CONTENTS Part 1. GENERAL INFORMATION ............1 1. Model lineup ....................2 1-1. Indoor unit connection patterns..................4 2. Optional parts .....................11 2-1. Controllers ........................11 2-2. Cassette grille ........................14 2-3. Others ..........................15 3. Indoor unit installation precautions ............21 3-1. Places where prohibited for use..................21 3-2.
1. Model lineup Refer to the following tables for the multi-split outdoor unit and the connectable indoor units. For the indoor unit's technical information, refer to the Design & Technical Manual for the multi-split indoor units. ●: Connectable, —: Not connectable Standard climate region Outdoor unit 2-unit...
Page 9
●: Connectable, —: Not connectable Cold climate region Outdoor unit 2-unit 3-unit 4-unit Indoor unit Type Model AOUH18KWAH2 AOUH24KWAH3 AOUH36KWAH4 ACUH07KUAS ● ● ● ACUH09KUAS ● ● ● Compact cassette ACUH12KUAS ● ● ● ACUH18KUAS — ● ● ADUH07KUAS ● ●...
1-1. Indoor unit connection patterns Refer to the following table for the combinations of indoor unit capacities connected to each outdoor unit. The indoor units are connectable up to 130% of the outdoor unit capacity. 2-unit multi-split outdoor unit: AOUH18KWAS2 or AOUH18KWAH2 Indoor unit Total Combination...
Page 11
4-unit multi-split outdoor unit: AOUH36KWAS4 or AOUH36KWAH4 Indoor unit Total Combination Unit 1 Unit 2 Unit 3 Unit 4 (kBtu class) — — — — — — — — — — — — — — — — — — — —...
Page 12
4-unit multi-split outdoor unit: AOUH36KWAS4 or AOUH36KWAH4 Indoor unit Total Combination Unit 1 Unit 2 Unit 3 Unit 4 (kBtu class) NOTE: Up to 2 units of Middle duct are connectable to the combination. However, if the combina- tion contains Middle ducts, the maximum connectable unit number will be up to 3. - 6 - 1-1.
Page 13
5-unit multi-split outdoor unit: AOUH45KWAS5 Indoor unit Total Combination Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 (kBtu class) — — — — — — — — — — — — — — — — — — — —...
Page 14
5-unit multi-split outdoor unit: AOUH45KWAS5 Indoor unit Total Combination Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 (kBtu class) — — — — — — — — — — — — — — — — — — — —...
Page 15
5-unit multi-split outdoor unit: AOUH45KWAS5 Indoor unit Total Combination Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 (kBtu class) — — — — — — — — — - 9 - 1-1. Indoor unit connection patterns 1. Model lineup...
Page 16
5-unit multi-split outdoor unit: AOUH45KWAS5 Indoor unit Total Combination Unit 1 Unit 2 Unit 3 Unit 4 Unit 5 (kBtu class) NOTE: If the combination contains 1 unit of Middle duct, the maximum connectable unit number will be up to 4. If the combination contains 2 units of Middle duct, the maximum connectable unit number will be up to 3.
2. Optional parts 2-1. Controllers ¢ Lineup ●: Accessory, ◌: Optional, —: Not applicable Type Wireless Remote Controller Indoor unit type UTY-LNTU AR-RRH1U AR-RRH2U AR-REJ1U* Compact cassette ◌ — — — Slim duct — ◌ — — Middle duct — ◌...
Page 18
¢ Parts Exterior Part name Model name Summary Remote controller that provides the functions you need in a sleek design that uniquely transforms itself to blend with any interior. NOTE: When this remote controller is connected to a wall- mounted type indoor unit, wireless remote controller cannot be used.
Page 19
Exterior Part name Model name Summary Compact remote controller concentrates on the basic functions such as Start/Stop, fan control, and temperature setting. Simple Remote UTY-RHRY Connecting point Controller • For other than wall mounted type: Terminal block (Y1 and Y2) •...
