Page 2
SM_AHU(GA)_R410A_3D INV_US1_NB_2205 AIR HANDLER INVERTER SERIES SERVICE MANUAL...
Page 4
Table of Contents §. Safety Precautions Precautions Information servicing §. Model Reference & External Appearance Model Reference External Appearance §. Indoor Unit Indoor Unit - Air Handler Type §. Outdoor Unit Dimensional Drawings Service Space Capacity Correction Factor for Height Difference Noise Criterion Curves Refrigerant Cycle Diagrams Electrical Wiring Diagrams...
Page 5
Table of Contents §. Troubleshooting Safety Caution General Troubleshooting Outdoor Unit Point Check Function Information Inquiry Error Diagnosis and Troubleshooting Without Error Code Quick Maintenance by Error Code Troubleshooting by Error Code Check Procedures §. Indoor Unit Disassembly Indoor Unit - Air Handler Type §.
1. Precautions CAUTION • • To prevent personal injury, or property or unit damage, While unpacking be careful of sharp edges around adhere to all precautionary measures and instructions the unit as well as the edges of the fins on the con- denser and evaporator.
Page 9
2. Information servicing(For • Prior to work taking place, the area around the equipment is to be surveyed to make sure that there are no flammable flammable materials) hazards or ignition risks. • NO SMOKING signs shall be displayed. Checks to the area Ventilated area •...
Page 10
• that capacitors are discharged: this shall be done in shall also take into account the effects of aging or a safe manner to avoid possibility of sparking; continual vibration from sources such as compressors or fans. • that there no live electrical components and wiring are exposed while charging, recovering or purging 2.13 Detection of flammable refrigerants the system;...
• The refrigerant charge shall be recovered into the • Before attempting the procedure ensure that: correct recovery cylinders. The system shall be flushed • mechanical handling equipment is available, if with OFN to render the unit safe. This process may required, for handling refrigerant cylinders;...
Page 12
• Empty recovery cylinders are evacuated and, if • The recovered refrigerant shall be returned to the possible, cooled before recovery occurs. refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged. Do not • The recovery equipment shall be in good working mix refrigerants in recovery units and especially not in order with a set of instructions concerning the cylinders.
Model Reference Contents Model Reference ....................2 External Appearance .....................3...
Page 14
1. Model Reference Refer to the following table to determine the specific indoor and outdoor unit model number of your purchased equipment. Indoor Unit Model Outdoor Unit Model Capacity (Btu/h) Power Supply MOX330U-18HFN1-MR0 MVC-18HWFN1-M MOX430U-18HFN1-M MOD30-24HFN1-MW MVC-24HWFN1-M MOX430U-24HFN1-MR0 MOD30U-30HFN1-MR0 MVC-30HWFN1-M 1Ph, 208/230V~, MOD30U-30HFN1-MR0(X) 60Hz...
1. Feature Full Multi-position installation • This AHU is capable of upflow, downflow, horizontal left, or horizontal right configurations. Installation Convenience • It simplifies the airflow volume adjustment process and saves lots of installation efforts. The traditional adjustment method needs the installers to manually set the motor speed, according to the installation instruction and ducting design.
3. Part names coil compartment (Access panel Removed) Upflow drain pan Horizontal drain pan 4. Service Place MINIMUM CLEARANCE OF 25.4mm/1″ALL SIDES FLEXIBLE DUCT COLLAR IDU-Air Handler 4...
5. Accessories The air conditioning system comes with the following accessories. Use all of the installation parts and accessories to in- stall the air conditioner. Improper installation may result in water leakage, electrical shock and fire, or equipment failure. Name Shape Quantity Manual...
8. Noise Criterion Curves 1m/3.28ft 2m/6.56ft 1.5m/4.92ft Notes: -Sound measured at 1.5m/4.92ft away from the center of the unit. -Data is valid at free field condition -Data is valid at nominal operation condition -Reference acoustic pressure OdB = 20µPa -Sound level will vary depending on a range of factors such as the construction -(acoustic absorption coefficient) of particular room in which the equipment is installed.
9. Electrical Characteristics Capacity (Btu/h) Phase Power (indoor) Frequency And Volt 208/230V,60Hz Phase Power (Outdoor) Frequency And Volt 208/230V,60Hz Indoor unit(A) Max. Fuse Outdoor unit(A) Indoor unit Line quantity Line diameter(AWG) 16/1.5mm² 16/1.5mm² 16/1.5mm² Power line Outdoor unit Line quantity Line diameter(AWG) 14/2.5mm²...
Page 60
Capacity (Btu/h) 18k hyper Heat 24k hyper Heat 30k hyper Heat Phase Power (indoor) Frequency And Volt 208/230V,60Hz Phase Power (Outdoor) Frequency And Volt 208/230V,60Hz Indoor unit(A) Max. Fuse Outdoor unit(A) Indoor unit Line quantity Line diameter(AWG) 16/1.5mm² 16/1.5mm² 16/1.5mm² Power line Outdoor unit Line quantity...
10. Electrical Wiring Diagrams IDU Capacity (Btu/h) IDU Wiring Diagram 18k~60k 16023000011626 Abbreviation Paraphrase Yellow-Green Conductor Indoor Fan Capacitor Indoor Fan Motor Indoor ECM Motor TO CCM Comm.Bus Central Controller Indoor Room Temperature Sensor Indoor Coil Inlet Temperature Sensor Indoor Coil Outlet Temperature Sensor Indoor Coil Temperature Sensor ...
Page 63
10.1 Micro-Switch Introduce: A For ALARM terminal port CN33 1. Provide the terminal port to connect ALARM, but no voltage of the terminal port , the power from the ALARM system (not from the unit ) 2. Although design voltage can support higher voltage ,but we strongly ask you connect the power less than 24V, current less than 0.5A 3.
Page 64
B. For remote control (ON-OFF) terminal port CN2 and short connector of JR1 1. Remove the short connector of JR1 when you use ON-OFF function; 2. When remote switch off (OPEN); the unit would be off; 3. When remote switch on (CLOSE); the unit would be on; 4.
Page 65
10.2 Micro-Switch Introduce: FOR SETTING NETADDRESS S1+S2 CODE 0~15 16~31 32~47 48~63 NETADDRESS F A C T O R Y S E T T I N G A. Micro-switch S1 and dial-switch S2 are for address setting when you want to control this unit by a central controller. Range: 00-63 ENC1 CODE...
Page 66
The first group controls the electric SW2-1 heating to turn on the temperature 1°C(1.8°F) 2°C(3.6°F) difference Whether the electric heating is SW2-2 delayed Electric auxiliary heating delay start SW2-3 30min 15min time Compressor allowed to Electric heating allowed to Electric heating/compressor allow SW2-4 operate to low limit set by operate to high limit set by...
