Tecnologic TLK 38-S Series Operation Manual

Microprocessor-based digital

Advertisement

TLK 38
MICROPROCESSOR-BASED
DIGITAL
T
EMPERATURE CONTROLLER
Operation Manual
The TLK38-S (Simplified) Series
Replaced the TLK38 Series in July, 2017.
The TLK38-S is a simplified version of the original TLK38. The new
"S" version is identical in size and functionally is similar to the original
in many respects, including PID control. However, the list of
parameters has been significantly reduced. While this makes the "S"
model far easier to program (there's only one 'list' of parameters to
scroll through), buyers seeking a replacement for an original TLK38
should check the TLK38-S User Manual to ensure that the "S" model
has the functions (parameters) they require.
ADVANCED THERMOELECTRIC
PO Box 1003, WRJ, VT 05001
toll-free 1(866) 665-5434
(603) 888-2467
sales@electracool.com
FOREWORD:
This manual contains the information necessary for the product
to be installed correctly and also instructions for its maintenance
and use; we therefore recommend that the utmost attention is
paid to the following instructions.
Though this manual has been issued with the greatest
care, TECNOLOGIC S.p.A. will not take any responsibility
deriving from its use. The same applies to each person or
Company involved in the issuing of this manual.
This document is the exclusive property of TECNOLOGIC
S.p.A. which forbids any reproduction and divulgation, even in
part, of the document, unless expressly authorized.
TECNOLOGIC S.p.A. reserves the right to make any formal
or functional changes at any moment and without any notice.
TECNOLOGIC spa - TLK 38 - OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06519 - PAG. 1
Pollock Industries, Inc.
INDEX
1 - INSTRUMENT DESCRIPTION
1.1 - GENERAL DESCRIPTION
TLK 38 is a "single loop" digital microprocessor-based controller,
with ON/OFF, Neutral Zone ON/OFF, PID single action, PID dual
action (direct and reverse) control and with AUTO-TUNING FAST
function, SELF-TUNING function and automatic calculation of the
FUZZY OVERSHOOT CONTROL parameter for PID control. The
PID control has a particular algorithm with TWO DEGREES OF
FREEDOM that optimizes the instrument's features independently in
the event of process disturbance and Set Point variations. The
process value is visualized on 4 red displays, while the output
status is indicated by 2 LED displays. The instrument is equipped
with a 3 LED programmable shift indexes. The instrument provides
for the storage of 4 Set Points and can have up to 2 outputs: relay
type or can drive solid state relays type (SSR).
Depending on the model required the input accept:
C: Thermocouples temperature probes (J,K,S and TECNOLOGIC
IRS Infrared sensors), mV signals (0..50/60 mV, 12..60 mV),
Thermoresistances PT100.
E : Thermocouples temperature probes (J,K,S and TECNOLOGIC
IRS Infrared sensors), mV signals (0..50/60 mV, 12..60 mV),
Thermistors PTC and NTC.
I : normalized analogue signals 0/4..20 mA
V : normalized analogue signals 0..1 V, 0/1..5 V, 0/2..10 V
Other important available functions are: Loop-Break Alarm function,
reaching of the Set Point at controlled speed, ramp and dwell
toll-free 1-866-665-5434
1
INSTRUMENT DESCRIPTION
1.1
GENERAL DESCRIPTION
1.2
FRONT PANEL DESCRIPTION
2
PROGRAMMING
2.1
FAST PROGRAMMING OF SET POINT
2.2
SELECTION OF CONTROL STATE AND PARAMETER
PROGRAMMING
2.3
PARAMETER PROGRAMMING LEVELS
2.4
CONTROL STATES
2.5
ACTIVE SET POINT SELECTION
3
INFORMATION ON INSTALLATION AND USE
3.1
PERMITTED USE
3.2
MECHANICAL MOUNTING
3.3
ELECTRICAL CONNECTIONS
3.4
ELECTRICAL WIRING DIAGRAM
4
FUNCTIONS
4.1
MEASURING AND VISUALIZATION
4.2
OUTPUTS CONFIGURATION
4.3
ON/OFF CONTROL
4.4
NEUTRAL ZONE ON/OFF CONTROL
4.5
SINGLE ACTION PID CONTROL
4.6
DOUBLE ACTION PID CONTROL
4.7
AUTO-TUNING AND SELF-TUNING FUNCTIONS
4.8
REACHING OF SET POINT AT CONTROLLED SPEED
AND AUTOMATIC COMMUTATION BETWEEN TWO
SET POINTS
4.9
SOFT-START FUNCTION
4.10
ALARMS OUTPUTS FUNCTIONS
4.11
LOOP BREAK ALARM FUNCTION
4.12
FUNCTION OF KEY "U"
4.13
PARAMETERS CONFIGURATION BY KEY01
5
PROGRAMMABLE PARAMETERS TABLE
6
PROBLEMS , MAINTENANCE AND GUARANTEE
6.1
ERROR SIGNALLING
6.2
CLEANING
6.3
GUARANTEE AND REPAIRS
7
TECHNICAL DATA
7.1
ELECTRICAL DATA
7.2
MECHANICAL DATA
7.3
MECHANICAL DIMENSIONS, PANEL CUT-OUT AND
MOUNTING
7.4
FUNCTIONAL DATA
7.5
MEASUREMENT RANGE TABLE
7.6
INSTRUMENT ORDERING CODE
(603) 888-2467
sales@electracool.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TLK 38-S Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Tecnologic TLK 38-S Series