2-2. Cassette grille ¢ Lineup Indoor unit type Model Compact cassette UTG-CCGFGA ¢ Parts Exterior Part name Model name Summary This cassette grille can be installed Cassette Grille UTG-CCGFGA appropriately on the grid type ceiling common in the office. - 14 - 2-2.
2-3. Others ¢ Lineup ●: Accessory, ◌: Optional, —: Not applicable Type External Input and Output PCB Indoor unit type External Input and Output PCB UTY-XCSX UTY-XCSXZ2 UTZ-GXEA UTZ-GXNA Compact cassette ◌ — ◌ — Slim duct ◌ — ◌ —...
Page 22
Type Fresh Air Intake Indoor unit type Auto Louver Grille Kit UTZ-VXAA UTD-GXTA-W UTD-GXTB-W UTD-GXTC-W Compact cassette ◌ — — — 07-12 models — ◌ — — Slim duct 18 model — — ◌ — 24 model — — — ◌...
Page 23
¢ Parts Exterior Part name Model name Summary Thermo-sensor for sensing the Remote Sensor temperature of arbitrary place in the UTY-XSZXZ* Unit room. Connecting point: CN8 on Main PCB Width: 26-7/8 in (683 mm) Auto Louver UTD-GXTA-W Grille Kit (For 07, 09, and 12 models) Width: 34-3/4 in (883 mm) Auto Louver UTD-GXTB-W...
Page 24
Exterior Part name Model name Summary By attaching Fresh Air Intake Kit to the indoor unit, it can be taken in fresh air of up to 10% of “high” air volume of Fresh Air Intake the indoor unit. UTZ-VXAA Do not branch the connecting duct into multiple rooms.
Page 25
UART interface and a KNX open KNX Convertor UTY-VKSX network. Connecting point: CN65 or CN75 on Main PCB This converter can control Fujitsu General products using a third-party thermostat controller. Optional Communication Kit is necessary for installation. Thermostat Connecting point...
Page 26
NOTE: Combined use of following optional parts and WLAN Adapter is not allowed. • External Input and Output PCB (UTY-XCSX) • External Input and Output PCB (UTY-XCSXZ2) • Modbus Converter • KNX Convertor - 20 - 2-3. Others 2. Optional parts...
3. Indoor unit installation precautions NOTE: The information listed below are general precautions. Some models also include items that do not apply. 3-1. Places where prohibited for use • Places where there is a danger of combustible gas leakage. • Places where sulfur gas, chlorine gas, acid, alkali, or other matter which effects equipment is gen- erated.
Page 28
Condition Contents Countermeasures (Reference) When inside the When the indoor unit is installed where the inside of the 1. Add heat insulating material to ceiling is high ceiling is 86 °F (30 °C) RH80% or greater, the dew point the outside of the indoor unit temperature temperature of the outer perimeter may become higher cabinet.
Page 29
Condition which requires addition of outside heat insulation Relative humidity 80 % Dry bulb temperature 86 °F (30 °C) Figure 3-1 Moist air curve Slit of heat insulating material Heat insulation reinforcement material Flare connection facing upward (locally purchased) To indoor unit Covered gas pipe (heat insulation...
4. Outdoor unit installation precautions NOTE: The information listed below are general precautions. Some models also include items that do not apply. 4-1. Places where prohibited for use • Places where there is a danger of combustible gas leakage. • Places where sulfur gas, chlorine gas, acid, alkali, or other matter which effects equipment is gen- erated.
1. Specifications Type Inverter, Heat pump Model name AOUH18KWAS2 Power supply 1Ø, 208/230 V~ 60 Hz Power supply intake Outdoor unit Available voltage range 187—253 V Min. Number Max. Connectable indoor unit Min. 14,000 Total capacity Btu/h range Max. 24,000 Wall mounted Duct Standard combination of indoor unit...