4. Noise Criterion Curves 1.0m/3.28ft Note: H= 0.5 × height of outdoor unit Notes: -Sound measured at 1.0m/3.25ft away from the center of the unit. -Data is valid at free field condition -Data is valid at nominal operation condition -Reference acoustic pressure OdB=20µPa -Sound level will vary depending on arrange off actors such as the construction (acoustic absorption coefficient) of particular room in which the equipment is installed.
Page 101
Outdoor unit printed circuit board diagram: 17122000044714, 17122000048121,17122000046453...
Page 102
Name Meaning Earth: connect to Ground N_in: connect to N-line (208-230V AC input) CN1A L_in: connect to L-line (208-230V AC input) CN16 S: connect to indoor unit communication HEAT1 CN17 connect to compressor heater, 208-230V AC when is ON 4-WAY CN60 connect to 4 way valve, 208-230V AC when is ON.
Page 103
Earth N-IN L-IN CN17 AC-FAN 4-WAY HEAT2 CN 60 R109 C515 CN 6 IC4 04 C 40 8 R403 E502 CN4 14 DC-FAN CN1 9 R4 04 C 517 C5 19 CN 18 R Y5 L2 01 IC401 E504 CN23 R8 02 R 804 C 40 2...
Page 104
Name Meaning Earth: connect to Ground Power Supply N_in: connect to N-line (208-230V AC input) L_in: connect to L-line (208-230V AC input) S: connect to indoor unit communication 4-WAY CN60 connect to 4 way valve, 208-230V AC when is ON. AC-FAN connect to AC fan HEAT2...
Page 105
Outdoor unit printed circuit board diagram: 17122000047742...
Page 106
Name Meaning CN11 N_in: connect to N-line (208-230V AC input) Power Supply CN12 L_in: connect to L-line (208-230V AC input) EEV-A CN16 EEV-B CN13 EEV-C EEV-D CN15 connect to electric expansion valve EEV-E EEV-F CN17 EEV-G CN14 connect to pipe temp. sensor T3, ambient temp. sensor T4, exhaust T3 T4 TP CN26 temp.
Page 107
Name Meaning HEAT_D CN20 connect to the heater, 208-230V AC when is ON CN21 HEAT_Y CN36 4-WAY CN38 connect to 4 way valve, 208-230V AC when is ON. CN27 connect to key board CN1 Note: This section is for reference only. Please take practicality as standard.
Page 108
Outdoor unit printed circuit board diagram: 17122000037804...
Page 109
Name Meaning L1_in: connect to L1-line (230V AC input) Power Supply L2_in: connect to L2-line (230V AC input) Exhaust temp. sensor TP TESTPORT CN35 used for testing HEAT1 CN19/CN20 connect to chassis heater, 208-230V AC when is ON HEAT2 CN24/CN25 connect to compressor heater, 208-230V AC when is ON 4-WAY CN17/CN18...
Page 110
Outdoor unit IPM board diagram: 17122000042012...
Page 111
Name Meaning connect to main board L-Out Power Supply connect to main board N-Out connect to main board CN6 FAN_DC FAN_1/FAN_2 connect to outdoor DC fan 1& DC fan 2 CN_COMP connect to compressor Note: This section is for reference only. Please take practicality as standard.
Page 112
Outdoor unit printed circuit board diagram: 17122000054047...
Page 113
Name Meaning connect to one-way solenoid valve connect to pressure sensor (5VDC) CN28 connect to electric expansion valve (12VDC) TESTPORT CN45 used for testing (5VDC) connect to suction temp. sensor, cold plate temp. sensor CN11 (5VDC) H-PRO CN38 connect to high pressure switch (5VDC) connect to main board L-Out Power Supply connect to main board N-Out...
1. Installation Overview Indoor Unit Indoor Unit Install the indoor unit Install the outdoor unit Install the drainpipe Evacuate the refrigeration system Connect the wires Connect the refrigerant pipes Install the panel Perform a test run (only for cassette type) ...
2. Location selection 2.1 Unit location selection can refer to installation manual. 2.2 DO NOT install the unit in the following locations: • Where oil drilling or fracking is taking place. • Coastal areas with high salt content in the air. •...
3. Indoor Unit Installation(AHU) Horizontal installation 3.1 Service space for indoor unit Horizontal installation Plenum Clearances: 24inch(min) MINIMUM CLEARANCE OF 25.4mm/1″ALL SIDES 3.2 Install the main body FLEXIBLE The unit may be installed in one of the upflow, downflow, DUCT COLLAR horizontal left or horizontal right orientations.
Page 118
For the Horizontal left installation and vertical down installation, the direction of the evaporator should be changed and the drain pan should be removed first. Please do it according to the following steps: 1. Remove the fixed plate of the filter ,then take the filter off.
Page 119
4. Unplug temperature sensors T1,T2,T2A,T2B and electronic expansion valve(EEV) from the control board. T1: Room temperature sensor T2: Evaporator central temperature sensor T2A: Evaporator input temperature sensor(only available for some models) T2B: Evaporator output temperature sensor(only available for some models) 7.
Page 120
Cut the foam gasket. Remove knockouts as 11. Reinstall evaporator cover plate. shown in the figure. Hook the wire into the buckle and go down from the wire slot. 12. Connect the wire according to the wiring diagram. Replace foam gaster over wires. 13.
Page 121
Installation must be performed by an authorized dealer or specialist. Please make necessary protection when installing the unit. Specification series of electric auxiliary heat module: 3kW,5kW,8kW,10kW, 15kw, 20kW,25kW. The electric auxiliary heat module is only used for installation on the AHU internal machine. If the unit needs to be equipped with electric auxiliary heat module, please check the electric auxiliary heat module specification that can be matched with the unit first to...
Page 122
3. Install the electric auxiliary heating assembly into the chassis shell from the front, and note that the front end needs to be inserted into the shell assembly hole. 4. Tighten the mounting screws. screws 2. Remove the terminal block and power cord, loosen the screws, and remove the electric auxiliary heating cover.
Page 123
9. After installing the electric auxiliary heat module, apply the circuit breaker label near the silicone breaker cover that was just applied. After the electric heating wiring is connected, please confirm before power on: • Check all wiring and ensure reliable connection of wire body.
4. Outdoor unit installation 4.3 Install Outdoor Unit Fix the outdoor unit with anchor bolts(M10) 4.1 Service space for outdoor unit >60cm / 23.6” Fix with bolts Caution Since the gravity center of the unit is not at its physical center, so please be careful when lifting it with a sling.
For Vertical drainage pipe (The following table is for 5. Drainage Pipe Installation reference) Install the drainage pipe as shown below and take Reference measures against condensation. Improperly installation Allowable value of inner could lead to leakage and eventually wet furniture and maximum water Remark pipe...
Page 127
5.3 Insulation work of drainage pipe Refer the introduction to the insulation engineering parts. • The correct installation will not cause converse water flow and the slope of the branch pipes can be adjusted freely • The false installation will cause converse water flow and the slope of the branch pipe can not be ad- justed.