  • Page 1 Set Point at controlled speed, ramp and dwell TECNOLOGIC spa - TLK 38 - OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06519 - PAG. 1 Pollock Industries, Inc.
  • Page 2: Front Panel Description

    20 seconds, or keep the “UP” or “DOWN” pressed until exit to enter into the operating parameters menu "OPEr" from the programming mode is obtained. TECNOLOGIC spa - TLK 38 - OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06519 - PAG. 2 Pollock Industries, Inc. toll-free 1-866-665-5434 (603) 888-2467...
  • Page 3 As the instrument is built-in equipment TECNOLOGIC spa - TLK 38 - OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06519 - PAG. 3 Pollock Industries, Inc.
  • Page 4: Electrical Wiring Diagram

    - for thermoresistances Pt100 IEC (Pt1) or thermistors PTC KTY81-121 (Ptc) or NTC 103AT-2 (ntc) TECNOLOGIC spa - TLK 38 - OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06519 - PAG. 4 Pollock Industries, Inc. toll-free 1-866-665-5434 (603) 888-2467...
  • Page 5: Outputs Configuration

    “tcr1” has to have a low value with contained in the group “ rEG”. a very frequent intervention of the control output. TECNOLOGIC spa - TLK 38 - OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06519 - PAG. 5 Pollock Industries, Inc. toll-free 1-866-665-5434 (603) 888-2467...
  • Page 6 4) Program an output as 2.rEG if the instrument controls a memory and remain constant during control. dual-action plant TECNOLOGIC spa - TLK 38 - OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06519 - PAG. 6 Pollock Industries, Inc. toll-free 1-866-665-5434 (603) 888-2467 sales@electracool.com...
  • Page 7: Soft-Start Function

    Note: In case of PID control, if Auto-tuning is desired whilst the MEASUREMENT ERROR ramp function is active, this will not be carried out until the tuning TECNOLOGIC spa - TLK 38 - OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06519 - PAG. 7 Pollock Industries, Inc. toll-free 1-866-665-5434 (603) 888-2467 sales@electracool.com...
  • Page 8: Alarm Delay

    (yES=alarm active; no=alarm deactivated). "Ab1" - ALARM CONFIGURATION: This parameter can assume a value between 0 and 31. TECNOLOGIC spa - TLK 38 - OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06519 - PAG. 8 Pollock Industries, Inc. toll-free 1-866-665-5434 (603) 888-2467...
  • Page 9: Programmable Parameters

    4) observe the indication led on the device KEY 01: if it results green this means that a configuration is already loaded on the TECNOLOGIC spa - TLK 38 - OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06519 - PAG. 9 Pollock Industries, Inc.
  • Page 10 HidE / LHdE LHAb= Absolute Band LodE= Deviation Low HidE= Deviation High LHdE= Deviation Band TECNOLOGIC spa - TLK 38 - OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06519 - PAG. 10 Pollock Industries, Inc. toll-free 1-866-665-5434 (603) 888-2467 sales@electracool.com...
  • Page 11 Reinforced insulation between the low voltage section (Supply 115 / cannot be modified 230 V and relay outputs) and the extra low voltage section (input, TECNOLOGIC spa - TLK 38 - OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06519 - PAG. 11 Pollock Industries, Inc. toll-free 1-866-665-5434 (603) 888-2467 sales@electracool.com...
  • Page 12 Measurement range: according to the used probe (see range table) TLK 38 PASSWORD = 381 Display resolution: according to the probe used 1/0,1/0,01/0,001 TECNOLOGIC spa - TLK 38 - OPERATING INSTRUCTIONS - Vr. 03 - ISTR 06519 - PAG. 12 Pollock Industries, Inc. toll-free 1-866-665-5434 (603) 888-2467 sales@electracool.com...