Page 33
Type Inverter, Heat pump Model name AOUH18KWAS2 NOTES: • Specifications are based on the following conditions: – Cooling: Indoor temperature of 80°FDB (26.7°CDB)/67°FWB (19.4°CWB), and outdoor temperature of 95 °FDB (35°CDB)/75°FWB (23.9°CWB). – Heating: Indoor temperature of 70°FDB (21.1°CDB)/60°FWB (15.6°CWB), and outdoor temperature of 47 °FDB (8.3°CDB)/43°FWB (6.1°CWB). –...
Page 34
Type Inverter, Heat pump Model name AOUH24KWAS3 Power supply 1Ø, 208/230 V~ 60 Hz Power supply intake Outdoor unit Available voltage range 187—253 V Min. Number Max. Connectable indoor unit Min. 14,000 Total capacity Btu/h range Max. 31,000 Wall mounted Duct ASUH07KPAS ×...
Page 35
Type Inverter, Heat pump Model name AOUH24KWAS3 Material Low-density polyethylene Drain hose Tip diameter in (mm) I.D.: Ø1/2 (Ø13.0), O.D.: Ø5/8 to Ø11/16 (Ø16.0 to Ø16.7) NOTES: • Specifications are based on the following conditions: – Cooling: Indoor temperature of 80°FDB (26.7°CDB)/67°FWB (19.4°CWB), and outdoor temperature of 95 °FDB (35°CDB)/75°FWB (23.9°CWB). –...
Page 36
Type Inverter, Heat pump Model name AOUH36KWAS4 Power supply 1Ø, 208/230 V~ 60 Hz Power supply intake Outdoor unit Available voltage range 187—253 V Min. Number Max. Connectable indoor unit Min. 25,000 Total capacity Btu/h range Max. 46,000 Wall mounted Duct Standard combination of indoor unit Mixed...
Page 37
Type Inverter, Heat pump Model name AOUH36KWAS4 Cooling 14 to 122 (-10 to 50) Operation range °F (°C) Heating 5 to 75 (-15 to 24) Material Low-density polyethylene Drain hose Tip diameter in (mm) I.D.: Ø1/2 (Ø13.0), O.D.: Ø5/8 to Ø11/16 (Ø16.0 to Ø16.7) NOTES: •...
Page 38
Type Inverter, Heat pump Model name AOUH45KWAS5 Power supply 1Ø, 208/230 V~ 60 Hz Power supply intake Outdoor unit Available voltage range 187—253 V Min. Number Max. Connectable indoor unit Min. 34,000 Total capacity Btu/h range Max. 58,000 Wall mounted Duct Standard combination of indoor unit Mixed...
Page 39
Type Inverter, Heat pump Model name AOUH45KWAS5 Cooling 14 to 122 (-10 to 50) Operation range °F (°C) Heating 5 to 75 (-15 to 24) Material Low-density polyethylene Drain hose Tip diameter in (mm) I.D.: Ø1/2 (Ø13.0), O.D.: Ø5/8 to Ø11/16 (Ø16.0 to Ø16.7) NOTES: •...
3. Installation space 3-1. Models: AOUH18KWAS2, AOUH24KWAS3, and AOUH36KWAS4 ¢ Space requirement Provide sufficient installation space for product safety. CAUTION Keep the space shown in the installation examples. If the installation is not performed accordingly, it could cause a short circuit and result in a lack of operating performance.
Multiple outdoor unit installation • Provide at least 10 in (250 mm) of space between the outdoor units if multiple units are in- stalled. • When routing the piping from the side of an outdoor unit, provide space for piping. •...
Outdoor units installation in multi-row Unit: in (mm) Single parallel unit arrangement Multiple parallel unit arrangement 4 (100) or more 8 (200) or more 40 (1,000) 80 (2,000) or more or more 8 (200) or more 16 (400) or more 20 (500) or more 40 (1,000) or more 8 (200) or more...
3-2. Model: AOUH45KWAS5 ¢ Space requirement Provide sufficient installation space for product safety. CAUTION Keep the space shown in the installation examples. If the installation is not performed accordingly, it could cause a short circuit and result in a lack of operating performance.