2.Confirm the cross way of the pipes. 6. Refrigerant Pipe Installation 3.Measure the necessary pipe length. 6.1 Maximum length and drop height 4.Cut the selected pipe with pipe cutter Ensure that the length of the refrigerant pipe, the number • Make the section flat and smooth.
7. Vacuum Drying and Leakage 10. Set the wall conduit Checking 11. Set the supporter for the pipe. 12. Locate the pipe and fix it by supporter 7.1 Purpose of vacuum drying • For horizontal refrigerant pipe, the distance be- •...
4. Rain water might penetrate into pipeline during 8. Additional Refrigerant Charge construction. • After the vacuum drying process is carried out, the additional refrigerant charge process need to be performed. Procedures of special vacuum drying are as follows: • The outdoor unit is factory charged with refrigerant.
9 . Engineering of Insulation insulation and cause easy aging of the material. 9.2 Insulation of drainage pipe 9.1 Insulation of refrigerant pipe 1. Operational procedure of refrigerant pipe 1. Operational procedure of refrigerant pipe insulation insulation Select the suitable pipe → insulation (except joint section) Cut the suitable pipe →...
Page 132
2. Specific wiring method Engineering of Electrical Wring Connection method A: 1. Highlights of electrical wiring installation Refer to the wiring method of internal and external • All field wiring construction should be finished by machine communication and wired controller as follows: qualified electrician.
W1/E THERMOSTAT W1 W2 Y1 Y2 B W D INDOOR UNIT OUTDOOR UNIT THERMOSTAT W1 W2 Y1 Y2 B W D S4-1 DIP switch off INDOOR UNIT OUTDOOR UNIT Disconnect and short S4-2 DIP switch off S4-1 DIP switch off circuit to realize heating Perform disconnection and Disconnect and short...
Page 134
signal of DH changes to 0V, the cooling system starts the dehumidification operation, and the air volume drops to 80% of the nominal cooling air volume. When the partition control, DH is connected to the DH port of the partition controller. When the 24V signal of DH changes to 0V, the air volume drops to 80% of the nominal refrigeration air volume.
b. Remove the test cover. Add 2000ml of water to the tank 11. Test Operation through the attached tube. 1. The test operation must be carried c. Turn on the main power switch and run the air out after the entire installation has been conditioner in COOL mode.
Maintenance Contents First Time Installation Check .................2 Refrigerant Recharge ....................4 Re-Installation .......................5 Indoor Unit ....................5 Outdoor Unit ....................7...
1. First Time Installation Check Air and moisture trapped in the refrigerant system affects To prevent air and moisture from affecting the air the performance of the air conditioner by: conditioner’s performance, the indoor unit, as well as the pipes between the indoor and outdoor unit, must be be •...
Page 138
Procedure: • If the pressure successfully reaches -0.1 MPa Tighten the flare nuts of the indoor and outdoor (14.5 Psi), fully close the Handle Lo valve, then units, and confirm that both the 2- and 3-way valves cease vacuum pump operations. are closed.
2. Refrigerant Recharge mA A Procedure: Close both 2- and 3-way valves. 3-way valves. Slightly connect the Handle Lo charge hose to the Operate the air conditioner in cooling mode to charge 3-way service port. the system with liquid refrigerant. Connect the charge hose to the valve at the bottom When the electronic scale displays the correct of the cylinder.
3. Re-Installation Indoor Unit Collecting the refrigerant into the outdoor unit Procedure: Confirm that the 2- and 3-way valves are opened. Close the 3-way valve so that the gauge rests between 0.3 MPa (43.5 Psi) and 0.5 MPa (72.5 Psi). Connect the charge hose with the push pin of Handle Lo to the 3-way valve’s gas service port.
Page 141
Air purging with vacuum pump Procedure: Tighten the flare nuts of the indoor and outdoor • If the pressure successfully reaches -0.1 MPa (14.5 Psi), fully close the Handle Lo valve, then units, and confirm that both the 2- and 3-way valves cease vacuum pump operations.
Outdoor Unit Evacuation for the whole system Procedure: Wait for 5 minutes then check whether the gauge Confirm that the 2- and 3-way valves are opened. needle moves after turning off the vacuum pump. If Connect the vacuum pump to the 3-way valve’s the gauge needle moves backward, check whether service port.
Page 143
Refrigerant charging mA A Procedure: Close both 2- and 3-way valves. Fully open the Handle Lo manifold valve, 2- and 3-way valves. Slightly connect the Handle Lo charge hose to the 3-way service port. Operate the air conditioner in cooling mode to charge the system with liquid refrigerant.
Page 144
Product Features Contents Display Function ....................2 Safety Features ......................3 Basic Functions .......................3 Abbreviation ....................3 Fan Mode ......................3 Cooling Mode ....................3 Heating Mode(Heat Pump Units) ..............4 Auto Mode ....................5 Drying Mode ....................5 Forced Operation Function ................5 Timer Function ....................6 Sleep Function ....................6 3.10 Auto-Restart Function ..................6 Remote Controller Functions ................7 LCD Wired Remote Controller ...............7...
2. Safety Features Fan Mode Compressor three-minute delay at restart When fan mode is activated: Compressor functions are delayed for up to ten seconds • The outdoor fan and compressor are stopped. upon the first startup of the unit, and are delayed for up •...
• Descent curve compressor to cease operations. • When T1-Tsc is lower than or equal to 3.5°C, fan 3.4.2 Indoor Fan Control: speed reduces to high; 1) In heating mode, the indoor fan operates continuously. • When T1-Tsc is lower than or equal to 1°C, fan The fan speed can be set to low, medium, high,turbo speed reduces to medium;...
• The unit enters defrosting mode according to the fan-only mode on the basis of ∆T (∆T =T1-TS). temperature value of T3 and T4 as well as the ∆T Running mode compressor running time. ∆T>2°C(3.6°F) Cooling • In defrosting mode, the compressor continues to run, the indoor and outdoor motor will cease operation, -3℃(-5.4°F)<∆T≤2°C(3.6°F) Fan-only the defrost light of the indoor unit will turn on, and...
preset time. • Timer Off. The machine turns off automatically at the preset time. • Timer On/Off. The machine turns on automatically at the preset On Time, and then turns off automatically at the preset Off Time. • Timer Off/On. The machine turns off automatically at the preset Off Time and then turns on automatically at the preset On Time.
4. Remote Controller Functions LCD Wired Remote Controller- KJR-120X/TFBG-E(Standard) i) Buttons and Functions 1. POWER button 6. TIMER button Turn on of turn off the unit. To set timer on and timer off time of one day MODE button 7. FAN SPEED button Used to select the operation mode: Auto / Cooling / Drying / Used to select the fan speed.
Page 151
ii) LCD Screen 1 Operation mode indication 8 Sleep mode indication 2 Fan speed indication 9 Electric Auxiliary Heat/Turbo function indication(some models) 3 Temperature display NOTE: AHU models only have turbo functions. 4 Lock indication 10 Left-right swing indication (some models) 5 °C / °F indication 11 Clock display 6 Room temperature indication...
