Kele KGC-120 Operation Instructions Manual

Detection and ventilation control pane
Table of Contents

Advertisement

Quick Links

Kele KGC-120
Detection and Ventilation Control Panel
Operation Instructions
IMPORTANT: Keep these user instructions for reference.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the KGC-120 and is the answer not in the manual?

Questions and answers

Summary of Contents for Kele KGC-120

  • Page 1 Kele KGC-120 Detection and Ventilation Control Panel Operation Instructions IMPORTANT: Keep these user instructions for reference.
  • Page 2: Table Of Contents

    Kele Gas Controller KGC-120 Operation Manual Table of Contents General Safety Information ................................ 5 List of warnings .................................. 5 Use Instructions and Limitations ..............................6 KGC-120 General Description ............................6 Features ..................................... 7 Specifications ..................................7 Installation Instructions ................................8 Location &...
  • Page 3 Kele Gas Controller KGC-120 Operation Manual 4.8.4 Configure Relays, Horn & Strobe Submenu ........................ 29 4.8.5 Configure Horn Submenu ............................31 4.8.6 Configure Strobe Submenu ............................31 4.8.7 Configure Zones Submenu ............................32 4.8.8 Configure Signals Submenu ............................36 Troubleshooting ..................................41 System Status Light ................................
  • Page 4 Appendix C – Replacement Parts ............................. 57 Appendix D – Setup Record ..............................58 Appendix E – KGC-120 Quick Start Guide ..........................59 Kele Gas Detection Product limited warranty .......................... 60 Technical Support Contact Information ..................... Error! Bookmark not defined.
  • Page 5: General Safety Information

    For proper use, see supervisor or User manual, or call Kele Technical Service at 877-826-9045. KGC-120 may not function effectively below 32°F (0°C) or above 120°F (49°C). Using the equipment outside of this temperature range may adversely affect product.
  • Page 6: Use Instructions And Limitations

    The KGC-120 exhaust fan controller, in conjunction with Kele™ gas detector, controller, transducers, provides automatic controls to help maintain an acceptable environment in parking garages or other facilities. The KGC-120 system is designed to meet specifications for safety in enclosed parking garages, including the Uniform Building Code and OSHA 50ppm CO requirements.
  • Page 7: Features

    ETL Listed to UL 2017 (Type SM) Where required by federal, state, local regulations or the Authority Having Jurisdiction, KGC-120 is required to be used with Listed Horn/Strobe model 78-2900-0211-X* to meet the 85dB(A) Audibility requirements of Standards UL 2017.
  • Page 8: Installation Instructions

    3.2 Mounting Mounting holes are provided in the KGC-120 case at the four corners. The top two are keyhole shaped so that the panel can be hung and then the two bottom screws driven to hold the panel. See figure 2-1. The panel should be mounted with sufficient space all around for access to Conduit entry holes provided on the top, bottom and right side of the panel.
  • Page 9: Installation

    (see the User Instructions of each sensor type for location and coverage details). Extra sensors may be needed near areas where people work, such as toll booths. Kele provides only the control panels and sensors. Fans, relays, and other devices are provided by the contractor.
  • Page 10: Power Connection

    AC power connections must be bundled with the KGC-120 sensor cables, the sensor connections should be made with two twisted pairs of the appropriate gauge, with an overall foil and braid shield. All shields should be terminated at the KGC-120 end of the cable only.
  • Page 11: Remote Sensor Connection

    Figure 3-4 Sensor Interface Connection – Channels 5 and 6 Note: If CX-6 (CO and NO dual sensor) is connected to Channel X in KGC-120 then address X is assigned to NO sensor and address “X+12” is assigned to CO Sensor.
  • Page 12: Relay Connection

    Kele Gas Controller KGC-120 Operation Manual 1250 Table 3-2 Recommended Wire Gauge Figure 3-5 KGC-120 Internal View 3.3.4 Relay Connection All poles of the three relays are available at the modular connector R1 R2 R3 (see Figure 2- for details). R1 R2 R3 is a 9-position variant of the high voltage modular connector used for power input.
  • Page 13: Horn & Strobe Connection

    Immediately exit any environment that causes an alarm condition on the sensor. 3.3.6 Interfacing Kele Sensors Kele sensors with current loop outputs may be used with the KGC-120. See Kele.com for information on compatible Kele gas transducers. See specific information on other manufacturer’s transducers.
  • Page 14 Power connections to Kele sensors used with the KGC-120 are polarity-insensitive (no polarity), since a bridge rectifier is connected to the power input terminals. All sensors used with the KGC-120 panel employ screw clamp terminal blocks for power and signal connections. Polarity of the current loop connections is marked on the modular connector of the sensor.
  • Page 15: Operation

