Functions can be selected with the wireless remote controller. Function selection using wireless remote controller is available only for refriger- ant system with wireless function. Refrigerant address cannot be specified by the wireless remote controller. [Flow of function selection procedure] The flow of the function selection procedure is shown below.
  • Page 76 12-2. FUNCTION SELECTION OF REMOTE CONTROLLER The setting of the following remote controller functions can be changed using the remote controller function selection mode. Change the setting when needed. Item 1 Item 2 Item 3 (Setting content) 1.Change Language Language setting to display •...
  • Page 77 Flowchart of Function Setting Setting language (English) Normal display (Display when the air condition is not running) Hold down the button and press the button for 2 seconds. Hold down the button and press the button for 2 seconds. Press the operation mode button. Press the TIMER MENU button.
  • Page 78: Easy Maintenance Function

    EASY MAINTENANCE FUNCTION Reduces maintenance work drastically. Enables you to check operation data of the indoor and outdoor units by remote controller. Furthermore, use of maintenance stable-operation control that fixes the operating frequency, allows smooth inspection, even for inverter models. Smooth Mainte- Discharge temperature 64: Conventional inspection work...
  • Page 79 Data measurement When the operation is stabilized, measure operation data as explained below. (4) Press the [TEMP] buttons ( ) to select the desired refrigerant address. [Screen (5) Select the type of data to be displayed. After selecting, go to step (6). Compressor information button MENU...
  • Page 80 13-2.GUIDE FOR OPERATION CONDITION Inspection item Result Check Points Breaker Good Retightened Enter the temperature differences between into Terminal block Outdoor Unit Good Retightened the graph given below. Indoor Unit Good Retightened Operation state is determined according to the plotted areas on (Insulation resistance) M"...
  • Page 81: Monitoring The Operation Databythe Remote Controller

    MONITORING THE OPERATION DATABYTHE REMOTE CONTROLLER 14-1. HOW TO "MONITOR THE OPERATION DATA" • Turn on the [Monitoring the operation data] Example) Request code "004" Discharge temperature 69 ; Refrigerant address "00" B: Refrigerant address C: Data display area D: Request code display area (1) Press the button for 3 seconds so that [ Maintenance mode] appears on the screen (at TEST...
  • Page 82 14-2. REQUEST CODE LIST * Certain indoor/outdoor combinations do not have the request code function; therefore, no request codes are displayed. Description Request content Unit Remarks (Display range) Operation state Refer to 14-2-1. Detail Contents in Request Code. – Compressor-Operating current (rms) 0 –...
  • Page 83 Description Request content Unit Remarks (Display range) Indoor unit-Control state – Refer to 14-2-1.Detail Contents in Request Code. Outdoor unit-Control state – Refer to 14-2-1.Detail Contents in Request Code. Refer to 14-2-1.Detail Contents in Request Code. Compressor-Frequency control state – Outdoor unit-Fan control state Refer to 14-2-1.Detail Contents in Request Code.
  • Page 84 Description Request content Unit Remarks (Display range) Error history 1 (latest) Displays error history. (" - - " is displayed if no history is present.) Code Error history 2 (second to last) Displays error history. (" - - " is displayed if no history is present.) Code Error history 3 (third to last) Displays error history.
  • Page 85 Description Request content Unit Remarks (Display range) Indoor-Fan operating time 0 – 9999 1 hour (After filter is reset) Indoor-Total operating time 0 – 9999 10 hours (Fan motor ON time) Indoor fan output value (Sj value) 0 – 255 Fan control data –...
  • Page 86 14-2-1. Detail Contents in Request Code Example) Request code "004" Discharge temperature 69 : Refrigerant address "00" B: Refrigerant address C: Data display area D: Request code display area [Operation state] (Request code ": 0 ") Relay output state Power currently Data display Display Compressor...
  • Page 87 [Fan control state] (Request code :" 53 ") Data display Fan step correction value by heat sink temperature overheat prevention control Fan step correction value by cool condensation temperature overheat prevention control Display Correction value - (minus) – 1 [Actuator output state] (Request code :"54") Data display Actuator output state 1 Actuator output state 2...
  • Page 88 [Contact demand capacity] (Request code "61") Setting content Data display Setting Display Setting value Setting content SW7-1 SW7-2 100% [External input state] (Request code "62") Input state : Input present Data display Contact demand Silent mode Spare 1 Spare 2 Display Input state input...
  • Page 89 [Outdoor unit switch setting display (SW1 to SW10, except SW3)] Request codes: 73 to 82 0: Swich OFF 1: Swich ON 0: Swich OFF 1: Swich ON SW1, SW2, SW6, SW7 Data display Data display 00 00 00 00 00 01 00 01 00 02 00 02...
  • Page 90 [Indoor unit – Model setting information] (Request code : 162) Data display Display Model setting state Display Model setting state PSA-RP•GA, PSH-PGAH PKA-RP•FAL, PKH-P•FALH See the table on the right. PEAD-RP•EA(2)/GA, PEHD-P•EAH PCA-RP•GA, PCH-P•GAH SEZ-KA•VA SLZ-KA•VA(L) PCA-RP•HA PKA-RP•GAL, PKH-P•GALH PLA-RP• AA PEA-RP•EA PLH-P•AAH MEXZ-GA•VA(L)
  • Page 91: Disassembly Procedure