Page 152
iii) Installation • Dimensions 20mm 120mm 46mm 60mm 1) Connection • Wire with the indoor unit: 60mm Wiring hole HA HB • 1: Indoor Unit. • 2: Notch the part for the wiring to pass through with a nipper tool. •...
Page 153
For some models: The wired controller connects to terminal board, terminal board connects to main control board. Main control board Terminal board CN40 ENC1 HA HB HA HB Wired controller 2) Address setting Unit1 Unit2 Unit16 HA HB HA HB HA HB HA HB Wired controller...
Centralized Controller 1) Connection For Light commercial air conditioner with XYE port, it can be directly connected to Centralized Controller (CCM03, CCM09). 2) Address setting When setting the address, please make sure the unit is powered off. The address can be set from 0 to 63 by the switch. Turn on the unit, then the address will be effective.
Troubleshooting Contents Safety Caution .......................3 General Troubleshooting ..................4 Outdoor Unit Point Check Function ..............7 Information Inquiry ....................9 Error Diagnosis and Troubleshooting Without Error Code .......13 Remote maintenance ...................13 Field maintenance ..................14 Quick Maintenance by Error Code ..............19 Troubleshooting by Error Code ................21 EH 00 / EC 51 (EEPROM parameter error Diagnosis and Solution) ....21 EL 01 (Indoor and outdoor unit communication error Diagnosis and Solution) 22 EH 03 / EC 07 (Fan speed is operating outside of the normal range )/EC 71(Over...
Page 156
Troubleshooting Contents 7.11 PC 02 (Top temperature protection of compressor or High temperature protection of IPM module Diagnosis and Solution) ........34 7.12 EC 0d (Outdoor unit malfunction Diagnosis and Solution) ......35 7.13 PC 40(Communication error between outdoor main PCB and IPM board diagnosis and solution) ................36 7.14 PC 08(Current overload protection)/PC 44(Outdoor unit zero speed protection)/ PC 46(Compressor speed has been out of control)/PC 49(Compressor...
1. Safety Caution WARNING Be sure to turn off all power supplies or disconnect all wires to avoid electric shock. While checking indoor/outdoor PCB, please equip oneself with antistatic gloves or wrist strap to avoid damage to the board. WARNING Electricity remains in capacitors even when the power supply is off.
2. General Troubleshooting Error Display (Indoor Unit) When the indoor unit encounters a recognized error, the operation lamp will flash in a corresponding series, the timer lamp may turn on or begin flashing, and an error code will be displayed. These error codes are described in the following table: Display Error Information...
Page 159
Low pressure protection (for some models) TS33 PC 03 Outdoor unit malfunction TS35 ec 0 Low ambient temperature protection TS42 PC 0L Mismatch between the new and old platforms TS48 FL 09 For other errors: The display board may show a garbled code or a code undefined by the service manual. Ensure that this code is not a temperature reading.
Page 160
Error Display (For Some Outdoor Unit) Display Malfunction or Protection Solution Outdoor EEPROM malfunction TS21 EC 51 Indoor / outdoor units communication error TS22 EL 01 Communication malfunction between adapter board and outdoor main board TS48 EL 16 IPM module protection TS30 PC 00 Top temperature protection of compressor or High temperature protection of IPM module...
3. Outdoor Unit Point Check Function • A check switch is included on the outdoor PCB. • Push SW1 to check the unit’s status while running. The digital display shows the following codes each time the SW1 is pushed. Number of Display Remark Presses...
Page 162
Frequency limit caused by The display value is a Bit7 IGBT radiator hexidecimal number. For example, the Bit6 Reserved digital display show Bit5 Reserved 2A, then Bit5=1, Frequency limit caused by low Bit4 Bit3=1, and Bit1=1. temperature of T2.(LH00) Frequency limit caused by Frequency limit symbol Bit3 This means that a...
4. Information Inquiry • To enter engineer mode, in power-on or standby mode, and in non-locked state, press the key combination “ON/OFF + Air Speed” for 7s: • After entering the engineer mode, the remote control will display icons of “Auto, Cool, Dry, Heat”, and the Battery icon;...
Page 164
press "On/Off" for 2s to enter Twins Selector, the code displayed is “Ch”, Compressor press "OK" to send the Query Twins Selector code; press the Up/Down key to Running select, 0 indicates that there is no Twins, 1 indicates the host, and 2 indicates Frequency Fr the slave.
Page 165
press "On/Off" for 2s to enter the Cooling Temperature Compensation Value Settings, the code displayed is “Ch”, then press "OK" to send the Query Cooling Temperature Compensation Value code; press the Up/Down key to select the cooling temperature compensation value, then press "OK"; and press "On/Off"...
Page 166
Error code of engineer mode Display Error Information Indoor unit EEPROM parameter error EH 00 Indoor / outdoor unit communication error EL 01 Communication malfunction between adapter board and outdoor main board EL 16 The indoor fan speed is operating outside of the normal range EH 03 Outdoor unit EEPROM parameter error EC 51...
5. Error Diagnosis and Troubleshooting Without Error Code WARNING Be sure to turn off unit before any maintenance to prevent damage or injury. Remote maintenance SUGGESTION: When troubles occur, please check the following points with customers before field maintenance. Problem Solution Unit will not start TS15 - TS16...
Field maintenance Problem Solution Unit will not start TS17 - TS18 Compressor will not start but fans run TS17 - TS18 Compressor and condenser (outdoor) fan will not start TS17 - TS18 Evaporator (indoor) fan will not start TS17 - TS18 Condenser (Outdoor) fan will not start TS17 - TS18 Unit runs, but shortly stops...
Page 170
1.Remote Maintenance Others Possible causes of trouble Unit will not start ☆ The power switch is on but fans will not start The temperature on the display board cannot be set Unit is on but the wind is not cold(hot) Unit runs, but shortly stops ☆...
Page 171
Replace the compressor Compressor stuck Leak test Shortage of refrigerant Replace restricted part Restricted liquid line Clean or replace Dirty air filter Clean coil Dirty evaporator coil Check fan Insufficient air through evaporator coil Change charged refrigerant volume Overcharge of refrigerant Clean condenser or remove obstacle Dirty or partially blocked condenser Purge, evacuate and recharge...
Page 172
Test voltage Power failure Inspect fuse type & size Blown fuse or varistor Inspect connections - tighten Loose connections Test circuits with tester Shorted or broken wires Test continuity of safety device Safety device opens Test continuity of thermostat / sensor & wiring Faulty thermostat / room temperature sensor Place the temperature sensor at the central of the air inlet Wrong setting place of temperature sensor...
6. Quick Maintenance by Error Code If you do not have the time to test which specific parts are faulty, you can directly change the required parts according the error code. You can find the parts to replace by error code in the following table. Error Code Part requiring replacement...
Page 174
Part requiring EL 16 eh 0b pc 06 pc 08/44/ 49 pc 0a pc 0f replacement Indoor PCB Outdoor PCB Outdoor fan motor T3 Sensor TP Sensor Pressure sensor Reactor Compressor IPM module board Data adapter board High pressure valve assy High pressure protector Low pressure protector Additional refrigerant...