Page 48
Multiple outdoor unit installation • Provide at least 250 mm of space between the outdoor units if multiple units are installed. • When routing the piping from the side of an outdoor unit, provide space for piping. • No more than 3 units must be installed side by side. When 4 units or more are arranged in a line, provide the space as shown in the following ex- ample “When an obstruction in the upper space:”.
Outdoor unit installation in multi-row Unit: in (mm) Single parallel unit arrangement Multiple parallel unit arrangement 6 (150) or more 20 (500) or more 119 (3,000) or more 138 (3,500) or more 24 (600) or more 24 (600) or more 60 (1,500) or more 60 (1,500) or more NOTES:...
6. Capacity table 6-1. Combinations ¢ Model: AOUH18KWAS2 • Connectable up to 130% of the outdoor unit capacity. • Up to 1 unit of Middle duct is connectable to the combination. • Specifications are based on the following conditions: – Power source of specifications: 230 V –...
Page 57
AOUH18KWAS2, Ducted Rated capacity for each in- Max. capacity for each in- Total capacity Combination of indoor unit Input power (kW) door unit (kBtu/h) door unit (kBtu/h) (kBtu/h) Unit Unit Unit Total Min. Rated Max. Min. Rated Max. 9.20 9.20 10.35 10.35 6.80...
Page 58
¢ Model: AOUH24KWAS3 • Connectable up to 130% of the outdoor unit capacity. • Up to 1 unit of Middle duct is connectable to the combination. • Specifications are based on the following conditions: – Power source of specifications: 230 V –...
Page 59
Heating AOUH24KWAS3, Non-ducted Rated capacity for each indoor Max. capacity for each indoor Total capacity Combination of indoor unit Input power (kW) unit (kBtu/h) unit (kBtu/h) (kBtu/h) Unit Unit Unit Total Min. Rated Max. Min. Rated Max. — 9.40 9.40 —...
Page 60
¢ Model: AOUH36KWAS4 • Connectable up to 130% of the outdoor unit capacity. • Up to 2 units of Middle duct are connectable to the combination. However, if the combination con- tains Middle ducts, the maximum connectable unit number will be up to 3. •...
Page 61
AOUH36KWAS4, Non-ducted Rated capacity for each indoor unit Max. capacity for each indoor unit Total capacity Combination of indoor unit Input power (kW) (kBtu/h) (kBtu/h) (kBtu/h) Unit Unit Unit Total Min. Rated Max. Min. Rated Max. 6.34 6.34 8.14 13.58 7.00 7.00 9.00...
Page 62
AOUH36KWAS4, Ducted Rated capacity for each indoor unit Max. capacity for each indoor unit Total capacity Combination of indoor unit Input power (kW) (kBtu/h) (kBtu/h) (kBtu/h) Unit Unit Unit Total Min. Rated Max. Min. Rated Max. — — 6.68 22.92 —...
Page 63
Heating AOUH36KWAS4, Non-ducted Rated capacity for each indoor unit Max. capacity for each indoor unit Total capacity Combination of indoor unit Input power (kW) (kBtu/h) (kBtu/h) (kBtu/h) Unit Unit Unit Total Min. Rated Max. Min. Rated Max. — — 7.07 24.23 —...
Page 64
AOUH36KWAS4, Ducted Rated capacity for each indoor unit Max. capacity for each indoor unit Total capacity Combination of indoor unit Input power (kW) (kBtu/h) (kBtu/h) (kBtu/h) Unit Unit Unit Total Min. Rated Max. Min. Rated Max. — — 7.07 24.23 —...
Page 65
¢ Model: AOUH45KWAS5 • Connectable up to 130% of the outdoor unit capacity. • If the combination contains 1 unit of Middle duct, the maximum connectable unit number will be up to 4. If the combination contains 2 units of Middle duct, the maximum connectable unit number will be up to 3.