    4.1 Power up When power is first applied to the KGC-120, a few simple self-tests will be performed, and the system will cycle through all status lights, and display the system name and model # (Figure 3-1). The system will then proceed to normal mode, if the operating parameters have been entered.
  • Page 16: User Interface

    The keypad is used to select the information displayed and to enter the configuration parameters, which are stored in the KGC-120 memory. The keypad consists of the usual ten-digit keys, four direction keys, plus a MENU key that is used to access the configuration menu and a HUSH key that will silence the audible alarm indicators.
  • Page 17: Hush Key

    Figure 4-5 Sensor prompt In this example, the first digit entered was 1. Since the KGC-120 can handle 12 sensors, the first digit for a sensor number is either 0 or 1. The leading zero must be entered when selecting a sensor less than ten. When the second digit is entered, the normal display will be restored;...
  • Page 18: Warning Status Display

    Kele Gas Controller KGC-120 Operation Manual Figure 4-6 Alarm display The display will cycle through all sensors that are signaling alarm levels, at five seconds per display. Pressing any key (except HUSH) will advance the display to the next sensor that is signaling an alarm level.
  • Page 19: Trouble Status Display

    Kele Gas Controller KGC-120 Operation Manual When the HUSH key is pressed, the internal buzzer will be silenced for fifteen (15) minutes. If the horn or strobe turn on delays have not finished, then they will also be silenced. If the delays have finished, the HUSH key must be held for three (3) seconds in order to silence the horn and strobe.
  • Page 20: Ventilation Control

    Kele Gas Controller KGC-120 Operation Manual 4.7 Ventilation Control The ventilation control function operates independently from the alarm function. It provides the ability to configure the KGC- 120 for control of one to three zones. Each zone can respond to gas levels indicated by one or more of the sensors, with configurable turn on and turn off concentrations (rising and falling) for each gas type.
  • Page 21: System Menu

    While the KGC-120 is in the configuration mode, alarm and ventilation control functions continue in the background with the previously set configuration values. If an alarm condition is detected, the alarm lamp, the buzzer, the horn and the strobe will operate as configured but the LCD will not display the detailed information.
  • Page 22: Configure System Submenu

    Kele Gas Controller KGC-120 Operation Manual 4.8.2 Configure System Submenu The system configuration submenu provides entries to: • Set the time of day, 24-hour format • Set the day of the week, day 1 is Monday • Load Default Configuration •...
  • Page 23 Kele Gas Controller KGC-120 Operation Manual This display example shows that Tuesday is the current day of the week. The underline character indicates that the day can be changed by entering the corresponding digit: • 1 - Monday • 2 - Tuesday •...
  • Page 24 KGC-120 will remain in normal mode. When new registration information is detected by the KGC- 120, for example if a different gas type of Kele sensor was installed, the following message is displayed: “Configuration Changed Any key to save” is displayed.
  • Page 25 Custom Sensor Implementation Custom sensor types or “wildcards” can be configured with the KGC-120. There are 8 Kele sensor types and 21 custom sensor types available. Though the Kele sensor data cannot be changed, custom sensor parameters can be configured to define the...
  • Page 26 Kele Gas Controller KGC-120 Operation Manual T y p e : 0 1 D e c . : 0 8 8 8 8 . p p m Figure 4-28 Decimal Points “Dec.” defines how many decimal points are used to display the reading, alarm, warning, range, rising and falling levels. It can have values between 0 and 2.
  • Page 27 Kele Gas Controller KGC-120 Operation Manual “Rise” is the default rising level used in Zone configuration. T y p e : 0 1 F a l l : 1 5 p p m Figure 4-34 Falling Trip Point “Fall” is the default falling level used in Zone configuration.
  • Page 28: Configure Sensors Submenu

    SYS header. 3. Power up the KGC-120. The first display is the current password on the unit. 4. Remove the Jumper Shorting Connector from the SYS header and install back onto the two bottom pins of the EXT header.
  • Page 29: Configure Relays, Horn & Strobe Submenu

    Kele Gas Controller KGC-120 Operation Manual Description Carbon Nitrogen Combustible Ammonia Hydrogen Refrigerants Carbon Oxygen Carbon Monoxide Dioxide Sulfide Dioxide Dioxide (KGD-6-CO2) Alarm 200 ppm 5 ppm 20% LEL 75 ppm 20 ppm 300 ppm 4000 ppm 19.5% v/v 0.50% vol Level Setting an alarm level of 0 (zero) will disable alarm detection for this particular sensor.
  • Page 30 Kele Gas Controller KGC-120 Operation Manual 4.8.4.1 Relay Summary R e l a y 1 N o r m . O f f D e l a y O n , M i n . O n Figure 4-43 Relay Summary This display example shows that Relay 1 is configured to operate Normally Off, with a turn on delay and a minimum on time.
  • Page 31: Configure Horn Submenu

