THREE PHASE FOUR WIRE ENERGY METER
MID certified with Modbus output - 4 Mod. DIN
ENGLISH
DESDSDNN02 EN
0
0 /24
6
Art. 1SDSD10CET4MB
MID
COMPLETE INSTRUCTIONS
PERRY ELECTRIC Srl
Via Milanese, 11
22070 VENIANO (Como) ITALY
www.perry.it
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 1SDSD10CET4MB and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Perry Electric 1SDSD10CET4MB

  • Page 1 THREE PHASE FOUR WIRE ENERGY METER MID certified with Modbus output - 4 Mod. DIN ENGLISH Art. 1SDSD10CET4MB COMPLETE INSTRUCTIONS www.perry.it PERRY ELECTRIC Srl Via Milanese, 11 22070 VENIANO (Como) ITALY DESDSDNN02 EN 0 /24...
  • Page 2: Safety Instructions

    Safety Instructions Information for your own safety T h i s m a n u a l d o e s n o t c o n t a i n a l l o f t h e s a f e t y m e a s u r e s f o r o p e r a t i o n o f t h e equipment(module,device),because special operating conditions,and local code requirements or regulations may necessitate further measures.
  • Page 3: Part 1 Specification

    Introduction The digital 3 phase 4 wires energy meter with white back-lighted LCD screen for perfect reading. The unit measures and displays voltage, current, frequency, power factor, active power, reactive power, active energy and reactive energy, etc. A resettable partial energy is provided, so the user can easily check the active energy imported and active energy exported during a certain period.
  • Page 4 RS485 Serial - Modbus RTU This unit uses an RS485 serial port with Modbus RTU protocol to provide a means of remotely monitoring and controlling the Unit. Set-up screens are provided for setting up the RS485 port, see the configuration screens. Pulse output The unit provides pulse output for active kWh.
  • Page 5: Parte 2 Operation

    PARTE 2 Operation Keys and Displays Total indicator Communication icon Import indicator Total Export Min dmd indicator Resettable icon L1 L2 L3 Phase indication Activation buttons Digital numbers Pulse indicator light Description energy readings Buttons function There are two buttons on the front panel. Scroll the display for data-check “Scroll”...
  • Page 6: Scroll Display

    Scroll display After initialization and self-checking program, the meter displays the measured values. The default page is total kWh. If the user wants to check other information, please press the scroll button on the front panel. Total active energy Total=Import+ Export Resettable partial kWh Import energy Export energy...
  • Page 7 Voltage L3-N L1 current L2 current L3 current L1 active power L2 active power L3 active power Total active power L1 reactive power...
  • Page 8 L2 reactive power L3 reactive power Total reactive power L1 Power factor L2 Power factor L3 Power factor Total Power factor Frequency Pulse output type: Default: kWh Pulse constant: 1000imp...
  • Page 9 Modbus Address Baud Rate Parity Software version example...
  • Page 10: Accessing Settings

    Accessing settings When setting up the unit, password must be entered. Digits are set individually, from left to right. 1. Keep the button pressed for 3 seconds to access password entry. 2. The current digit to be set ashes and is set by using fl...
  • Page 11 Parity Option:NONE (N), EVEN (E),ODD (O) default:NONE Stop bit Option: 1, 2 default: 1 Pulse output type Option: kWh totali, Imp kWh, Exp kWh Default: kWh totali Pulse constant Option: 1000,100,10,1 imp/kWh Pulse width Option: 60, 100, 200, unit: ms Not : e If pulse constant is 1000imp/kWh,pulse width will be fixed...
  • Page 12: Wiring Diagram

    System tion : 3P4W,1P2W default: 3P4W Password default: 1000 Resettable partial energy Keep pressing button to exit the set-up mold. Wiring diagram Terminals Make sure that the 230V mains power supply is disconnected before proceeding with installation or maintenance. 3 phase 4 wire Terminals COMM/Pulse COMM/Pulse...
  • Page 13: Installation

    1 phase 2 wire Make sure that the 230V mains power supply is disconnected before proceeding with installation or maintenance. Terminals COMM/Pulse COMM/Pulse ÷ 1.5mm² 0.2Nm Load Load ÷ 25mm² 2.5Nm NOT : E Maximum Wire Size for Mainload: 25mm² Dimensions Installation The digital energy meter has to be installed in...
  • Page 14: Part 3 Modbus Protocol

    PART 3 Modbus Protocol Input registers are used to indicate the present values of the measured and calculated electrical quantities. Each parameter is held in two consecutive 16 big register. The following table details the 3X register address, and the values of the the address bytes within the message.
  • Page 15 30031 None Phase 1 power factor (1). Float 30033 None Phase 2 power factor (1). Float None 30035 Phase 3 power factor (1). Float 30043 Average line to neutral volts. Float 30047 Average line current. Float 30049 Sum of line currents. Float 30053 Total system power.
  • Page 16: Holding Registers

    Holding Registers Holding register are used to store and display instrument configuration settings. All holding registers not listed in the table below should be considered as reserved for manufacturer use and no attempt should be made to modify their values. The holding register parameters may be viewed or changed using the Modbus Protocol.
  • Page 17 Write the network port node Modbus Address: 1 to 247 default 1. 40021 Length : 4 byte Address Data Format : Float Option: 0 3, default 0 ÷ 0 :1000 imp/kWh 1 : 100 imp/kWh 2: 10 imp/kWh 3: 1 imp/kWh Pukse Note: If pulse output 40023...
  • Page 18 Serial number Numero di Length : 4 byte 464513 Data Format : unsigned int32 serie Note: Only read Meter code 1SDSD10CET4MB = 00 89 Codice Length : 2 byte 464515 unità Data Format : Hex Note: Only read The software showed on display XX.YY...
  • Page 20 Via Milanese, 11 - 22070 Veniano (CO) Italia Tel. +39.031.89441 Declare under our sole responsibility as manufacturer that the three phase active energy (kWh) indoor electricity meter 1SDSD10CET4MB with the measurement range 3x230/400V~, 0.5-10(100)A, 50Hz, 1000imp/kWh is in conformity with the type as described in the EU-type examination certificate...