Page 66
AOUH45KWAS5, Non-ducted Rated capacity for each indoor unit Max. capacity for each indoor unit Total capacity Input power Combination of indoor unit (kBtu/h) (kBtu/h) (kBtu/h) (kW) Unit Unit Unit Total Min. Rated Max. Min. Rated Max. — 6.40 6.40 8.23 21.96 —...
Page 67
AOUH45KWAS5, Non-ducted Rated capacity for each indoor unit Max. capacity for each indoor unit Total capacity Input power Combination of indoor unit (kBtu/h) (kBtu/h) (kBtu/h) (kW) Unit Unit Unit Total Min. Rated Max. Min. Rated Max. 5.68 5.68 7.30 9.74 14.60 6.34 6.34...
Page 68
AOUH45KWAS5, Ducted Rated capacity for each indoor unit Max. capacity for each indoor unit Total capacity Input power Combination of indoor unit (kBtu/h) (kBtu/h) (kBtu/h) (kW) Unit Unit Unit Total Min. Rated Max. Min. Rated Max. — — — 12.00 24.00 —...
Page 69
AOUH45KWAS5, Ducted Rated capacity for each indoor unit Max. capacity for each indoor unit Total capacity Input power Combination of indoor unit (kBtu/h) (kBtu/h) (kBtu/h) (kW) Unit Unit Unit Total Min. Rated Max. Min. Rated Max. 6.14 7.90 7.90 10.53 10.53 6.86 8.82...
Page 70
Heating AOUH45KWAS5, Non-ducted Rated capacity for each indoor unit Max. capacity for each indoor unit Total capacity Input power Combination of indoor unit (kBtu/h) (kBtu/h) (kBtu/h) (kW) Unit Unit Unit Total Min. Rated Max. Min. Rated Max. — — —...
Page 71
AOUH45KWAS5, Non-ducted Rated capacity for each indoor unit Max. capacity for each indoor unit Total capacity Input power Combination of indoor unit (kBtu/h) (kBtu/h) (kBtu/h) (kW) Unit Unit Unit Total Min. Rated Max. Min. Rated Max. — 5.79 12.41 14.90 14.90 —...
Page 72
AOUH45KWAS5, Ducted Rated capacity for each indoor unit Max. capacity for each indoor unit Total capacity Input power Combination of indoor unit (kBtu/h) (kBtu/h) (kBtu/h) (kW) Unit Unit Unit Total Min. Rated Max. Min. Rated Max. — — — 12.27 24.53 —...
Page 73
AOUH45KWAS5, Ducted Rated capacity for each indoor unit Max. capacity for each indoor unit Total capacity Input power Combination of indoor unit (kBtu/h) (kBtu/h) (kBtu/h) (kW) Unit Unit Unit Total Min. Rated Max. Min. Rated Max. 6.57 8.45 8.45 11.27 11.27 7.71 9.92...
6-2. Cooling capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: AOUH18KWAS2 • TC: Total Capacity • IP: Input Power • Values mentioned in the table are based on the following conditions: – Power source of specifications: 230 V –...
Compact cassette type • TC: Total Capacity • SHC: Sensible Heat Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ACUH07KUAS Indoor temperature (°FDB / °FWB) 64 / 54...
Slim duct type • TC: Total Capacity • IP: Input Power • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ADUH07KUAS Indoor temperature (°FDB / °FWB) 64 / 54...
Page 81
Middle duct type • TC: Total Capacity • SHC: Sensible Heat Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ARUH12KUAS Indoor temperature (°FDB / °FWB) 64 / 54...
Wall mounted type • TC: Total Capacity • SHC: Sensible Heat Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ASUH07KPAS Indoor temperature (°FDB / °FWB) 64 / 54...
Page 84
¢ Model: AOUH24KWAS3 • TC: Total Capacity • IP: Input Power • Values mentioned in the table are based on the following conditions: – Power source of specifications: 230 V – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) •...
Compact cassette type • TC: Total Capacity • SHC: Sensible Heat Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ACUH07KUAS Indoor temperature (°FDB / °FWB) 64 / 54...
