TABLE OF CONTENTS GENERAL INFORMATION .....................................3 Overview .........................................3 Purpose of the Manual ..................................3 Symbols Contained in this Manual ...............................3 Retention of Documents ..................................3 Updates ........................................3 Technical Features ....................................3 Cooling Unit Application ..................................3 1.7.1 Intended Use ....................................3 1.7.2 Misuse ......................................3 TECHNICAL INFORMATION ..................................3 Operating Principles ....................................3 Safety Devices .......................................3 SUPPLY ..........................................4...
1. GENERAL INFORMATION If these requirements are not respected, excessive condensation build-up may occur. As a consequence, cable entry points or any WARNING: Read the following instructions carefully before other openings in the enclosure should be well sealed. installing and using the product. •...
The refrigeration circuit is fitted with an EN 12263 compliant If the cooling unit is to be installed on the door of an electrical high-pressure safety switch P (figure F.12) set to the maximum switchboard, make sure the door can take the weight. working pressure of the cooling unit.
7.1 Two-Phase Models reaches the set point. The thermostat is factory-set to 35°C. The setpoint can be set between 20°C and 45°C. The two-phase models can operate with two different supply Notice: To save energy and minimise the production of voltages: 460 V 2~50–60 Hz and 400 V 2~50–60 Hz. If the condensate, we recommend not setting the setpoint below 30°C.
11. TROUBLESHOOTING Malfunction Conditions Causes Remedy It fails to cool The internal fan works, the The temperature inside the enclosure is This is not a malfunction of the cooling unit. To external fan and compressor lower than what is set on the adjustment verify functioning when testing, lower the thermostat do not work.
Page 13
14. PERFORMANCES F.21 NXT20 NXT30 NXT40 NXT60 P (W) Ta (°C) Ti (°C) Useful cooling output Ambient temperature Enclosure internal temperature nVent.com/HOFFMAN...
16. SPARE PARTS F.23 NXT04 NXT06-08 1. Front structure 4. Compressor 7. Electric Control 10. Autotransformer 2. Condenser 5. Condenser fan 8. Display 11. Assembly accessory kit 3. Evaporator 6. Evaporator fan 9. Electronic Board When ordering the following informations are essential: Model, Serial number, Date of production, Requested parts’ code nVent.com/HOFFMAN...
Page 17
16. SPARE PARTS F.23 NXT10 NXT12-16-20 1. Front structure 4. Compressor 7. Electric Control 10. Autotransformer 2. Condenser 5. Condenser fan 8. Display 11. Assembly accessory kit 3. Evaporator 6. Evaporator fan 9. Electronic Board When ordering the following informations are essential: Model, Serial number, Date of production, Requested parts’ code nVent.com/HOFFMAN...
Page 18
16. SPARE PARTS F.23 NXT30-40 NXT60 10. Autotransformer 1. Front structure 4. Compressor 7. Electric Control 11. Assembly accessory 2. Condenser 5. Condenser fan 8. Display 3. Evaporator 6. Evaporator fan 9. Electronic Board When ordering the following informations are essential: Model, Serial number, Date of production, Requested parts’ code nVent.com/HOFFMAN...
17. GUARANTEE 18. ASSISTANCE SERVICE TEXA INDUSTRIES S.r.l. guarantees its product free from quality Assistance Service For machine malfunctions, technical defects. It also guarantees for 12 months all the product’s information or advice on installation, please contact Assistance components starting from the date of shipment and when they Service at: TEXA INDUSTRIES S.r.l.
Need help?
Do you have a question about the NXT10B0E0C00000 and is the answer not in the manual?
Questions and answers