Quick Links

• 5 RJ45 Ethernet ports
• Autosense
This section contains the instructions necessary for correct
installation of the GILOGIK II into the machine control panel
or the host system and for correct connection of the system
power supply, inputs, outputs and interfaces.
Before proceeding with installation read the following
warnings carefully!
Remember that lack of observation of these warnings
could lead to problems of electrical safety and electroma-
gnetic compatibility, as well as invalidating the warranty.
Qualified staff
the installation and use of the system and components are only reserved
at qualified staff.
Conform use
the system and relative components are usable exclusively to the use
previewed in the manual
In order to guarantee a correct and sure operation are indispensable that
the product comes transported, stored correctly, installed, and controlled
second the previewed modalities.
Electrical power supply
the GILOGIK II is NOT equipped with an On/Off switch: the user must
provide a two-phase disconnecting switch that conforms to the required
safety standards (CE marking), to cut off the power supply upstream of the
system. The switch must be located in the vicinity of the system and must
be within easy reach of the operator.
One switch may control more than one systems.
To make sure that the system very is connected to earth second the
detailed lists of the relative understood one it.
if the system is used in applications with risk of damage to persons,
machinery or materials, it is essential to connect it up to auxiliary security
equipment. It is advisable to make sure that alarm signals are also trigge-
red during normal operation.
The dispositif must NOT be installed in flammable or explosive environ-
ments; it may be connected to equipment operating in such atmospheres
only by means of appropriate and adequate types of interface, conforming
to the applicable safety standards
80125_MHW_R-SW5_1006_ENG
R-SW5
5 PORTS SWITCH ETHERNET MODULE
INSTALLATION AND OPERATION MANUAL
cod. 80125 / Edit 01 - 10/06 - ENG
For SW configuration please refer to the user's
manual contained in the attached CD
1 • MAIN FEATURES
I
2 • INSTALLATION AND CONNECTION
• Up-link port
• 10/100Mbps
Notes Concerning Electrical Safety and Electromagnetic
Compatibility:
• CE MARKING: EMC Conformity (electromagnetic compatibility)
in accordance with EEC Directive 89/336/CEE modified by Directive
93/68. The GILOGIK II system is mainly designed to operate in industrial
environments, installed on the switchboards or control panels of producti-
ve process machines or plants.
As regards electromagnetic compatibility, the strictest generic standards
have been adopted, as indicated in the table below.
• BT Conformity (low tension)
in accordance with Directive 73/23/CEE modified by Directive 93/68.
Advice for Correct Installation for EMC
Module power supply
The power supply to the modules on the switchboards must always
come directly from an isolation device with a fuse.
The electronic instruments and electromechanical power devices
such as relays, contactors, solenoid valves, etc., must always be powered
by separate lines.
When the power supply is strongly disturbed by the commutation of
transistor or power units or motors, an isolation transformer should be
used, earthing the screen.
It is essential that the plant has a good earth connection:
- the voltage between neutral and earth must not be > 1V
- the Ohmic resistance must be < 6Ω;
In the proximity of high frequency generators or arc welders, use
adequate filters.
The power supply lines must be separate from the instrument input
and output ones.
GEFRAN S.p.A. declines all responsibility for any damage
to persons or property caused by tampering, neglect,
improper use or any use which does not conform to the
characteristics of the controller and to the indications
given in these Instructions for Use.
1

Advertisement

loading
Need help?

Need help?

Do you have a question about the 80125 and is the answer not in the manual?

Questions and answers

Summary of Contents for gefran 80125

  • Page 1 R-SW5 5 PORTS SWITCH ETHERNET MODULE INSTALLATION AND OPERATION MANUAL cod. 80125 / Edit 01 - 10/06 - ENG For SW configuration please refer to the user’s manual contained in the attached CD 1 • MAIN FEATURES • 5 RJ45 Ethernet ports •...
  • Page 2 Green LED ACTIVITY 4 Yellow LED LINK 4 PORT 4 Yellow LED POWER Green LED UP-LINK Up LINK Yellow LED ACTIVITY GEFRAN spa via Sebina, 74 - 25050 Provaglio d’Iseo (BS) Tel. 03098881 - fax 0309839063 - Internet: http://www.gefran.com 80125_MHW_R-SW5_1006_ENG...

This manual is also suitable for:

R-sw5