Slim duct type • TC: Total Capacity • SHC: Sensible Heat Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ADUH07KUAS Indoor temperature (°FDB / °FWB) 64 / 54...
Page 94
Middle duct type • TC: Total Capacity • SHC: Sensible Heat Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ARUH12KUAS Indoor temperature (°FDB / °FWB) 64 / 54...
Wall mounted type • TC: Total Capacity • SHC: Sensible Heat Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ASUH07KPAS Indoor temperature (°FDB / °FWB) 64 / 54...
Page 98
¢ Model: AOUH36KWAS4 • TC: Total Capacity • IP: Input Power • Values mentioned in the table are based on the following conditions: – Power source of specifications: 230 V – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) •...
Compact cassette type • TC: Total Capacity • SHC: Sensible Heat Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ACUH07KUAS Indoor temperature (°FDB / °FWB) 64 / 54...
Slim duct type • TC: Total Capacity • SHC: Sensible Heat Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ADUH07KUAS Indoor temperature (°FDB / °FWB) 64 / 54...
Page 111
Middle duct type • TC: Total Capacity • SHC: Sensible Heat Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ARUH12KUAS Indoor temperature (°FDB / °FWB) 64 / 54...
Wall mounted type • TC: Total Capacity • SHC: Sensible Heat Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ASUH07KPAS Indoor temperature (°FDB / °FWB) 64 / 54...
Page 116
¢ Model: AOUH45KWAS5 • TC: Total Capacity • IP: Input Power • Values mentioned in the table are based on the following conditions: – Power source of specifications: 230 V – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) •...
Compact cassette type • TC: Total Capacity • SHC: Sensible Heat Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ACUH07KUAS Indoor temperature (°FDB / °FWB) 64 / 54...
Slim duct type • TC: Total Capacity • SHC: Sensible Heat Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ADUH07KUAS Indoor temperature (°FDB / °FWB) 64 / 54...
Page 129
Middle duct type • TC: Total Capacity • SHC: Sensible Heat Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ARUH12KUAS Indoor temperature (°FDB / °FWB) 64 / 54...
Wall mounted type • TC: Total Capacity • SHC: Sensible Heat Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ASUH07KPAS Indoor temperature (°FDB / °FWB) 64 / 54...
6-3. Heating capacity NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Model: AOUH18KWAS2 • TC: Total Capacity • IP: Input Power • Values mentioned in the table are based on the following conditions: – Power source of specifications: 230 V –...
Compact cassette type • TC: Total Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ACUH07KUAS Indoor temperature (°FDB) Outdoor temperature °FDB...
Slim duct type • TC: Total Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ADUH07KUAS Indoor temperature (°FDB) Outdoor temperature °FDB...
Page 141
Middle duct type • TC: Total Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ARUH12KUAS Indoor temperature (°FDB) Outdoor temperature °FDB...
Page 142
Wall mounted type • TC: Total Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ASUH07KPAS Indoor temperature (°FDB) Outdoor temperature °FDB...
Page 144
¢ Model: AOUH24KWAS3 • TC: Total Capacity • IP: Input Power • Values mentioned in the table are based on the following conditions: – Power source of specifications: 230 V – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) •...
Page 149
Compact cassette type • TC: Total Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ACUH07KUAS Indoor temperature (°FDB) Outdoor temperature °FDB...
Page 151
Slim duct type • TC: Total Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ADUH07KUAS Indoor temperature (°FDB) Outdoor temperature °FDB...
Page 153
Middle duct type • TC: Total Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ARUH12KUAS Indoor temperature (°FDB) Outdoor temperature °FDB...
Page 154
Wall mounted type • TC: Total Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ASUH07KPAS Indoor temperature (°FDB) Outdoor temperature °FDB...
Page 157
¢ Model: AOUH36KWAS4 • TC: Total Capacity • IP: Input Power • Values mentioned in the table are based on the following conditions: – Power source of specifications: 230 V – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) •...
Compact cassette type • TC: Total Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ACUH07KUAS Indoor temperature (°FDB) Outdoor temperature °FDB...
