HB22 Heater Breakdown Detector (For Phase-Control Circuit)
Thank you for purchasing the Shimaden HB22 Heater Breakdown Detector. Please ensure that this
manual is delivered to the end user and read for safety before use.
Introduction
This instruction manual is meant for those who will be involved in wiring, installation, operation and routine maintenance of the HB22.
As this manual describes matters to be attended to in its operation, wiring and installation, you are requested to keep this manual at your work
site when using the apparatus. You are also requested to follow the instructions provided herein.
For matters concerning safety, potential damage to equipment and facilities, additional explanation and instructions are given under the
following heading:
WARNING
This heading indicates that failure to follow instructions could cause injury or even death.
CAUTION
This heading indicates that failure to follow instructions could cause damage to equipment and/or facilities.
1. This apparatus must be housed, for example, in a control box to prevent the terminal board from coming into accidental physical
contact with personnel.
2. Wiring should be carried out without energizing the apparatus. Otherwise, an electric shock is probable.
3. Once wired, do not touch the terminals or other charged parts while they are energized.
1. The alert mark on the plate affixed to the apparatus:
On the nameplate affixed to the case of the apparatus, the alert mark is printed. This is to warn you of an electric shock which may
result if the charger is touched while it is energized.
2. A means to turn power off, a switch or a breaker, should be installed in the external power circuit to be connected to the power
terminals of this apparatus.
3. Note on Fuse
This apparatus has no built-in fuse. Install a fuse in the power circuit to be connected to the power terminals. (0.5A, normal blow type)
4. In wiring, terminal connectors should be fastened properly.
5. Use power voltage and a frequency respectively within the ranges of their ratings.
6. Do not apply voltage and current which are out of the ranges of their ratings to the input terminals. Such an act may shorten the life of
the product or cause trouble with the apparatus.
7. In case the system is equipped with output terminals, current and voltage of a load to be connected to the output terminals should be
within the ranges of their ratings. If their ratings are exceeded, a rise in temperature may shorten the life of the product or cause
trouble with the apparatus.
8. Be sure to cut the power supply OFF before pulling the apparatus out of its surface socket. Especially in case of using with an external
CT, CT may be burnt out by pulling it out.
9. Users are prohibited from remodeling the apparatus or using it in an unauthorized manner.
10. You are requested to adhere to the matters to be attended to as described in the instruction manual in order to use the apparatus
safely and correctly and to maintain its reliability.
1. Specifications
Model:
Power supply:
Rated control voltage (Heater voltage):
Rated frequency:
Operation current:
Continuous allowable current:
Setting range:
Sensitivity:
Operation time:
Effect of fluctuation of input voltage:
Alarm action output:
Contact capacity:
Alarm action display:
Operating ambient temperature/humidity: -10 to 50 ℃/90% RH max. (No dew condensation allowed.)
Temperature when kept unused:
Insulation resistance:
Dielectric strength:
Material:
External dimensions
Mounting:
Weight:
Note:
This apparatus is designed for single-phase circuits, that is, unusable for 3-phase circuits.
In case if it is used for a heater of which the amperage exceeds 5A, a CT (current detector) should be installed externally.
Instruction Manual
WARNING
CAUTION
HB22
100 to 240V AC ±10% 50/60Hz
100, 110, 120, 200, 220, 240 V AC (Either one to be selected.)
50/60 Hz
0.5 to 5A AC (Depends on the external CT when the operating current is more than 5A.)
7A AC
10 to 100% (0.5 to 5A: When input voltage is rated value)
Approx. 3% of the current setting value (When input voltage is rated value)
0.5 sec. Max.(In case of the current changes from 150% to 0% of the operating value)
±5% FS or less of the theoretical value on operating current value with the rated voltage
(In a range from 20% to 110% of the input voltage)
Relay contact (1c/SPDT)
240 V AC, 2A (Resisitive load)
Red LED lamp is on during alarm action.
-20 to 65
℃
500V DC
100MΩ
Min. between each terminal of the power supply-heater voltage-heater current-alarm output.
1 min. at 1500V AC between each terminal of the power supply-heater voltage-heater current-alarm output.
ABS resin molding.
H83.5×W50×D146.5mm (including socket terminal block)
11P plug-in panel or DIN rail
Approx. 190g
MHB22-E01-A
Sep. 2024