7. Troubleshooting by Error Code EH 00 / EC 51 (EEPROM Parameter Error Diagnosis and Solution) Description: Indoor or outdoor PCB main chip does not receive feedback from EEPROM chip. Recommended parts to prepare: • Indoor PCB • Outdoor PCB Troubleshooting and repair: Shut off the power supply and turn it on 2 minutes later.
EL 01 (Indoor and Outdoor Unit Communication Error Diagnosis and Solution) Description: Indoor unit can not communicate with outdoor unit Recommended parts to prepare: • Signal wires • Magnet ring • Indoor PCB • Outdoor PCB Troubleshooting and repair: XYE Communication: Power off, then restart the unit 2 Power off, then restart the unit 2 minutes later...
Page 177
S Communication: Power off, then restart the unit after 2 minutes. Does the error code Solved disappear? Check the wiring connection Correct the connection or between indoor and outdoor change wires unit, are they good? The value is alternative from negative to positive Check the wiring connection Measure the DC voltage between N/L2 The value is fixed and close...
Page 178
Remarks: • Use a multimeter to test the DC voltage between 2 port(or S or L2 port) and 3 port(or N or S port) of outdoor unit. The red pin of multimeter connects with 2 port(or S or L2 port) while the black pin is for 3 port(or N or S port) . •...
EH 03 / EC 07 (Fan Speed Is Operating Outside of Normal Range)/EC 71(Over Current Failure of Outdoor DC Fan Motor)/ EC73(Zero-speed failure of outdoor DC fan motor) Diagnosis and Solution Description: When indoor / outdoor fan speed keeps too low or too high for a certain time, the unit ceases operation and the LED displays the failure.
Page 180
Index: 1. Indoor DC Fan Motor(control chip is in fan motor) Power on and when the unit is in standby, measure the voltage of pin1&pin2 of CN15, pin3 of CN34 in fan motor connector. If the value of the voltage is not in the range showing in below table, the PCB must has problems and need to be replaced.
EH 60/EH 61/EH 62/ EH 65/ EC 53/EC 52/EC 54/EC 56/EC 57/EC 50/EC 5C (Open Circuit or Short Circuit of Temperature Sensor Diagnosis and Solution) Description: If the sampling voltage is lower than 0.06V or higher than 4.94V, the LED displays the failure. Recommended parts to prepare: •...
EL 0C (Refrigerant Leakage Detection Diagnosis and Solution) Description: Judging the abnormality of the refrigeration system according to the number of compressor stops and the changes in operating parameters caused by excessive exhaust temperature. Recommended parts to prepare: • Indoor PCB •...
EH 0E(Water-Level Alarm Malfunction Diagnosis and Solution) Description: If the sampling voltage is not 5V, the LED displays the failure code. Recommended parts to prepare: • Connection wires • Water-level switch • Water pump • Indoor PCB Shut off the power supply and Shut off the power supply and turn it on 2 minutes later.
PC 00(IPM malfunction or IGBT over-strong current protection Diagnosis and Solution) Description: When the voltage signal the IPM sends to the compressor drive chip is abnormal, the display LED shows “PC 00” and the AC turn off. Recommended parts to prepare: •...
PC 01(Over voltage or too low voltage protection)/PC 10(Outdoor unit low AC voltage protection)/PC 11(Outdoor unit main control board DC bus high voltage protection)/PC 12(Outdoor unit main control board DC bus high voltage protection /341 MCE error) Diagnosis and Solution Description: Abnormal increases or decreases in voltage are detected by checking the specified voltage detection circuit.
PC 04(Inverter compressor drive error Diagnosis and Solution) Description: An abnormal inverter compressor drive is detected by a special detection circuit, including communication signal detection, voltage detection, compressor rotation speed signal detection and so on. Recommended parts to prepare: • Connection wires •...
7.10 PC 03/PC 31(Low Pressure Protection Diagnosis and Solution) Description: If the sampling voltage is not 5V, the LED displays a failure code. Recommended parts to prepare: • Connection wires • Low pressure protector • Indoor fan assembly • Outdoor PCB Troubleshooting and repair: Low pressure protection Low pressure protection...
7.11 PC 02/LC 06(Top temperature protection of compressor or High temperature protection of IPM module diagnosis and solution) Description: For some models with overload protection, If the sampling voltage is not 5V, the LED will display the failure. If the temperature of IPM module is higher than a certain value, the LED displays the failure code. Recommended parts to prepare: •...
Check the fastening screws on the PCB and IPM radiator. Replace the outdoor Are they fixed tightly? control PCB. Tighten the screws and apply silicon grease. 7.12 EC 0d(Outdoor unit malfunction Diagnosis and Solution) Description: The indoor unit detect the outdoor unit is error. Recommended parts to prepare: •...
7.13 PC 40(Communication error between outdoor main PCB and IPM board diagnosis and solution) Description: The main PCB cannot detect the IPM board. Recommended parts to prepare: • Connection wires • IPM board • Outdoor main PCB • Electric control box Troubleshooting and repair: Is there at least one LED in Is there at least one LED in...
7.14 PC 08(Current overload protection)/PC 44(Outdoor unit zero speed protection)/ PC 46(Compressor speed has been out of control)/PC 49(Compressor overcurrent failure) diagnosis and solution Description: An abnormal current rise is detected by checking the specified current detection circuit. Recommended parts to prepare: •...
Page 192
Was the protection activated Was the protection activated in standby? in standby? Restart the unit when the power supply Restart the unit when the power supply Is the power voltage is normal? Is the power voltage is normal? returns to normal returns to normal Is outdoor terminal voltage Is the power wiring...
7.15 PC 0F PFC module protection diagnosis and solution) Description: When the voltage signal that IPM send to compressor drive chip is abnormal, the LED displays the failure code and the AC turns off. Recommended parts to prepare: • Connection wires •...
7.16 EC 72 (Lack phase failure of outdoor DC fan motor diagnosis and solution) Description: When the three-phase sampling current of the DC motor is abnormal, especially when the current of one or more phases is always small and almost 0, the LED displays the failure code. Recommended parts to prepare: •...
7.17 PC 43 (Outdoor compressor lack phase protection diagnosis and solution) Description: When the three-phase sampling current of the compressor is abnormal, especially when the current of one or more phases is always small and almost 0, the LED displays the failure code Recommended parts to prepare: •...
7.18 PC 45 (Outdoor unit IR chip drive failure diagnosis and solution) Description: When the IR chip detects its own parameter error, the LED displays the failure code when power on. Recommended parts to prepare: • Inverter module PCB. Troubleshooting and repair: Power off,then restart the unit 2 minutes later.
7.20 PC 30 (High pressure protection diagnosis and solution) Description: Outdoor pressure switch cut off the system because high pressure is higher than 4.4 MPa Recommended parts to prepare: • Connection wires • Pressure switch • Outdoor fan • Outdoor main PCB Troubleshooting and repair: ...
