Page 1
ADDRESSABLE RAPTOR SOUNDER & SOUNDER BEACON - INSTALLATION MANUAL ADDRESSABLE RAPTOR SOUNDER & SOUNDER BEACON INSTALLATION MANUAL Final Fix Description • The Raptor addressable sounder is a large Set the device address (see address setting) weatherproof horn sounder suitable for many indoor &...
Protocol Usage The Raptor Sounder and sounder beacon work on the Zeta Fyreye II protocol only. The flasher (if fitted) can be triggered independently to the sounder, if the control panel sup- ports that function.
Page 3
One of 16 tones can be chosen for the alarm tone. Tone Description Pattern Frequency Rate 800 & 970 1Hz (500ms-500ms) BS Fire (Default Zeta tone) Alternating 800 & 970 2Hz (250ms-250ms) BS Fire Alternating 800 to 970...
Page 4
ADDRESSABLE RAPTOR SOUNDER & SOUNDER BEACON - INSTALLATION MANUAL Flasher Setting The Raptor has a 4 way dip switch for configuring the flasher. Switches 1 to 3 configure the flasher as shown below. Switch 4 is for future use. Setting 1 gives the specified flasher rating.
Check that loop is connected with correct polarity Check that sounder flying leads have been connected to the backbox. Check the panel is running the Zeta Fyreye MkII protocol Check panel`s actions (cause & effect) programming is correct. Sounder Is Not Operating...
Type B: For Outdoor Use ZRAPB/R (W) Other Technical Data: See Doc: “Addressable Raptor Product file” held by the manufacturer Zeta Alarms Limited, 72-78 Morfa Road, Swansea SA1 2EN Document No: GLT-271-7-2 Author: NRP Jones Page 8 Issue No: 008...