Slim duct type • TC: Total Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ADUH07KUAS Indoor temperature (°FDB) Outdoor temperature °FDB...
Page 168
Middle duct type • TC: Total Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ARUH12KUAS Indoor temperature (°FDB) Outdoor temperature °FDB...
Wall mounted type • TC: Total Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ASUH07KPAS Indoor temperature (°FDB) Outdoor temperature °FDB...
Page 173
¢ Model: AOUH45KWAS5 • TC: Total Capacity • IP: Input Power • Values mentioned in the table are based on the following conditions: – Power source of specifications: 230 V – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) •...
Page 181
Compact cassette type • TC: Total Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ACUH07KUAS Indoor temperature (°FDB) Outdoor temperature °FDB...
Page 183
Slim duct type • TC: Total Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ADUH07KUAS Indoor temperature (°FDB) Outdoor temperature °FDB...
Page 186
Middle duct type • TC: Total Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ARUH12KUAS Indoor temperature (°FDB) Outdoor temperature °FDB...
Page 188
Wall mounted type • TC: Total Capacity • Values mentioned in the table are based on the following conditions: – Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.) Model: ASUH07KPAS Indoor temperature (°FDB) Outdoor temperature °FDB...
7. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 7-1. Model: AOUH18KWAS2 NOTE: Values mentioned in the table are calculated based on the maximum capacity.
7-2. Model: AOUH24KWAS3 NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Indoor unit: 7,000 Btu Pipe length COOLING — — — 0.956 0.942 0.928 Indoor unit is higher than — — 0.977 0.963 0.950 0.936 outdoor unit * —...
7-3. Model: AOUH36KWAS4 NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Indoor unit: 7,000 Btu Pipe length COOLING — — — 0.955 0.941 0.927 Indoor unit is higher than — — 0.976 0.962 0.949 0.935 outdoor unit * —...
7-4. Model: AOUH45KWAS5 NOTE: Values mentioned in the table are calculated based on the maximum capacity. ¢ Indoor unit: 7,000 Btu Pipe length COOLING — — — 0.955 0.941 0.927 Indoor unit is higher than — — 0.976 0.962 0.949 0.935 outdoor unit * —...
10-2. Sound level check point Rear Microphone Microphone Airflow 40 in (1 m) Side view Rear view NOTE: Detailed shape of the actual outdoor unit might be slightly different from the one illustrated above. - 204 - 10-2. Sound level check point 10.
11. Electrical characteristics Model name AOUH18KWAS2 AOUH24KWAS3 Voltage 208/230 Power supply Frequency 14.9 18.0 MCA* Starting current MAX. CKT. BKR* Power cable Wiring Size spec.* Connection Limited wiring cable* ft (m) 85 (26) length Model name AOUH36KWAS4 AOUH45KWAS5 Voltage 208/230 Power supply Frequency...
12. Safety devices Model Type of Protection form protection AOUH18KWAS2 AOUH24KWAS3 250 V, 10 A × 2 Circuit Current fuse (Main PCB*) 250 V, 3.15 A protection 250 V, 25 A 257 ±18°F (125 ±10°C) Activate Fan motor stop Fan motor Thermal protector protection 248 ±18°F (120 ±10°C)
13. Function settings Perform appropriate function setting locally according to the installation environment. NOTE: Incorrect settings can cause a product malfunction. CAUTION • Before setting up the switch buttons, discharge the static electricity from your body. • Never touch the terminals or the patterns on the parts that are mounted on the PCB. 13-1.
¢ Setting method Various settings can be adjusted by changing DIP switches and push switches on the PCB of the outdoor unit. LED display part POWER MONITOR ERROR /MODE ( GRN ) ( RED ) TEST RUN / SET 1 SET 2 CHECK PUMP DOWN...
¢ Description of display LED lamp Function or operation method • Turns on when the power supply is ON (Including when error occurs). (1) POWER/MODE Green • Indicate the MODE by the number of flashes when the installation function is active. (2) ERROR Flashes at high-speed when there is an error.