Page 198
High pressure protection High pressure protection Are the high pressure switch Are the high pressure switch Connect high pressure switch and Connect high pressure switch and and main control boar wired and main control boar wired mian control board mian control board correctly? correctly? Is the high pressure...
7.21 PC 0A (High temperature protection of condenser diagnosis and solution) Description: When the outdoor pipe temperature is more than 65°C, the unit stops. It starts again only when the outdoor pipe temperature is less than 52°C. Recommended parts to prepare: •...
7.22 PC 06 (Discharge temperature protection of compressor diagnosis and solution) Description: If the compressor discharge temperature exceeds a certain level for nine seconds, the compressor ceases operation, the LED displays the failure code Recommended parts to prepare: • Connection wires •...
7.23 EH 0b(Communication error between indoor two chips diagnosis and solution) Description: Indoor PCB main chip does not receive feedback from another chip. Recommended parts to prepare: • Indoor main board • Adapter board Troubleshooting and repair: Shut off the power supply and turn it on 2 minutes later.
7.24 EL 16(Communication malfunction between adapter board and outdoor main board diagnosis and solution) Description: The adapter PCB cannot detect the main control board. Recommended parts to prepare: • Connection wires • Adapter board • Outdoor main PCB Troubleshooting and repair: Power off, then restart the unit after 3 minutes.
7.26 PC 41(Outdoor compressor current sampling circuit failure diagnosis and solution) Description: Three-phase sampling offset voltage error, the static bias voltage is normally 2.5V Recommended parts to prepare: • Outdoor main PCB Troubleshooting and repair: Shut off the power supply and turn it on 2 minutes later.
8. Check Procedures 8.1 Temperature Sensor Check WARNING Be sure to turn off all power supplies or disconnect all wires to avoid electric shock. Operate after compressor and coil have returned to normal temperature in case of injury. 1. Disconnect temperature sensor from PCB (Refer to Chapter 5. Indoor Disassembly and Chapter 6. Outdoor Disassembly). 2.
Page 206
Note: The picture and the value are only for reference, actual condition and specific value may vary. 8.3 IPM Continuity Check WARNING Electricity remains in capacitors even when the power supply is off. Ensure the capacitors are fully discharged before troubleshooting. 1.
Page 207
Note: The picture and the value are only for reference, actual condition and specific value may vary. Normal voltage of P and N 208-240V(1-phase,3-phase) 380-415V(3-phase) In standby around 310VDC around 530VDC In operation With passive PFC module With partial active PFC With fully active PFC module module...
Page 208
Indoor Unit Disassembly-Air Handle Contents Indoor Unit Disassembly ..................1 Electrical Parts ....................2 Fan Motor and Fan ..................5 Evaporator .....................7...
1. Indoor Unit Disassembly Electrical Parts (Antistatic gloves must be worn.) Procedure Illustration 1) Remove 2 screws of the upper cover Plate assembly and then remove the it. (see CJ_AHU_001) CJ_AHU_001 2) Remove 2 screws and unplug the plugs. (see CJ_AHU_002) 3) Pull out the electric control box subassembly.(see CJ_AHU_002) CJ_AHU_002...
Page 210
Procedure Illustration 4) Release 2 fixing screws and 1earthing screw.(see CJ_AHU_003) 5) Unplug the plugs and then remove the main control board subassembly. (see CJ_AHU_003) CJ_AHU_003 6) Release 1 fixing screw of the data transfer module control board to remove it. (see CJ_AHU_004) CJ_AHU_004 Note: This section is for reference only.
Page 211
Procedure Illustration 7) Release 2 screws and then remove the transformer. (see CJ_AHU_005) CJ_AHU_005 Note: This section is for reference only. Actual unit appearance may vary. Indoor Unit Disassembly 4...
Fan Motor and Fan Procedure Illustration 1) Remove 2 screws of fan assembly (see CJ_AHU_006) CJ_AHU_006 2) Take out the fan assembly (see CJ_ AHU_007) CJ_AHU_007 Note: This section is for reference only. Actual unit appearance may vary. Indoor Unit Disassembly 5...
Page 213
Procedure Illustration 3) Release 3 nuts fixing the fan motor and then take out the fan motor. (see CJ_AHU_008) CJ_AHU_008 4) Release the 1 nut fixing the fan and then take out the fan. (see CJ_AHU_009) CJ_AHU_009 Note: This section is for reference only. Actual unit appearance may vary. ...
Evaporator Procedure Illustration 1) Remove the cover plate (see CJ_ AHU_010) CJ_AHU_010 2) Remove 3 screws of cover plate assembly(below) (see CJ_AHU_011) CJ_AHU_011 Note: This section is for reference only. Actual unit appearance may vary. Indoor Unit Disassembly 7...
Page 215
Procedure Illustration 3) Take out the evaporator(with water collector assembly). (see CJ_AHU_012) CJ_AHU_012 4) Remove 2 screws of water collector assembly.(see CJ_AHU_013) 4) Release evaporator and the water collector assembly. CJ_AHU_013 Note: This section is for reference only. Actual unit appearance may vary. ...
Page 216
Outdoor Unit Disassembly Contents Outdoor Unit Table ....................2 Outdoor Unit Disassembly ..................3 Panel Plate .....................3 Electrical Parts .....................16 Fan Assembly ....................41 Fan Motor ....................42 Sound Blanket .....................43 Four-way Valve ....................44 Compressor ....................45...
2. Outdoor Unit Disassembly 2.1 Panel Plate 1. X230/X330 Procedure Illustration 1) Turn off the air conditioner and the power breaker. 2) Remove the screw of the big handle and then remove the big handle (1 screws) (see CJ_X230_001). Big Handle CJ_X230_001 Top Cover 3) Remove the screws of the top cover...
Page 219
Procedure Illustration 4) Remove the screws of water collecting cover and then remove the water collecting cover (2 screws) (see CJ_ X230_003). Water Collecting Cover CJ_X230_003 5) Remove the screws of the front panel and then remove the front panel (7 screws(onoff models) or 9 screws(inverter models) (see CJ_ X230_004).
Page 220
Procedure Illustration 6) Remove the screws of the right panel and then remove the right panel (5 screws) (see CJ_X230_005). Right Panel CJ_X230_005 Note: This section is for reference only. Actual unit appearance may vary. Outdoor Unit Disassembly 5...
Page 221
2.X430 Procedure Illustration 1) Turn off the air conditioner and the power breaker. 2) Remove the screw of the big handle and then remove the big handle (1 screw) (see CJ_X430_001). Big Handle CJ_X430_001 Top Cover 3) Remove the screws of the top cover and then remove the top cover (3 screws).
Page 222
Procedure Illustration 4) Remove the screws of water collecting cover and then remove the water collecting cover (2 screws) (see CJ_ X430_003). Water Collecting Cover CJ_X430_003 5) Remove the screws of the front panel and then remove the front panel (7 screws(onoff models) or 9 screws(inverter models) (see CJ_ X430_004).
