Matsushima MWLM-PR26C Instruction Manual

Radar level transmitter

Advertisement

Quick Links

RADAR LEVEL TRANSMITTER
Safety precautions ······························································ 1
1.Overview ····································································· 2
2.Measurement principle···················································· 2
3.Specifications ······························································· 2
4.System configuration ······················································ 4
5.Dimensions ·································································· 5
6.Installation ···································································· 9
7.Wiring ········································································ 12
8.LCD adjustment unit ······················································ 13
9.Start-up ······································································ 13
10.Parameter setting ························································ 14
11.Troubleshooting ·························································· 21
12.Menu structure ··························································· 23
※The operator should read this Instruction Manual carefully and handle the
device correctly.
1-8-18 Norimatsu-Higashi,Yahatanishi-ku,Kitakyushu 807-0837 Japan
Phone No.(8193)691-3731 Fax No.(8193)691-3735
https://www.matsushima-m-tech.com
INSTRUCTION MANUAL
FOR
TYPE
MWLM-PR26C / MWLM-PR26H
Contents
TMWLM-008E
Rev5:May.08.2024

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MWLM-PR26C and is the answer not in the manual?

Questions and answers

Summary of Contents for Matsushima MWLM-PR26C

  • Page 1: Table Of Contents

    TMWLM-008E Rev5:May.08.2024 INSTRUCTION MANUAL RADAR LEVEL TRANSMITTER TYPE MWLM-PR26C / MWLM-PR26H Contents Safety precautions ······························································ 1 1.Overview ····································································· 2 2.Measurement principle···················································· 2 3.Specifications ······························································· 2 4.System configuration ······················································ 4 5.Dimensions ·································································· 5 6.Installation ···································································· 9 7.Wiring ········································································ 12 8.LCD adjustment unit ······················································ 13 9.Start-up ······································································...
  • Page 2: Safety Precautions

    Cause for any peripheral equipment or device. d. Accident beyond control and force majeure (fire, earthquake, flood, riots, etc.). Lack of instructions to MATSUSHIMA for information or safety requirements that can be predicted only by customers’ side. This warranty conditions do not limit customers’ legal right.
  • Page 3: 1.Overview

    The time difference between transmission and reception of microwave is processed by microcomputer to accurately determine level of stored materials. 3. Specifications Table1. Standard specification (For Liquid) Type MWLM-PR26C MWLM-PR26H Code MWLM-PR26C1G MWLM-PR26H1G MWLM-PR26H2G...
  • Page 4 Table2. Standard specification (For Powder) Type MWLM-PR26H Code MWLM-PR26H3G / F / S MWLM-PR26H7G / F / S Applications For powder Antenna Horn Power Supply (※1) DC 13 to 36V (When installing the LCD adjustment unit: 16V~36V) Power consumption 800mW G:G1 1/2 thread G:G1 1/2 thread F:JIS5K65A flange...
  • Page 5: 4.System Configuration

    4. System configuration This device is two wired which 4..20mA current output signal and power supply are carried on the same two wire cable. ・Power supply:DC 13 to 36V (When installing the LCD adjustment unit: 16V~36V) ・Output current signal:DC 4 to 20mA ・Load resistance:Max.
  • Page 6: 5.Dimensions

    Extension type with waveguide between Housing and Antenna, Antenna with dust cap etc.) suitably produced to the application environment. Accordingly there are some different cases from the undermentioned dimensions and shape. ●Liquid-1 Type MWLM-PR26C MWLM-PR26H Code MWLM-PR26C1G MWLM-PR26H1G Lead outlet G1/2 Lead outlet G1/2 Cable φ8~12mm...
  • Page 7 ●Liquid-2 Type MWLM-PR26H Code MWLM-PR26H2G MWLM-PR26H2F Lead outlet G1/2 Cable φ8~12mm Earth terminal(M4) Transparent window: PC Housing/Cover: ADC (82) JIS5K50A SUS304 Purge hole G1/8 Hex-head Measurement opposite side 50 reference point G1 1/2 PCD105 φ130 4-M4 Bolt Antenna: 4-φ19 Boss: SUS316L Mounting SUS304...
  • Page 8 ●Solid-1 Type MWLM-PR26H Code MWLM-PR26H3G MWLM-PR26H3S MWLM-PR26H3F Lead outlet G1/2 Cable φ8~12mm Earth terminal(M4) Transparent window: PC Housing/Cover: ADC (82) Max.10° Max.10° JIS10K100A flange with Swivelling mechanism SUS304 Hex-head JIS5K65A opposite side SUS304 Purge hole Measurement G1/8 reference point G1 1/2 PCD130 PCD175 4-M4...
  • Page 9 ●Solid-2 Type MWLM-PR26H Code MWLM-PR26H7G MWLM-PR26H7S MWLM-PR26H7F Lead outlet G1/2 Cable φ8~12mm Earth terminal(M4) Transparent window: PC Housing/Cover: ADC (82) Max.10° Max.10° JIS10K100A JIS10K100A flange with SUS304 Hex-head Swivelling mechanism opposite Purge side 50 SUS304 hole Measurement G1/8 reference point G1 1/2 PCD175 PCD175...
  • Page 10: 6.Installation