13-2. Outdoor unit low noise operation function Change the outdoor unit low noise operation by using this setting. CAUTION • When the low noise operation function is working, cooling and heating capacity will de- crease. • When changing the settings, explain to the customer beforehand that the capacity decreas- SET1-4 Setting Factory setting...
14. Check and test 14-1. Check run • The check run is a function to screen and detect any wiring errors. • After carrying out the check run, you can use the automatic wiring correction function to correct the wiring. •...
¢ Operating procedure for check run CAUTION Initiate check run after more than 12 hours after the power supply is connected. NOTE: Be sure that the indoor unit and outdoor unit are not operating before starting the check run. Press the CHECK switch for 3 seconds or more. CHECK The number of indoor units (and the places) connected through the communication lines is dis- played.
Page 219
After the check run is completed, results will be displayed. Fill the displayed results in the result table accordingly. • If the connection is correct (Example: When 4 indoor units are connected) After the number of connected units are displayed, the LED for each unit will light up in order from A to D.
Page 220
[How to record the contents] • Fill the displayed results according to the following example. Example: When piping A to D is connected but the wires for B and C are connected in reverse. <Displayed results> The LEDs will light up in 7 second intervals in the following order. POWER MONITOR ERROR...
Page 221
c. Select the correction method. Correct the wiring manually.*2 Proceed to step 6. Use the Automatic wiring correction function.*1 Proceed to step 5. Write down the same results in the label on the reverse side of the service panel. The results recorded are needed at the time of servicing. <Result Table>...
Page 222
¢ Failure indication of check-run judgment The check run stops when there is an error, and the LED shows the relevant error indication. When you encounter the errors described here, perform checking by using the cooling test run of the indoor unit.
14-2. Test run CAUTION Always connect the power supply 12 hours prior to the start of the operation in order to protect the compressor. 1. Indoor unit a. Is the drain normal? b. Is there any abnormal noise and vibration during operation? 2.
14-3. Error code If an error occurs, the LED lights to inform the relevant location and the code. When error occurs, the error LED blinks at high speed. POWER ERROR MONITOR /MODE ( GRN ) ( RED ) blink (High speed) ¢...
¢ Error code display While the error is occurring, briefly push the SW1. The error code is displayed. Example: Coil error (Error cord = 9A.1) POWER ERROR MONITOR /MODE ( GRN ) ( RED ) [A(10)] Blink (High speed) (9-blink) Display mode LED on: Blink:...
Page 226
Error code Error type 11.3 Serial communication error 11.4 Serial communication error during operation 16.5 Communication error between controller and outdoor unit 22.1 Indoor unit capacity error 23.1 Connection prohibited (Series error) 5U.1 Indoor unit error 62.1 PCB model information error 62.3 EEPROM access error 62.8...
14-4. Pump down WARNING During the pump down operation, make sure that compressor is off before you remove the refriger- ant pipe. Do not remove the connection pipe while the compressor is in operation with valve open. This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury. ¢...
Page 228
7. Disconnect the power supply or turn off the breaker. NOTE: • Even if the pump down operation is not stopped by pushing the switch as in step 6, the operation stops automatically after 15 minutes, and the LED light as fol- lows.
15. Accessories 15-1. Model: AOUH18KWAS2 Part name Exterior Part name Exterior Installation manual Cable tie Drain pipe Protection label Drain cap 15-2. Model: AOUH24KWAS3 Part name Exterior Part name Exterior Installation manual Cable tie Drain pipe Protection label Adapter K Drain cap 1/2 in (12.70 mm) to 3/8 in (9.52 mm)
15-4. Model: AOUH45KWAS5 Part name Exterior Part name Exterior Installation manual Protection label Adapter K Drain pipe 1/2 in (12.70 mm) to 3/8 in (9.52 mm) Adapter H Drain cap 3/8 in (9.52 mm) to 1/2 in (12.70 mm) Cable tie - 224 - 15-4.