200MICROP01 is a magnetic door switch compatible with all Pego electronics and electronic panels with low voltage digital input. The simplicity of installation and its technology make it the ideal accessory for cold room management.
The 200MICROP01 must only be used as a switch, connected to a digital input of the control unit, to signal the opening of the door of a cold room.
Please Note: 200MICROP01 is not a safety device.
PEGO CODE | DESCRIPTION |
200MICROP01 | Magnetic door switch with N.O. contact |
Open the door switch by unscrewing the two screws on the back of the sensor to access the board. Pass the cable through the PG and connect the two wires to the terminal.
Close the sensor taking care to position the bottom so as to have the cable outlet on the desired side and tighten the two screws on the back.
The door switch can be fixed to the wall using the long screws provided. The magnet is equipped with a double-sided adhesive, but it is advisable to fix it to the door using also screws. It is important that the door switch and the magnet do not come into direct contact when the door is closed; this to avoid shocks that could damage them over time.
DIMENSIONS
NB: The distance (D) between the magnet and the sensor must be between 4mm and 7mm.
It is advisable to mount the door switch as high as possible; follow the examples below.
MOUNTING VARIATIONS
INSTALLATION EXAMPLES
PROBLEM | SOLUTIONS |
Operation is reversed |
|
When the door is closed the plant does not restart |
|
Electrical characteristics | |
Switched power | 10W |
Switched voltage | 200 VDC 140 VAC RMS |
Switched current | 500mA DC 500mA AC RMS |
Number of cycles | 1.000.000.000 (1V, 10mA) |
Environment conditions | |
Operating temperature | -20T90°C humidity < 90% Rel. Hum. not condensing |
Storage temperature | -20T90°C humidity < 90% Rel. Hum. not condensing |
Unsuitable operating environments | Environments with strong vibrations or impacts; aggressive, polluted or corrosive atmospheres, exposure to direct solar radiation, explosive atmospheres or flammable gas. |
General characteristics | |
Cable entry | PG7, max cable diameter = 7mm Right or left side entry, rotating the bottom. |
Electrical connection | Fixed screw terminals for cables with cross-sections from 0.2 to 1.5mm2 |
Type of contact | N.O. |
Dimensional, insulation and mechanical characteristics | |
Dimensions | 74x48x40mm (sensor) 44x15x8mm (magnet) |
Front protection rating | IP65 |
Installation | With supplied screws |
Casing | Plastic body in PC + ABS UL94 V-0 |
PEGO S.r.l.
Via Piacentina, 6/b - 45030 - Occhiobello (RO)
Tel: 0425 762906
www.pego.it
e-mail: info@pego.it
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Advertisement
Need help?
Do you have a question about the Expert Series and is the answer not in the manual?
Questions and answers