    6. Installation 6-1. Installation φ98 φ45 Blind sector Blind sector 0.5m 0.3m Fig. 5. Installation for liquid and for solid ・ If material surface enter to the blind sector, a stand pipe shall be used to ensure that material surface can not reach the blind sector of the level meter.
  • Page 11 6-2. Mounting direction At the application with repose angle and the mounting position near the sidewall etc, the reflection Intensity of Level Meter may weaken or the noise reflection is likely to occur. As a countermeasure, the change of mounting direction can improve it in some cases. Level Meter has a marking at the reference position of electric field direction on Adapter.
  • Page 12 ・Provide shielding to minimize noise or unwanted reflections, when crossbeams, and other supports are installed within the tank. Fig. 10. Installation precaution (3) 【False reflections】 In environments where interfering signals are generated, level meter may indicate incorrect measurements results. False reflections up to a certain level of strength can be suppressed by executing the echo learning function.
  • Page 13: 7.Wiring

    7. Wiring Cover 7-1. Unscrew the cover. (Rotate counterclockwise) 7-2. If an optional LCD adj. unit is attached, remove it. (Rotate counterclockwise or to direction “OPEN"). 7-3. Open the wire entry of terminal block by pushing on the actuating lever with flat screwdriver. LCD adj.
  • Page 14: 8.Lcd Adjustment Unit

    * "LCD adj. unit" ,"Software for PC adjustment" and Ready to start "HART modem" are optional products. level measurement * For the error code details, please refer to “Instruction manual for LCD adjustment unit” and “Operating manual for adjustment Fig.17. Start - up software Matsushima DTM”.
  • Page 15: 10.Parameter Setting

    10. Parameter setting 10-1. Measurement span Sets measurement span corresponding to the process level of 100% and 0%. Distance: Distance from level meter measuring reference point to material surface 【Measurement screen】 1.000m is changed to Measurement range span 2.2 2.000m as an example. 1.Full setting 12.345m...
  • Page 16 10-2. Damping Sets time constant for the damping filter. The damping filter smooth the response to a sudden change in process level. This time can be set between 0 and 999 seconds. Keep in mind that the reaction time of the entire measurement will be longer and the sensor will react to measured value changes with a delay) 【Measurement screen】...
  • Page 17 10-3. Current output Selects the 4..20mA current output mode corresponding to the process level 0-100% and alarm current value. 【Measurement screen】 Current output set ’20-4mA’ is changed to 12.345m 1.Current output sel ‘4-20mA’as an example. =4-20mA 2.Alarm output sel Distance =Hold 3.Max current sel =20mA...
  • Page 18 10-4. Echo learning of false echo Sets mask to unwanted reflections (false echoes or noise echoes) being received from obstructions within a tank. Important:In most cases sets distance from level meter to unwanted reflections as echo learning distance. If there is true echo between the level meter and the masking distance, then echo learning distance shall be set as distance to true echo.
  • Page 19 Continued from previous page. + ×1 Echo learning 3.2.1 Distance = 2.00m Execution=- ×1 Echo learning 3.2.1 Selectable execution Distance = 2.00m 【Clear/Update/Addition】 It changes from the Execution=- display of "-" to the Clear: display of "Update". Deletes all echo learning data. +...
  • Page 20 10-5. Reset There are two reset options. Use "Measuring reset" to restart measurement without affecting parameters. Use "Parameter reset" to reset parameters to the default settings. Important:"Parameter reset" ・ Parameter reset returns various parameters to instrument default. Please take note of current settings before execute parameter reset.
  • Page 21 → + × Several-time ×1 Note: In this manual, only setup steps of the typical parameters have been described. Please refer to "Instruction manual for LCD adjustment unit" and "Operating manual for adjustment software Matsushima DTM" for other settings.
  • Page 22: 11.Troubleshooting

    (0% over) over)". Note: Error message No.13 to 16 will be displayed, only when appropriate settings are set to "Valid" by PC adjustment software Matsushima DTM. The default settings are "Invalid". If problem persists, please contact your local Matsushima sales office.
  • Page 23 Table 6. Periodic inspection Item Descriptions Interval (standard) ・Confirm whether there is damage on housing etc. Check of ・Tighten the cover and lead outlet Every 12 months appearance ・Tighten the bolt for installation fixture ・Clean the antenna (Solid: Inside,Liquid: Outside) Check of antenna Every 6 to 12 months Important: Standard periodic inspection interval differs depending on measurement...
  • Page 24: 12.Menu Structure

    12.Menu structure * All values shown here are parameter defaults. Main menu Menu Identification setting 1.Identification setting 1.Tag=SENSOR 2.Basic setting 2.Description=PULSE-RADAR 3.Sensor adjustment 3.Message=LEVEL METER 4.Graph display 4.Installation Day=2018/01/01 5.Self test 6.Reset 7.Current output test 1.1 Tag change 8.HART communication SENSOR 9.Sensor information 【Character input range】...
  • Page 25 PV = Distance SV = Level Distance TV = Level% QV = - 【It is not possible to set it.】 Sensor information Manufacturer = Matsushima Device type = MWLM-PR26 Serial number Firmware version = 2.00 Order number Factory adj.date = 2018/1/1 【Setting range】...