Page 223
Procedure Illustration 6) Remove the screws of the right panel and then remove the right panel (6 screws) (see CJ_X430_005). Right Panel CJ_X430_005 Note: This section is for reference only. Actual unit appearance may vary. Outdoor Unit Disassembly 8...
Page 224
3. D30 Procedure Illustration 1) Turn off the air conditioner and the Big Handle power breaker. 2) Remove the screws of the big handle and then remove the big handle (2 screws) (see CJ_D30_001). CJ_D30_001 3) Remove the screws of the top cover and then remove the top cover (4 Top Cover screws).
Page 225
Procedure Illustration 4) Remove the screws of the front right panel and then remove the front right panel (2 screws) (see CJ_D30_003). Front Right Panel CJ_D30_003 5) Remove the screws of the front panel and then remove the front panel (9 screws) (see CJ_D30_004).
Page 226
Procedure Illustration 6) Remove the screws of water collecting cover and then remove the water collecting cover (2 screws) (see CJ_ D30_005). Water Collecting Cover CJ_D30_005 7) Remove the screws of the rear net and then remove the rear net (2 screws) (see CJ_D30_006).
Page 227
Procedure Illustration 8) Remove the screws of the right panel and then remove the right panel (8 screws) (see CJ_D30_007). Right Panel CJ_D30_007 Note: This section is for reference only. Actual unit appearance may vary. Outdoor Unit Disassembly 12...
Page 228
4. E30/590 Procedure Illustration 1) Turn off the air conditioner and the power breaker. 2) Remove the screws of the big handle and then remove the big handle (2 screws) (see CJ_E30_001). CJ_E30_001 3) Remove the screws of the top cover and then remove the top cover (4 screws).
Page 229
Procedure Illustration 5) Remove the screws of the front right panel and then remove the front right panel (2 screws) (see CJ_E30_004). CJ_E30_004 Note: This section is for reference only. Actual unit appearance may vary. Outdoor Unit Disassembly 14...
Page 230
Procedure Illustration 1) Remove the screws of the front panel and then remove the front panel (7 screws) (see CJ_E30_005). CJ_E30_005 2) Remove the screws of the right panel and then remove the right panel (10 screws) (see CJ_E30_006). CJ_E30_006 Note: This section is for reference only.
Electrical parts Antistatic gloves must be worn when you disassemble the electronic box. WARNING: Note: Remove the air outlet grille(refer to 3.1 Panel Plate) before disassembling electrical parts. 1. PCB board 1 Procedure Illustration 1) Remove the screws of the top cover. (2 screws) (see CJ_ODU_PCB_001- 1 ).
Page 232
2. PCB board 2 Procedure Illustration 1) Unfix the hooks and then open the electronic control box cover (4 hooks) (see CJ_ODU_PCB_002-1 ). 4-Way Valve 2) Disconnect the connector for fan CJ_ODU_PCB_002-1 motor from the electronic control board (see CJ_ODU_PCB_002-2 ). 3) Remove the connector for the Reactor compressor (see CJ_ODU_PCB_002-...
Page 233
3. PCB board 3 Procedure Illustration 1) Remove the screws and unfix the hooks, then open the electronic control box cover (5 screws and 2 hooks )(see CJ_ODU_PCB_003-1 ). Note:Electric control box cover cannot be removed, so the voltage between P and N cannot be measured.
Page 234
4. PCB board 4 Procedure Illustration 1) Remove the screws of the top cover. (1 screws) (see CJ_ODU_PCB_004- 1 ). CJ_ODU_PCB_004-1 2) Unfix the hooks and then open the electronic control box cover (5 hooks) (see CJ_ODU_PCB_004-2 ). CJ_ODU_PCB_004-2 3) Disconnect the connector for fan motor from the IPM board (see CJ_ ODU_PCB_004-3 ).
Page 235
Procedure Illustration 5) Pull out the wire connected with the terminal. (see CJ_ODU_PCB_004-4 ). T3/T4 6) Pull out connectors of the condenser coil temp. sensor(T3),outdoor ambient temp. sensor(T4) and discharge temp. sensor(TP) (see CJ_ODU_PCB_004-4 ). 7) Disconnect the electronic expansion valve wire (see Fig CJ_ODU_PCB_004- 4 ).
Page 236
5. PCB board 5 Procedure Illustration 1) Unfix the hooks and then open the electronic control box cover (4 hooks) (see CJ_ODU_PCB_005-1 ). 2) Disconnect the connector for outdoor DC fan from the electronic control board (see CJ_ODU_ PCB_005-2 ). 3) Remove the connector for the compressor (see CJ_ODU_PCB_005- 2 ).
Page 237
6. PCB board 6 Procedure Illustration 1) Unfix the hooks and then open the electronic control box cover (4 hooks) (see CJ_ODU_PCB_006-1 ). CJ_ODU_PCB_006-1 2) Remove 8 screws on the electronic control board and then turn over the electronic control board (see CJ_ODU_PCB_006-2 ).
Page 238
Procedure Illustration 3) Pull out the two blue wires connected with the four way valve. connect to IPM board PFC Inductor (see CJ_ODU_PCB_006-3 )(for heat T3&T4 Compressor pump models) 4) Pull out connectors of the condenser coil temp. sensor(T3),outdoor ambient temp. sensor(T4) and discharge temp.
Page 239
7. PCB board 7 Procedure Illustration 1) Unfix the hooks and then open the electronic control box cover (4 hooks) (see CJ_ODU_PCB_007-1 ). CJ_ODU_PCB_007-1 2) Remove 4 screws on the electronic control board and then remove the electronic control box subassembly. (see CJ_ODU_PCB_007-2 ).
Page 240
Procedure Illustration 3) Remove two screws and then remove the electronic control box subassembly on partition board assembly. (see CJ_ODU_PCB_007- 3 ). CJ_ODU_PCB_007-3 Note: This section is for reference only. Actual unit appearance may vary. Outdoor Unit Disassembly 25...
Page 241
Procedure Illustration 6) Remove two screws and two connectors and then remove the inverter control board (see CJ_ODU_ PCB_007-4 ). Connect to CN301 Connect to FM1 CJ_ODU_PCB_007-4 Note: This section is for reference only. Actual unit appearance may vary. ...
Page 242
8. PCB board 8 Procedure Illustration 1) Remove 2 screws to disconnect the power supply wires. (see CJ_ODU_ PCB_008-1) 2) Remove 3 screws to disconnect ground wires. (see CJ_ODU_ PCB_008-1) 3) Disconnect the wires connected to main control board. (see CJ_ODU_ PCB_008-1) 4) Disconnect the wires between main control board and IPM module board.
Page 243
Procedure Illustration 1) Remove 2 screws to disconnect the power supply wires. (see CJ_ODU_ PCB_008-2) 2) Remove 3 screws to disconnect the wires connected to the compressor. (see CJ_ODU_PCB_008-2) 3) Remove 3 screws to remove the radiator.(see CJ_ODU_PCB_008-2) 4) Disconnect the wires between IPM module board and main control board.