    DISASSEMBLY PROCEDURE PUHZ-P100VHA.UK PUHZ-P100VHA OPERATING PROCEDURE PHOTOS & ILLUSTRATION Top panel fixing screws 1. Removing the service panel and top panel Figure 1 Top panel (1) Remove 3 service panel fixing screws (5 10) and slide the hook on the right downward to remove the service panel.
  • Page 92: Operating Procedure

    OPERATING PROCEDURE PHOTOS Thermistor 4. Removing the thermistor <Outdoor 2-phase pipe> (TH6) Photo 4 <Outdoor 2-phase pipe> (1) Remove the service panel. (See figure 1.) (TH6) (2) Remove the top panel. (See figure 1.) (3) Disconnect the connectors, TH6 and TH7 (red), on the controller circuit board in the electrical parts box.
  • Page 93 OPERATING PROCEDURE PHOTOS Photo 7 7. Removing the solenoid valve coil <Four-way valve> (21S4), linear expansion valve coil (LEV(A)) and solenoid Linear expansion solenoid valve coil <Bypass valve> (SV) valve coil valve coil (LEV A) (1) Remove the service panel. (See figure 1.) <Four-way valve>...
  • Page 94 OPERATING PROCEDURE PHOTOS 10. Removing the bypass valve Photo 9 (1) Remove the service panel. (See figure 1.) solenoid Linear expansion (2) Remove the top panel. (See figure 1.) valve coil valve coil (LEV A) (3) Remove the electrical parts box. (See photo 3.) <Four-way valve>...
  • Page 95 OPERATING PROCEDURE PHOTOS 13. Removing the motor for compressor (MC) Photo 12 (1) Remove the service panel. (See figure 1.) (2) Remove the top panel. (See figure 1.) (3) Remove 2 front cover panel fixing screws (5 10) and Inlet remove the front cover panel.
  • Page 96 PUHZ-P125VHA.UK PUHZ-P140VHA.UK PUHZ-P125VHA .UK PUHZ-P140VHA OPERATING PROCEDURE PHOTOS & ILLUSTRATION 1. Removing the service panel and top panel Top panel fixing screws Top panel Figure 1 (1) Remove 3 service panel fixing screws (5 10) and slide the hook on the right downward to remove the service Service panel panel.
  • Page 97 OPERATING PROCEDURE PHOTOS Thermistor 4. Removing the thermistor <Outdoor 2-phase pipe> (TH6) Photo 4 <Outdoor 2-phase pipe> (1) Remove the service panel. (See figure 1.) (TH6) (2) Remove the top panel. (See figure 1.) (3) Disconnect the connectors, TH6 and TH7 (red), on the controller circuit board in the electrical parts box.
  • Page 98 OPERATING PROCEDURE PHOTOS 7. Removing the solenoid valve coil <Four-way valve> (21S4), Photo 7 and linear expansion valve coil (LEV(A)) (1) Remove the service panel. (See figure 1.) (2) Remove the top panel. (See figure 1.) [Removing the solenoid valve coil <Four-way valve>] (3) Remove four-way valve solenoid coil fixing screw (4) Remove the solenoid valve coil <Four-way valve>...
  • Page 99 OPERATING PROCEDURE PHOTOS 10. Removing the high pressure switch (63H) Photo 8 (1) Remove the service panel. (See figure 1.) (2) Remove the top panel. (See figure 1.) (3) Remove 3 right side panel fixing screws (5 10) in the Lead wire of high pressure switch High pressure switch (63H) rear of the unit and remove the right side panel.
  • Page 100 OPERATING PROCEDURE PHOTOS 12. Removing the motor for compressor (MC) Photo 10 (1) Remove the service panel. (See figure 1.) (2) Remove the top panel. (See figure 1.) (3) Remove 2 front cover panel fixing screws (5 10) and remove the front cover panel. (See photo 3.) (4) Remove 2 back cover panel fixing screws (5 10) and remove the back cover panel.
  • Page 101: Parts List

