DESCRIPTION

200MICROP01 is a magnetic door switch compatible with all Pego electronics and electronic panels with low voltage digital input. The simplicity of installation and its technology make it the ideal accessory for cold room management.

MAIN FEATURES

  • Contact closed when the magnet is near the sensor (door closed).
  • No calibration required.
  • The cable exit side can be established during installation, by turning the bottom by 180°.

REQUIREMENTS

The 200MICROP01 must only be used as a switch, connected to a digital input of the control unit, to signal the opening of the door of a cold room.
Please Note: 200MICROP01 is not a safety device.

MODELS

PEGO CODE DESCRIPTION
200MICROP01 Magnetic door switch with N.O. contact

ASSEMBLY INSTRUCTIONS

Open the door switch by unscrewing the two screws on the back of the sensor to access the board. Pass the cable through the PG and connect the two wires to the terminal.

Close the sensor taking care to position the bottom so as to have the cable outlet on the desired side and tighten the two screws on the back.
The door switch can be fixed to the wall using the long screws provided. The magnet is equipped with a double-sided adhesive, but it is advisable to fix it to the door using also screws. It is important that the door switch and the magnet do not come into direct contact when the door is closed; this to avoid shocks that could damage them over time.

DIMENSIONS

NB: The distance (D) between the magnet and the sensor must be between 4mm and 7mm.
It is advisable to mount the door switch as high as possible; follow the examples below.

MOUNTING VARIATIONS

INSTALLATION EXAMPLES
Installation Examples

  1. door side
  2. above the door

PROBLEMS AND SOLUTIONS

PROBLEM SOLUTIONS
Operation is reversed
  • The contact is closed when the magnet is near the sensor (door closed). Invert the operating logic of the electronic control input to which it is connected.
When the door is closed the plant does not restart
  • Excessive distance between the sensor and the magnet.
  • Check the electrical connections.

TECHNICAL DATA

Electrical characteristics
Switched power 10W
Switched voltage 200 VDC
140 VAC RMS
Switched current 500mA DC
500mA AC RMS
Number of cycles 1.000.000.000 (1V, 10mA)
Environment conditions
Operating temperature -20T90°C
humidity < 90% Rel. Hum. not condensing
Storage temperature -20T90°C
humidity < 90% Rel. Hum. not condensing
Unsuitable operating environments Environments with strong vibrations or impacts; aggressive, polluted or corrosive atmospheres, exposure to direct solar radiation, explosive atmospheres or flammable gas.
General characteristics
Cable entry PG7, max cable diameter = 7mm
Right or left side entry, rotating the bottom.
Electrical connection Fixed screw terminals for cables with cross-sections from 0.2 to 1.5mm2
Type of contact N.O.
Dimensional, insulation and mechanical characteristics
Dimensions 74x48x40mm (sensor)
44x15x8mm (magnet)
Front protection rating IP65
Installation With supplied screws
Casing Plastic body in PC + ABS UL94 V-0

PEGO S.r.l.
Via Piacentina, 6/b - 45030 - Occhiobello (RO)
Tel: 0425 762906
www.pego.it
e-mail: info@pego.it

Documents / Resources

References

Download manual

Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.

Download Pego Expert Series, MicroP, 200MICROP01 Manual

Advertisement

Need help?

Need help?

Do you have a question about the Expert Series and is the answer not in the manual?

Questions and answers

Table of Contents