Download Print this page

Renu Electronics FL055-0808N-V2 Manual

Advertisement

Quick Links

FL055-0808N-V2 &
FL005-0808N-V2
FL055-0808N-V2: Is base PLC model from FlexiLogics family.
It has inbuilt 8 digital inputs and 8 digital NPN type outputs
with 2 serial ports, one USB Type C, one Ethernet port. The
model can be expanded up to 16 I/O modules.
FL005-0808N-V2: This is a base PLC model from FlexiLogics
family. It has inbuilt 8 digital inputs and 8 digital NPN type
outputs with 2 serial ports, one USB Type C port. This model
can be expanded up to 16 I/O modules. This model does not
have an Ethernet port.
System Components:
- FL055-0808N-V2 or FL005-0808N-V2
- Installation Kit: 2 Locking Connectors, 2 DIN rail sliders.
PRODUCT DIMENSIONS
SPECIFICATIONS
Power Supply
24VDC (±15%), 110mA
Isolation
Non-Isolated
Memory
Total Program Memory
8 MB + 2 MB
(Application+ Ladder/Logic)
Program Capacity
50K Steps
Keep Memory Registers
10752 WORDS (FRAM)
Communication Ports
COM1 (RJ45)
RS232, for Programming & Communication
COM2 (Open terminals)
2-wire RS485 for Communication
Ethernet* (FL055 only)
10/100Mbps, for
upload/download/Communication
USB
1 x USB Type C
Expansions
Expansion IO capacity
16 Expansions modules, 256 I/O ports
Local IO Specification
Number of Inputs
8 Inputs [Bi-directional type]
Input Design
According to the EN 61131-2 type 1
ON Voltage
Minimum : 15VDC, Maximum: 30VDC
OFF Voltage
Minimum : -3VDC, Maximum: 5VDC
Nominal Input
24VDC, 5mA typical
Isolation
Optically isolated from internal circuit
High isolation voltage (BV= Greater than
1I bk
1.5KV)
Input Response Time
ON: 10msec, OFF: 10msec
Input Impedance
4.8KΩ
High Speed Channels
High Frequency 200kHz: 4 Pairs (X0-X1, X2-
Single Phase Counter
X3, X4-X5 & X6-X7) or
Low Frequency 25kHz: 8 (X0-X7)
Quadrature Channels
High Frequency 200kHz: 4 Pairs (X0-X1, X2-
X3, X4-X5 & X6-X7)
Max. Input Count
4294967295 (32 Bit)
Number of Outputs
8 (NPN Transistor type), within which 4
Outputs are PWM type
4 PWM Output
Y0(Pulse 200kHz), Y1(for Direction of Y0),
Y2(Pulse 200kHz), Y3(for Direction of Y2),
Y4(Pulse 200kHz), Y5(for Direction of Y4),
Y6(Pulse 200kHz), Y7(for Direction of Y6)
ON Output Voltage
Min ON: 22VDC (Voltage across load)
Max. ON: 30VDC (Voltage across load)
Nominal Output Voltage
24VDC
Nominal Output Current
250mA typical per channel
Output Response Time
ON: 10µsec, OFF: 10µsec
Nominal Load Max.
96Ω/6W (resistive) @24VDC
5VA(inductive)
Environment & Approvals
Operating Temperature
0 to 55°C
Humidity
10 to 90% (Non-Condensing)
25g, 11ms, Half Sine wave, 3 mutually
Shock Circuit Protection
perpendicular axes
5 to 150Hz, displacement of 0.3mm
Vibration
(peak to peak), 3G, 3 mutually
perpendicular axes
Approvals
CE, RoHS
PANEL MOUNTING
FIG-1: Pull up the sliders (highlighted) provided with the unit
towards outward direction as shown.
FIG-2: Rest the unit on the DIN rail plate.
FIG-3: Press the highlighted connector into the downward
direction to lock it same connector from the downside of the
product press upward direction. Locking connector helps the
two units (FL base & expansion) to hold each-other properly on
the DIN rail plate.
FIG-4
FIG-4: Two slots to grip the locking connector are provided on
the case highlighted by RED circle, pulled the connector.
FIG-5: Lock connector provided with base module unit as shown
to the Expansion module.
FIG-5

Advertisement

loading
Need help?

Need help?

Do you have a question about the FL055-0808N-V2 and is the answer not in the manual?

Questions and answers

Summary of Contents for Renu Electronics FL055-0808N-V2

  • Page 1 1 x USB Type C Expansions Expansion IO capacity 16 Expansions modules, 256 I/O ports FL055-0808N-V2: Is base PLC model from FlexiLogics family. Local IO Specification Number of Inputs 8 Inputs [Bi-directional type] It has inbuilt 8 digital inputs and 8 digital NPN type outputs...
  • Page 2 COM2: 2-wire RS485 for Communication Rev. Description Date Pin number Signal First Draft 05/08/2022 TX+/RX+ Updated Specifications 14/09/2022 TX-/RX- Updated Wiring Diagrams 04/01/2023 RENU Electronics Pvt. Ltd® reserves the right to change or discontinue Specifications and features without prior notice. www.renuelectronics.com.

This manual is also suitable for:

Fl005-0808n-v2