Page 244
Procedure Illustration 1) Remove the 1 screw and disconnect the wires and then remove the key board.(see CJ_ODU_PCB_008-4 )(for some models) CJ_ODU_PCB_008-4(for some models) Note: This section is for reference only. Actual unit appearance may vary. 9. PCB board 9 Procedure Illustration 2) Remove 3 screws to disconnect the...
Page 245
Procedure Illustration 7) Remove 3 screws to disconnect the power supply wires. (see CJ_ODU_ PCB_009-1) 8) Remove 3 screws to disconnect ground wires. (see CJ_ODU_ PCB_009-1) 9) Disconnect the wires connected to main control board. (see CJ_ODU_ PCB_009-2) 10) Remove the 4 screws and unfix the 4 hooks and then remove the filter board.(see CJ_ODU_PCB_009-2 ) 11) Remove the 2 screws of the reactor...
Page 246
10. PCB board 10 Procedure Illustration 1) Unfix the hooks and then open the electronic control box cover (4 hooks) (see CJ_ODU_PCB_010-1 ). CJ_ODU_PCB_010-1 2) Remove 6 screws on the electronic control board and then remove the electronic control box subassembly. (see CJ_ODU_PCB_010-2 ).
Page 247
Procedure Illustration 3) Pull out the connector, remove one screw and then remove the key board subassembly on terminal board. (see CJ_ODU_PCB_010-3 ) (for some models). CJ_ODU_PCB_010-3 Note: This section is for reference only. Actual unit appearance may vary. ...
Page 248
11. PCB board 11 Procedure Illustration 1) Disconnect the connector for compressor and release the ground wire(1 screw). (see CJ_ODU_ PCB_011-1 ). 2) Remove the electronic control box subassembly. (see CJ_ODU_ CJ_ODU_PCB_011-1 PCB_011-2 ). Note:Electric control box cover cannot be removed, so the voltage between P and N cannot be measured.
Page 249
12. PCB board 12 Procedure Illustration 1) Pull out the connectors (see CJ_ ODU_PCB_012-1 ). 2) Remove the 9 screws and unfix the 3 hooks and then remove the electronic control board(see CJ_ ODU_PCB_012-2 ). CJ_ODU_PCB_012-1 3) Disconnect the wires connected to main control board.
Page 250
13. PCB board 13 Procedure Illustration 1) Remove 4 screws unfix the radiator. (see CJ_ODU_PCB_013-1) 2) Remove 3 screws unfix the electronic control box assembly and partition board. (see CJ_ODU_PCB_013-1) 3) Remove 2 screws unfix the electronic control box assembly and terminal board subassembly.
Page 251
Procedure Illustration 5) Disconnect the wires connected to main control board. (see CJ_ODU_ PCB_013-3) 6) Remove the 4 screws and then remove the main control board.(see CJ_ODU_PCB_013-3 ) 7) Remove 1 screw to remove the key board .(see CJ_ODU_PCB_013-3 ). CJ_ODU_PCB_013-3 8) Disconnect the wires between filter board and main control board.
Page 252
Procedure Illustration 10) Remove the 2 screws and then remove the DR module box subassembly.(see CJ_ODU_ PCB_013-5 )(DR module box subassembly is on the back of the electronic control box assembly)(for some models) CJ_ODU_PCB_013-5(for some models) 11) Remove the 2 screws and then remove the DR module board.(see CJ_ODU_PCB_013-6 )(for some models)
Page 253
14. PCB board 14 Procedure Illustration 1) Unfix the hooks and then open the electronic control box cover (4 hooks) (see CJ_ODU_PCB_014-1 ). CJ_ODU_PCB_014-1 2) Remove 6 screws on the electronic control board and then remove the electronic control box subassembly. (see CJ_ODU_PCB_014-2 ).
Page 254
Procedure Illustration 3) Remove the 1 screw and disconnect the wires and then remove the 24V board.(see CJ_ODU_PCB_014-3 )(for some models) CJ_ODU_PCB_014-3(for some models) Note: This section is for reference only. Actual unit appearance may vary. Outdoor Unit Disassembly 39...
2.3 Fan Assembly Note: Remove the panel plate (refer to 3.1 Panel Plate) before disassembling fan. Procedure Illustration 1) Remove the nut securing the fan with a spanner (see CJ_ODU_ FAN_001-1&2). 2) Remove the fan. CJ_ODU_FAN_001-1 CJ_ODU_FAN_001-2 Note: This section is for reference only. Actual unit appearance may vary. ...
Fan Motor Note: Remove the panel plate and the connection of fan motor on PCB (refer to 3.1 Panel Plate and 3.2 Electrical parts) before disassembling fan motor. Procedure Illustration 3) Remove the fixing screws of the fan motor (4 screws) (see CJ_ODU_MOTOR_001). 4) Remove the fan motor.
Sound blanket Note: Remove the panel plate (refer to 3.1 Panel plate) before disassembling sound blanket. Procedure Illustration 1) Remove the sound blanket (side and top) (see CJ_ODU_BLANKET_001). Sound Blanket(top) (Applicable to models with blanket) Sound Blanket(side) (Applicable to models with blanket) CJ_ODU_BLANKET_001 Note: This section is for reference only.
Four-way valve (for heat pump models) WARNING: Evacuate the system and confirm that there is no refrigerant left in the system before removing the four-way valve and the compressor. (For R32 & R290, you should evacuate the system with the vacuum pump; flush the system with nitrogen;...
2.7 Compressor WARNING: Evacuate the system and confirm that there is no refrigerant left in the system before removing the four-way valve and the compressor. (For R32 & R290, you should evacuate the system with the vacuum pump; flush the system with nitrogen;...
Page 260
Procedure Illustration 3) Remove the hex nuts and washers securing the compressor, located on the bottom plate (see CJ_ODU_COMP_003). CJ_ODU_COMP_003 Suction Pipe 4) Heat up the brazed parts and then remove the the discharge pipe and the suction pipe (see CJ_ODU_COMP_004). Discharge Pipe 5) Lift the compressor from the base pan assembly with pliers.
Page 261
Appendix Contents Temperature Sensor Resistance Value Table for T1, T2, T3, and T4 (°C – K) ..2 Temperature Sensor Resistance Value Table for TP (for some units)(°C --K) ..3 iii) Pressure On Service Port ..................4...
Page 262
i) Temperature Sensor Resistance Value Table for T1,T2,T3 and T4 (°C – K) °C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm 115.266 12.6431 2.35774 0.62973 108.146 12.0561 2.27249 0.61148 101.517 11.5 2.19073 0.59386 96.3423 10.9731...
Page 263
ii) Temperature Sensor Resistance Value Table for TP(for some units) (°C --K) °C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm...
Need help?
Do you have a question about the MOOVAIR 22023111000271 and is the answer not in the manual?
Questions and answers