    Kele Gas Controller KGC-120 Operation Manual The default minimum on time is one minute and the maximum allowed value is fifteen minutes. 4.8.5 Configure Horn Submenu The configuration parameters for the horn are similar to those for relays. A horn would not normally require a minimum on time, but this parameter allows a more versatile configuration.
  • Page 32: Configure Zones Submenu

    4.8.7 Configure Zones Submenu The KGC-120 ventilation control can support up to three zones. The zone functionality makes the KGC-120 very flexible. For example, each zone can be configured to monitor a separate set of four sensors and control a single relay.
  • Page 33 Kele Gas Controller KGC-120 Operation Manual • 3 - Relay 3 added/removed from the zone’s control • 4 - Horn added/removed from the zone’s control • 5 - Strobe added/removed from the zone’s control When controlled by a zone the default horn pattern is the Triple Tap pattern, see 3.3.8.7 and the strobe will turn on continuously when a zone is controlling them.
  • Page 34 Group 10 in each zone Type 10 CO , Voting mode, Quorum = 1 NOTE: If CX-6 is connected to KGC-120, it will occupy two address and appear as one CO (Type: 1) sensor and one NO (Type 2) sensor on the panel.
  • Page 35 Kele Gas Controller KGC-120 Operation Manual The stop time is entered in 24-hour format and the default value is 18:00 (6:00 PM). 4.8.7.6 Sensor Selection G r o u p 1 N O 2 S e n s o r : 0 2 , 0 4 , 1 1 Figure 5-56 Sensor Selection Sensors are included or removed from the group by entering the two-digit channel number.
  • Page 36: Configure Signals Submenu

    4.8.8 Configure Signals Submenu The KGC-120 can drive the buzzer, horn and strobe with different sound patterns to indicate the severity of the current conditions. These patterns are selectable by the installer using this group of submenus. Once again, the left and right keys will scroll through the signal types and the up and down keys will scroll to the signal sources.
  • Page 37 Kele Gas Controller KGC-120 Operation Manual 4.8.8.1 Alarm Signal Summary The alarm signals are in response to one or more sensors indicating gas levels at or above the sensors’ configured alarm level. A l a r m S i g n a l s...
  • Page 38 Kele Gas Controller KGC-120 Operation Manual This display example shows that the strobe will signal an alarm condition with a continuous signal. The signal definitions are: • 1 - Continuous (default) • 2 - Intermittent, one second on at two second intervals •...
  • Page 39 Kele Gas Controller KGC-120 Operation Manual • 1 - Continuous • 2 - Intermittent, one second on at two second intervals • 3 - Double tap, two beeps at 5 second intervals • 4 - Triple tap, three short beeps at 10 second intervals •...
  • Page 40 Kele Gas Controller KGC-120 Operation Manual 4.8.8.11 Trouble Horn Signal T r o u b l e S i g n a l s H o r n : 5 O F F Figure 4-72 Horn Trouble Signal This display example shows that the horn will not signal a trouble condition. The horn signal definitions are: •...
  • Page 41: Troubleshooting

    Kele sensors may be tested by depressing the TEST button on the sensor printed circuit board, or (depending on the type of sensor), the button on the interior front panel of the unit. Kele sensors will step the output current level from 4 mA to 20 mA over the course of the warm-up period, allowing the technician to determine where the trouble condition exists.
  • Page 42: Internal Controller Board Trouble

    When using the timed ventilation mode, the system clock should be checked regularly (at least twice a year). The battery backed real time clock in the KGC-120 does not adjust for daylight saving time so the spring and fall switch over points are good choices to check the system clock.
  • Page 43: Lcd Display Unreadable

    Kele Gas Controller KGC-120 Operation Manual 5.4 LCD Display Unreadable It is possible that the LCD is unreadable due to temperature or aging of the control panel. If this is the case the following steps should rectify the problem: •...
  • Page 44: Testing & Maintenance

    6.1.2 Functionality Test Turn off the KGC-120. For KGC-120 move the jumper from bottom two pins of EXT connector to pins 1 and 2 of EXT connector. For KGC- 120, move the jumper in J10 to left two pins of J10.
  • Page 45: Appendix A - Table Of Figures