    PARTS LIST ( non-RoHS compliant ) STRUCTURAL PARTS PUHZ-P100VHA.UK ty/set Price Recom- Wiring Remarks PUHZ-P Part No. Part Name Specification Diagram mended (Drawing No.) Symbol Unit Amount VHA.UK — (5 10) (DG12F536H10) F.ST SCREW S70 E10 662 SIDE PANEL (L) S70 E20 675 FAN GRILLE S70 E10 668...
  • Page 102 FUNCTIONAL PARTS PUHZ-P100VHA.UK 27 26...
  • Page 103 Part numbers that are circled are not shown in the figures. ty/set Price Wiring Recom- PUHZ-P Remarks Specification Part No. Part Name Diagram mended (Drawing No.) Symbol Unit Amount VHA.UK S70 K04 115 PROPELLER FAN S70 K01 097 S70 E10 763 FAN MOTOR S70 E33 202 THERMISTOR (DISCHARGE)
  • Page 104 FUNCTIONAL PARTS PUHZ-P125VHA.UK PUHZ-P140VHA.UK...
  • Page 105 Part numbers that are circled are not shown in the figures. ty/set Price Wiring PUHZ-P Recom- Remarks Part No. Part Name Specification Diagram mended (Drawing No.) Symbol Unit Amount VHA.UK S70 E10 763 FAN MOTOR S70 E60 408 HEAT EXCHANGER (TOP) S70 K04 115 PROPELLER FAN S70 K01 097...
  • Page 106 STRUCTURAL PARTS PUHZ-P125VHA.UK PUHZ-P140VHA.UK ty/set Price Wiring Recom- Remarks PUHZ-P Part No. Part Name Specification Diagram mended (Drawing No.) 125, 140 Unit Amount Symbol VHA.UK (5 10) — (DG12F536H10) F.ST SCREW S70 E20 662 SIDE PANEL (L) S70 E20 675 FAN GRILLE S70 E20 668 FRONT PANEL...
  • Page 107: Rohs Parts List

    RoHS PARTS LIST STRUCTURAL PARTS PUHZ-P100VHA.UK PUHZ-P100VHA Q,ty/set Price Wiring Recom- PUHZ-P Remarks Part No. Specification mended Diagram Part Name (Drawing No.) Symbol Unit Amount (DG12F536H10) — F.ST SCREW (5 10) S70 E10 662 SIDE PANEL (L) S70 E20 675 FAN GRILLE S70 E10 668 FRONT PANEL...
  • Page 108 FUNCTIONAL PARTS PUHZ-P100VHA.UK PUHZ-P100VHA 27 26...
  • Page 109 Part numbers that are circled are not shown in the figures. Q,ty/set Price Wiring Recom- Remarks Specification PUHZ-P100 Part No. Part Name Diagram mended (Drawing No.) Symbol Unit Amount VHA.UK S70 K04 115 PROPELLER FAN S70 K01 097 S70 E10 763 FAN MOTOR S70 E33 202 THERMISTOR (DISCHARGE)
  • Page 110 FUNCTIONAL PARTS PUHZ-P125VHA.UK PUHZ-P140VHA.UK PUHZ-P125VHA PUHZ-P140VHA...
  • Page 111 Part numbers that are circled are not shown in the figures. ty/set Price Wiring PUHZ-P Recom- Remarks Part No. Part Name Specification Diagram mended (Drawing No.) Symbol Unit Amount VHA.UK VHA VHA.UK S70 E10 763 FAN MOTOR S70 E60 408 HEAT EXCHANGER(TOP) S70 K04 115 PROPELLER FAN...
  • Page 112 S70 E10 655 HANDLE HEAD OFFICE : TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN CCopyright 2006 MITSUBISHI ELECTRIC ENGINEERING CO., LTD. Distributed in Dec. 2006 No.OC359 REVISED EDITION-B PDF 8 Distributed in Jul. 2006 No.OC359 REVISED EDITION-A PDF 7 New publication, effective Dec.
  • Page 113 Related Links Model Number: PUHZ-P125VHA.UK PUHZ-P100-140_Parts_Catalog_(OC359B) PUHZ-P100-140_Service_Manual_(OC359B)

This manual is also suitable for:

Mr.slim puhz-p125vhaMr.slim puhz-p140vhaPuhz-p100vha.ukPuhz-p100vha1.ukPuhz-p125vha.ukPuhz-p125vha1.uk ... Show all