    Figure 3-4 Sensor Interface Connection – Channels 5 and 6 ......................11 Table 3-2 Recommended Wire Gauge .............................. 12 Figure 3-5 KGC-120 Internal View ..............................12 Figure 3-6 Relay Connections ................................13 Figure 3-7 Horn & Strobe Connector ..............................13 Table 3-3 Wire Gauge for Horn &...
  • Page 46 Kele Gas Controller KGC-120 Operation Manual Figure 4-35 Enter Password ................................27 Figure 4-36 Password Prompt................................27 Figure 4-37 Wrong Password Prompt ............................... 27 Figure 4-38 Sensor Summary ................................28 Figure 4-39 Sensor Type ................................... 28 Figure 4-40 Sensor Alarm Level ................................ 28 Figure 4-41 Sensor Warning Level ..............................
  • Page 47: Appendix B - Quick Setup

    Note: The Delay Time default is 1 minute. If the duration of a test procedure or gas exposure is less than 1 minute, the relays, horns, and strobes may not engage even though the KGC-120 display and the sensors respond. When testing the system disable the delay (set Delay Time to zero minutes/seconds).
  • Page 48 5,000 sq. ft. (464.5 sq. m) (see the User Instructions for each sensor type for location and coverage details). Extra sensors may be needed near areas where people work, such as toll booths. Kele provides only the control panels and sensors. Fans, relays, and other devices are provided by the contractor. See the appropriate building code for the size of fans and air changes per unit of time.
  • Page 49 Kele Gas Controller KGC-120 Operation Manual Kele KGC-120 Figure B-1 System Wiring Diagram Setting the System Configuration The configuration menus can be entered from normal mode by pressing the MENU key. While in configuration mode, the user can review all configuration parameters to check the current operating conditions.
  • Page 50: Configure System Submenu

    Kele Gas Controller KGC-120 Operation Manual When exiting from the menu system to normal mode, if any configuration changes have been made, the panel will ask whether changes are to be saved. S a v e C o n f i g . ?
  • Page 51: Set Day Of Week

    Kele Gas Controller KGC-120 Operation Manual 8.1.2 Set Day of Week T i m e : 2 2 : 5 5 D a y : 2 T u e s d a y Figure B-6 Set Day of the Week This display example shows that Tuesday is the current day of the week.
  • Page 52: Configure Sensors Submenu

    SYS header. → Power up the KGC-120. The first display is the current password on the unit. → Remove the Jumper Shorting Connector from the SYS header and install back onto the two bottom pins of the EXT header.
  • Page 53: Configure Relays, Horn & Strobe Submenu

    Kele Gas Controller KGC-120 Operation Manual S e n s o r R a n g e : 2 0 0 p p m Figure B-15 Sensor Range ↑ Next Sensor - complete for all sensor channels 8.3 Configure Relays, Horn & Strobe Submenu 8.3.1 See section...
  • Page 54 Kele Gas Controller KGC-120 Operation Manual Press Menu to display Hardware Summary ↑ x 4 Configure Zones → Zone 1 Controls R_ R_ R_ H_ S_ Enter (underlined) number of outputs for zone R = Relay (1, 2 and 3), H = Horn (4), S = Strobe (5)
  • Page 55: Configure Signals Submenu

    → Configure Group 2 - repeat for up to three groups When multiple sensors are being monitored as a Group, the KGC-120 output can be based on either sensor Voting (default) or the Average of all sensor readings in the Group.
  • Page 56 Kele Gas Controller KGC-120 Operation Manual Figure B-27 Buzzer Alarm Signal ↑ Warning Signals W a r n i n g S i g n a l s H o r n : 5 O F F Figure B-28 Horn Warning Signal ↑...
  • Page 57: Appendix C - Replacement Parts

    KGC-120B Replacement Board 70-2900-0017-3 KGC-1200 KGC-1200 Replacement Board 70-2900-0017-7 * Replacement Lock/Key is for KGC-120, KGC-120M, KGC-120B. Lock assembly on the KGC-1200 is part of the housing and is not replaceable. REV – 1.3 57 | P a g e...
  • Page 58: Appendix D - Setup Record

    Kele Gas Controller KGC-120 Operation Manual 10 Appendix D – Setup Record Record network parameters and keep in a safe place to assist with installation and future troubleshooting will be simplified. Date of Install: _______________________________ Serial Number: _______________________________ Location of Install: ____________________________...
  • Page 59: Appendix E - Kgc-120 Quick Start Guide

    Kele Gas Controller KGC-120-B Operation Manual 11 Appendix E – KGC-120 Quick Start Guide Quick Start Guide for Adding Sensor to Zone KGC-120 with 3 CO and 3 NO2 Detectors REV – 1.3.0 59 | P a g e...
  • Page 60: Kele Gas Detection Product Limited Warranty

    12 Kele Gas Detection Product limited warranty Kele warrants the KGC-120 gas detector will be free from defective materials and workmanship for a period of two (2) years from the date of manufacture (indicated on inside cover of the KGC-120), provided it is maintained and used in accordance with Kele instructions and/or recommendations.

Table of Contents